background image

dIXEL

Installing and Operating Instructions

1592007231

1592007231 XR40C-D GB r1.0 22.04.2005.doc

XR40C – XR40D

3/4

If the nPS activation in the did time is reached, switch off and on the
instrument to restart normal regulation.

 

odc

Compressor status when open door:

  

no,

 

Fan

 = normal; 

CPr, F_C

 =

Compressor OFF

OTHER
PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

= PBC probe, 

ntC = 

NTC probe.

 

dP1

First probe display

 

dP2

Second probe display

 

rEL

Software release 

for internal use.

 

Ptb

Parameter table code:

 readable only.

8.  DIGITAL INPUT (IF AVAILABLE)

The free contact digital input is programmable in five different configurations by the

i1F

” parameter.

8.1  DOOR SWITCH INPUT  (i1F = dor)

It signals the door status and the corresponding relay output status through the

odc

” parameter: 

no,

 

Fan

 = normal (any change);

CPr, F_C

 = Compressor OFF;

Since the door is opened, after the delay time set through parameter “

did

”, the

door alarm is enabled, the display shows the message “

dA

” and 

the regulation

restarts

. The alarm stops as soon as the external digital input is disabled again.

With the door open, the high and low temperature alarms are disabled.

8.2  GENERIC ALARM (i1F = EAL)

As soon as the digital input is activated the unit will wait for “

did

” time delay before

signalling the “

EAL

” alarm message. The outputs status don’t change. The alarm

stops just after the digital input is de-activated.

8.3  SERIOUS ALARM MODE (i1F = bAL)

When the digital input is activated, the unit will wait for “

did

” delay before signalling

the “

CA

” alarm message. The relay outputs are switched OFF. The alarm will stop

as soon as the digital input is de-activated.

8.4  PRESSURE SWITCH (i1F = PAL)

If during the interval time set by “

did

” parameter, the pressure switch has reached

the number of activation of  the “

nPS

” parameter, the “

CA

” pressure alarm

message will be displayed. The compressor and the regulation are stopped. When
the digital input is ON the compressor is always OFF.

If the nPS activation in the did time is reached, switch off and on the
instrument to restart normal regulation.

8.5  START DEFROST (i1F = dFr)

It starts a defrost if there are the right conditions. After the defrost is finished, the
normal regulation will restart only if the digital input is disabled otherwise the
instrument will wait until the “MdF” safety time is expired.

8.6  INVERSION OF  THE KIND OF ACTION: HEATING-
COOLING (i1F = Htr)

This function allows to invert the regulation of the controller: from cooling to
heating and viceversa.

8.7  DIGITAL INPUTS POLARITY

The digital input polarity depends on the “

i1P

” parameter.

i1P=CL

: the input is activated by closing the contact.

i1P=OP

: the input is activated by opening the contact

9.  INSTALLATION AND MOUNTING

Instrument 

XR40C

 shall be mounted on vertical panel,

in a 29x71 mm hole, and fixed using the special bracket
supplied.
To obtain an IP65 protection grade use the front panel
rubber gasket (mod. RG-C) as shown in figure.

Instrument 

XR40D

 shall be mounted on an omega DIN rail

The temperature range allowed for correct operation is 0

÷

60 °C. Avoid places

subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same
recommendations apply to probes. Let air circulate by the cooling holes.

10. ELECTRICAL CONNECTIONS

The instrument is provided with screw terminal block to connect cables with a
cross section up to 2,5 mm

2

. Before connecting cables make sure the power

supply complies with the instrument’s requirements. Separate the probe cables
from the power supply cables, from the outputs and the power connections. Do not

exceed the maximum current allowed on each relay, in case of heavier loads use a
suitable external relay.

10.1 PROBE 

CONNECTION

The probes shall be mounted with the bulb upwards to prevent damages due to
casual liquid infiltration. It is recommended to place the thermostat probe away
from air streams to correctly measure the average room temperature. Place the
defrost termination probe among the evaporator fins in the coldest place, where
most ice is formed, far from heaters or from the warmest place during defrost, to
prevent premature defrost termination.

11.  HOW TO USE THE HOT KEY

11.1  HOW TO PROGRAM A HOT KEY FROM THE
INSTRUMENT (UPLOAD)

1. 

Program one controller with the front keypad.

2. When 

the 

controller 

is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL"

message appears followed a by flashing 

“End”

3. Push 

SET”

 key and the 

End

 will stop flashing.

4. 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again.

NOTE

: the “

Err

” message is displayed for failed programming. In this case push

again 

o

 key if you want to restart the upload again or remove the “

Hot key

” to

abort the operation.

11.2  HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)

1. 

Turn OFF the instrument.

2. 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn

the Controller ON.

3. Automatically 

the 

parameter list of the 

“Hot Key”

 is downloaded into the

Controller memory, the “

doL

” message is blinking followed a by flashing

“End”.

4.  After 10 seconds the instrument will restart working with the new

parameters.

5. Remove 

the 

“Hot Key”.

.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the

unit off and then on if you want to restart the download again or remove the “

Hot

key

” to abort the operation.

12. ALARM SIGNALS

Message

Cause

Outputs

“P1”

Room probe  failure

Compressor output according
to par. “Con” and “COF”

“P2”

Evaporator probe  failure

Defrost end is timed

“HA”

Maximum temperature alarm

Outputs unchanged.

“LA”

Minimum temperature alarm

Outputs unchanged.

“dA”

Door open

Regulation restarts

“EA”

External alarm

Output unchanged.

“CA”

Serious external alarm (i1F=bAL)

All outputs OFF.

“CA”

Pressure switch alarm (i1F=PAL)

All outputs OFF

12.1 ALARM 

RECOVERY

Probe alarms “

P1

” and “

P2

” start some seconds after the fault in the related probe;

they automatically stop some seconds after the probe restarts normal operation.
Check connections before replacing the probe.
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat

temperature returns to normal values and when defrost starts.
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is

disabled.
Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument.

13. TECHNICAL DATA

Housing: 

self extinguishing ABS.

Case: XR40C 

frontal 32x74 mm; depth 60mm;

XR40D 

4 DIN modules 70x85 mm; depth 61mm

Mounting: XR40C 

panel mounting in a 71x29mm panel cut-out

XR40D

 DIN RAIL mounted in a omega (3) din rail

Protection: 

IP20.

Frontal protection: XR40C 

IP65 with frontal gasket RG-C (optional).

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring.

Power supply: 

according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;

230Vac 

±

10%, 50/60Hz, 110Vac 

±

10%, 50/60Hz

Power absorption: 

3VA max

Display

: 3 digits, red LED, 14,2 mm high.

Inputs

: 2 NTC or PTC probes.

Digital input: 

free contact

Relay outputs

compressor: 

SPDT relay 8(3) A, 250Vac or

SPST relay 20(8)A; 250Vac

defrost: 

SPDT relay 8(3) A, 250Vac

Data storing

: on the non-volatile memory (EEPROM).

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A.

Operating temperature: 

0÷60 °C.

Storage temperature: 

-30÷85 °C.

Relative humidity:

 20

÷

85% (no condensing)

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F)

Reviews: