CONTROLS 

6.1  Minimum fan speed  

To avoid that the fan can be damaged with low voltage output, it is possible set 
a minimum voltage output (minimum speed). The range is selectable from 0 to 
50% of the power supply. 

6.2  Cut-off function  

The Cut-off function drastically reduces the output to 0V, when the voltage on 
the  load  is  lower  than  a  percentage  set  with  this  trimmer.  The  range  is 
selectable from 10 to 30% of the power supply. Example: if set to the middle 
position (15%), when the voltage on the load is lower than 15% of 230V, the 
fan immediately are stopped. 

6.3  M

AXIMUM FAN SPEED AT START UP 

(J2)

 

By closing the external jumper J2, each time that the fan restarts, it will run at 
maximum speed for 10 seconds. 

6.4  Trigger signals 

(Master / slave J3)

 

To control different loads having more than the rating plate of the instrument, 
the trigger out can be used to connect another speed controller provided with 
the trigger in terminals.  
MASTER 
By closing the 2-3 position of the jumper J3 the instrument is set as master, 
therefore the control function is repeated through terminals 5 and 6 to a slave 
instrument. 
SLAVE 
By closing the 1-2 position jumper J3 the instrument is set as slave, therefore it 
can receive the trigger signal to the terminals 7 and 8, the controller will follow 
exactly the function executed by the master instrument itself. 
When using the three phases power supply, both the Master and the Slave 
must be connected to the same phase. 

6.5  Changing the action type with current or 

voltage input models 

(J2) 

All  the  instruments  having  a  4/20mA  or  0/1Vdc  and  0/10Vdc  inputs,  can 
change  the  action  by  means  of  J2  jumper.  Jumper  closed  =  direct  action 
(condensing), jumper open = reverse action (evaporating). 
 

ANTI CONDENSING KIT (OPTIONAL)

 

This heater element, called XV –ACK, can be used to warm the air inside the 
IP55 box, in order to permit the correct functioning of the instrument when it is 
used in critical applications up to –40°C below zero. In this case connect the 
element  on  the  faston  near  the  power  supply  terminals  4  and  5.  The  order 
code for this optional heater element is DG 000001 00. 

INSTALLING AND MOUNTING 

The instruments shall be mounted on panel. The temperature range allowed 
for correct operation is 0 - 60 °C. By using the heater element XV-ACK, the 
temperature of the environment where the instrument is placed, can reach –40 
°C 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases,  excessive  dirt  or 
humidity. The same recommendations apply to probes. Let air circulate nearby 
the instrument. 

ELECTRICAL WIRING 

The instruments are provided with Kress screw terminals to connect the input 
signals  and  Faston  6.3mm  to  connect  the  power  supply  and  the  load.  The 
6.3mm faston placed on the heat sink must be connected to the ground. The 
two 6.3mm faston terminals near the power supply terminals 4 and 5, can be 
used  to  connect  the  heater  XV-ACK  when  the  temperature  of  the  outside 
environment is too low. 
Before  connecting  cables  make  sure  the  power  supply  complies  with  the 
instrument’s  requirements.  Separate  the  input  signal  cable  from  the  power 
supply cables, from the outputs and the power connections. Do not exceed the 
maximum current allowed on the output terminals. 

10  OUTPUT STATUS FOR FAULTY PROBE 

Open probe (direct action) 

0 Volt 

Short circuited probe (direct action) 

0 Volt 

Open probe (inverse action) 

230 Volt 

Short circuited probe (inverse action) 

230 Volt 

11  TECHNICAL DATA 

Housing: 

open board or IP55 box.

 

Case:

 plastic box (only for IP55 model). 

Mounting: 

panel with screw. 

 

Connections: 

KRESS terminals;  

       Faston 6.3mm for power loads. 

Power supply: 

230Vac,   10%  50/60Hz

 

Power absorption: 

1VA max. 

Maximum load:

   XV110K controls up to 1000Watt . 

 

          XV150K controls up to 5000Watt. 

Input

: NTC or 4/20mA or 0/1 and 0/10Vdc. 

Range

: depending on the probe. 

Operating  temperature

:  0 60  °C,  down  to  –40°C  with  the  XV-ACK 

Heater element. 

Storage temperature:

 -30 85 °C. 

Relative humidity: 

20 85% (not condensing). 

12  CONNECTIONS 

 

 

 

13  DEFAULT VALUES 

Input 

Action 

Set range 

Diff 

NTC 

Direct 

0 60°C 

1 30°C 

NTC 

Reverse 

-40 +10°C 

1 30°C 

4/20mA 

Direct 

4 20mA 

1 10mA 

4/20mA 

Reverse 

4 20mA 

1 10mA 

0/1Vdc 

Direct 

0 1Vdc 

0 0,5V 

0/1Vdc 

Reverse 

0 1Vdc 

0 0,5V 

0/10Vdc 

Direct 

0 10Vdc 

0 5V 

0/10Vdc 

Reverse 

0 10Vdc 

0 5V 

 

Dixell s.r.l. 