background image

 

1592026000 XW20K GB R2.0 08.06.2011.doc 

                       

XW60K 

1/5 

 

XW20K AND T620T - T620 – V620 – CX620 

1

 

GENERAL WARNING ......................................................................................................... 1

 

2

 

GENERAL DESCRIPTION .................................................................................................. 1

 

3

 

CONTROLLING LOADS ...................................................................................................... 1

 

4

 

SPECIAL FUNCTIONS........................................................................................................ 1

 

5

 

KEYBOARDS...................................................................................................................... 1

 

6

 

AUTOMATIC KEYBOARD LOCK (ONLY FOR T620T) ......................................................... 2

 

7

 

CONTROLLER INTERFACE ............................................................................................... 2

 

8

 

PARAMETER LIST ............................................................................................................. 2

 

9

 

DIGITAL INPUT .................................................................................................................. 3

 

10

 

INSTALLATION AND MOUNTING ....................................................................................... 4

 

11

 

ELECTRICAL CONNECTIONS............................................................................................ 4

 

12

 

TTL/RS485 SERIAL LINE .................................................................................................... 4

 

13

 

HOW TO: USE OF THE PROGRAMMING “HOT KEY” ......................................................... 4

 

14

 

ALARM SIGNALS ............................................................................................................... 4

 

15

 

TECHNICAL DATA ............................................................................................................. 4

 

16

 

CONNECTIONS.................................................................................................................. 4

 

17

 

DEFAULT SETTING VALUES ............................................................................................. 5

 

 

1

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 
cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to  water or moisture: use the controller  only  within the operating  limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2

 

GENERAL DESCRIPTION  

Model  XW20K  is  microprocessor  based  controller  suitable  for  applications  on  normal  or  medium 
temperature refrigerating units.  It has to  be connected by means  of a two-wire cable (

 1mm) at  a 

distance of up to 30 meters to the keyboard T620TT620, V620 or CX620.  
It is provided with two relay outputs to control compressor and light. It is also provided with 3 NTC or 
PTC  probe  inputs,  one  for  temperature  control,  one  to  control  the  defrost  end  temperature  of  the 
evaporator and the third to control condenser temperature or to display another temperature. 
The  HOT-KEY  output  allows  to  connect  the  unit,  by  means  of  the  external  module  XJ485-CX,  to  a 
network line ModBUS-RTU compatible such as a 

dIXEL 

monitoring units of X-WEB family. It allows 

to program the controller by means the HOT-KEY programming keyboard.  
The  instrument  is  fully  configurable  through  special  parameters  that  can  be  easily  programmed 
through the keyboard. 

3

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according to  the  temperature  measured  by  the  thermostat  probe  with  a 
positive  differential  from  the  set  point:  if  the  temperature  increases  and  reaches  set  point  plus 
differential the compressor is started and then turned off when the temperature reaches the set point 
value again. 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters Con and CoF
The relay of the second compressor is activated in parallel with the relay of the first compressor, with a 
possible delay set in the AC1 parameter. Both the compressors are switched off at the same time. 

3.2

 

FAST FREEZING 

When defrost is not in  progress, it can be activated by holding the UP key pressed for about  3 sec. 
The compressor operates to maintain the CCS set point for the time set through the CCt parameter. 
The cycle can be terminated before the end of the set time using the same activation key UP for 3 sec. 

3.3

 

DEFROST 

Defrost is performed through a simple stop of the compressor. The parameters involved are: idF, to 
control the interval between defrost cycles and MdF, which is the maximum defrost length. There are 
also two defrost modes: timed or controlled by the  evaporator’s probe (parameter dFP and P3P). At 
the end of a defrost cycle a dripping time is started; its length is set in the FSt parameter. With FSt=0 
the dripping time is disabled. 

4

 

SPECIAL FUNCTIONS 

By means of the parameter oA3, it’s possible to configure the functions  of the  light relay (22-23), as 
described in the following paragraphs: 

4.1

 

OA3 = LIG: LIGHT RELAY (FACTORY SETTING) 

By setting oA3=Lig the relay will work as light relay, it is switched on and off by the light button on the 
keyboard and is affected by status of the digital input when i1F=dor

4.2

 

OA3 = CP2 SECOND COMPRESSOR MANAGEMENT  

By  setting  oA3=CP2,  the  relay  at  terminals  22-23  will  operate  as  “second  compressor”.    It  will  be 
activated  in  parallel  with  the  relay  of  the  first  compressor,  with  a  possible  delay  set  in  the  AC1 
parameter (seconds). Both the compressors are switched off at the same time. 

