background image

Dixell

 

Installing and Operating Instructions 

rel.1.0 - cod.

 

1592008200

 

 

1592008200 XR110C   GB 

XR110C with built in RS485 

1/4 

XR110C  with built-in RS485 

CONTENTS 

 
1. GENERAL 

WARNING _________________________________________________________________ 1 

2. General 

description ___________________________________________________________________ 1 

3. Controlling 

loads______________________________________________________________________ 1 

4. 

Front panel commands_________________________________________________________________ 1 

5. 

List of Parameters ____________________________________________________________________ 2 

6. Digital 

inputs_________________________________________________________________________ 3 

7. 

Installation and mounting _______________________________________________________________ 3 

8. Electrical 

connections__________________________________________________________________ 3 

9. 

RS485 Serial communication____________________________________________________________ 3 

10.  Use of the programming “HOT KEY “ _____________________________________________________ 3 
11. Alarm 

signals ________________________________________________________________________ 3 

12. Technical 

data _______________________________________________________________________ 4 

13. Connections _________________________________________________________________________ 4 
14.  Default setting values__________________________________________________________________ 4 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy 
and quick reference. 

 

The instrument shall not be used for purposes different from those described 
hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits 
avoiding sudden temperature changes with high atmospheric humidity to prevent  
formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be 
opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to 
“Dixell s.r.l.” (see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical 
Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far 
enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. 
FT1) in parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

XR110C is connectable to the XJ500 monitoring system through the two terminals of serial 
port RS485. 
Model  XR110C, 32 x 74 mm format, is a single stage temperature controller suitable for 
applications  in the field of refrigeration or heating. It’s provided with a relay output and a 
PTC or NTC probe inputs configurable by the User. 

3.

 

CONTROLLING LOADS 

3.1

 

TYPE OF REGULATION  

The regulation is performed according to the temperature measured by the probe. 
The instruments are provided with the CH  programmable parameter which enables the 
user to set the regulation both for heating or cooling applications: 
· 

 CH = cL : cooling applications  

·  

CH = Ht : heating applications 

3.2

 

CH=CL : COOLING 

 

 

 

The regulation is performed according to the temperature measured by the thermostat 
probe with a positive differential from the set point: if the temperature increases and 
reaches set point plus differential the compressor is started and then turned off when the 
temperature reaches the set point value again. 

3.3

 

CH = HT: HEATING  

 

 

The Hy value is automatically set under the Set Point. If the temperature decreases and 
reaches set point minus differential the regulation output is activated and then turned off 
when the temperature reaches the set point value again. 
N.B. :In case of fault in the thermostat probe the start and stop of the compressor are 
timed through parameters “COn” and “COF”. 

4.

 

FRONT PANEL COMMANDS 

 

 

:To display target set point; in programming mode it selects a parameter or 
confirm an operation.  

 

By holding it pressed for 5s the instrument Stand By started( If it is enable) 

 

By holding it pressed for 3s when max or min temperature is displayed it will 
be erased. 

 

 

:To see the max. stored temperature; in programming mode it browses the 
parameter codes or increases the displayed value. By holding it pressed for 
3s the fast freezing  cycle is started 

 
 

:To see the min stored temperature; in programming mode it browses the 
parameter codes or decreases the displayed value. By holding it pressed for 
3s the auxiliary relay is switched ON or OFF ( If it is configured) 

 

KEY COMBINATIONS: 

          +   

  

To lock & unlock the keyboard

 
             + 

To enter in programming mode. 

 
             +   

      

To return to the room temperature display

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON Compressor 

enabled 

 

FLASHING  - Programming Phase (flashing with LED 1) 

- Anti-short cycle delay enabled 

LED1 

FLASHING  Programming Phase (flashing with LED  ) 

  

ON 

- ALARM signal 
- In “Pr2” indicates the parameter is also present in “Pr1” 

4.2

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum 
temperature recorded. 

3. 

 

By pressing the 

n

 key or waiting for 5s the normal display will be 

  

restored. 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  
temperature recorded. 

3. 

 

By pressing the 

o

 key or waiting for 5s the normal display will be 

  

restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 

 

 

LED 1 