4.3

 

OA3 = ONF: ON –OFF   RELAY  

By setting oA3=onF, the relay will  operate as “on-off” relay: it will be activated when the controller is 
switched on and it will be switched off when the controller is in stand-by status. 

4.4

 

OA3 = AUS: AUXILIARY RELAY 

By setting oA3=AUS, the relay 22-23 will work as auxiliary thermostat (ex. anti condensing heater). 
Parameters involved:  

-

 

ACH (cL, Ht): Kind of regulation for the auxiliary relay: Ht = heating / CL = cooling

-

 

SAA (-50÷150) Set point for auxiliary relay  

-

 

SHy (0÷25.5°C) Differential for auxiliary output.  

With ACH = CL: aux relay cut in is SAA+SHy, cut out SAA. 
With ACH = Ht: aux relay cut in is SAA-SHy, cut out SAA. 

-

 

ArP (nP, P1, P2, P3, P4) Probe for auxiliary relay  

-

 

Sdd (n, Y) Auxiliary output working during defrost 

4.5

 

OA3 = ALR: ALARM RELAY 

By setting oA3=ALr the relay will work as alarm relay, it is switched on when an alarm happens. 
Parameters involved:  

-

 

tbA (n, y) Alarm relay silencing 

-

 

AoP (cL; oP)   Alarm relay polarity 

4.6

 

OA3 = DB: NEUTRAL ZONE 

By  setting  oA3=db  the  controller  will  perform  a 
“neutral zone” regulation. 
The heating element has to be connected to the 
oA3 relay (22-23) 
If  the  temperature  increases  and  reaches  set 
point  plus  differential  (HY)  the  compressor  is 
started  and  then  turned  off  when  the 
temperature reaches the set point value again.  
If  the  temperature  decreases  and  reaches  the 
set point minus differential (HY) the oA3 output 
(heater)  is  switched  on  and  then  turned  OFF 
when  the  temperature  reaches  again  the  set 
point.   

 

 

5

 

KEYBOARDS 

T620T 

 

 

T620 

 

 

 

V620 

 

CX620 

 

 
 

 

To display and modify target set point; in programming mode it selects a parameter 
or  confirm  an  operation.  By  holding  it  pressed  for  3  sec  when  max  or  min 
temperature is displayed it will be erased. 

 

To  see  the  max  stored  temperature;  in  programming  mode  it  browses  the 
parameter codes or increases the displayed value.  
By holding it pressed for 3s the fast freezing cycle is started. 
 

 

To see the min stored temperature; in programming mode it browses the parameter 
codes or decreases the displayed value. 
 

Summary of Contents for XW20K

Page 1: ...mpressor with a possible delay set in the AC1 parameter Both the compressors are switched off at the same time 3 2 FAST FREEZING When defrost is not in progress it can be activated by holding the UP key pressed for about 3 sec The compressor operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same ac...

Page 2: ... To exit Press SET UP or wait for 15 sec without pressing any key NOTE1 if no parameter is present in the Pr1 level after the first 3 sec the noP message will be displayed Keep SET DOWN keys pushed till the Pr2 message will be displayed NOTE2 the new set value will be stored even if the procedure is exited by waiting for the time out to expire 7 7 2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO ...

Page 3: ...m is present in any case regulation restarts after AC time at minimum AC2 Compressor off with high temperature alarm of condenser n compressor keeps on working Y compressor is switched off till the alarm is present in any case regulation restarts after AC time at minimum RELAY OA3 22 23 CONFIGURATION tbA Alarm relay silencing with oA3 ALr n silencing disabled alarm relay stays on till alarm condit...

Page 4: ...10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation 14 ALARM SIGNALS Message Cause Outputs P1 Thermostat probe failure Alarm output ON Compressor output according to paramet...

Page 5: ...y nP P1 P2 P3 nP Pr2 Sdd Aux output working during defrost n Y n Pr2 ALARMS ALP Probe setting for temperature alarm P1 P2 P3 P4 P1 Pr2 ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 ALL minimum temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 AFH Temperature alarm and fan differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr2 ALd Te...

Reviews: