20. STANDARD VALUES OF THE PARAMETERS.
Label
Value
Level Description
Range
SEt
3
- - -
Set point
-50.0 to 50.0°C
Pr2
- - -
Pr1
not used
-
Hy
2.0
Pr1
Compressor hysteresis
0.1 to 12.0°C
AC
1
Pr2
Compressor restart delay
0 to 30 min
PAU
0
Pr2
Time of stand by
0 to 60 min
PFt
15
Pr2
Maximum acceptable duration of power failure
0 to 250 min
Con
15
Pr2
Compressor ON time with faulty probe
0 to 250 min
COF
10
Pr2
Compressor OFF time with faulty probe
0 to 250 min
rPo
0.0
Pr2
Thermostat probe calibration
-12.0 to 12.0°C
EPP
YES
Pr2
Evaporator probe presence
n; Y
EPo
0.0
Pr2
Evaporator probe calibration
-12.0 to 12.0°C
i1P
YES
Pr2
Insert probe 1 presence
n; Y
i1o
0.0
Pr2
Insert probe 1 calibration
-12.0 to 12.0°C
i2P
n
Pr2
Insert probe 2 presence
n; Y
i2o
0
Pr2
Insert probe 2 calibration
-12.0 to 12.0°C
i3P
n
Pr2
Insert probe 3 presence
n; Y
i3o
0
Pr2
Insert probe 3 calibration
-12.0 to 12.0°C
rEM
iPt
Pr2
Probe selection to stop chilling cycle
iPt; rPt
CF
°C
Pr2
Temperature measurement unit
°C; °F
rES
dE
Pr2
Resolution (for °C):
in; dE
Lod
rP
Pr2
Upper display view
rP;EP
rEd
rP
Pr2
View for rep
rP; EP; tiM; i1P; i2P; i3P
d1P
cL
Pr2
Door switch input polarity
OP; CL
odC
F-C
Pr2
Loads locked by door switch
no; FAn; CP; F-C
doA
5
Pr2
Open door alarm delay
da 0 a 254 min, 255=nu
dLc
Y
Pr2
Cycle block with open port
n; Y
rrd
Y
Pr2
Regulation restart after door open alarm
n; Y
d2F
EAL
Pr2
Second digital input function
EAL; bAL, ACy
d2P
cL
Pr2
Digital input polarity
OP; CL
did
5
Pr2
Time delay for digital input alarm
0 to 255min
oA1
tMr
Pr2
Configuration of first auxiliary relay
ALL; Lig; AUS; C2; tMr
oA2
ALL
Pr2
Configuration of second auxiliary relay
ALL; Lig; AUS; C2; tMr
oA3
Lig
Pr2
Configuration of third auxiliary relay
ALL; Lig; AUS; C2; tMr
2CH
C1
Pr2
Compressor setting during the holding
C1; C2; 1C2
OAt
3
Pr2
Second compressor switching on delay
0 to 255 min
OAS
0.1
Pr2
Set point for second compressor
-50.0 to 50.0°C
OAH
2.0
Pr2
Differential for second compressor
-12.0 to 12.0°C
OAi
rP
Pr2
Probe selection for second compressor
rP; EP; i1P; i2P; i3P
OSt
0
Pr2
Auxiliary output timer
0 to 255 min
OSS
0.0
Pr2
Output set point delta
-50.0 to 50.0°C
OSH
2.0
Pr2
Differential for auxiliary output
-12.0 to 12.0°C
OSi
rP
Pr2
Probe selection for auxiliary output
rP; EP; i1P; i2P; i3P
tdF
rE
Pr2
Defrost type
rE; in
idF
06:00
Pr2
Interval between defrost cycles
0.1 to 24h00min
dtE
8
Pr2
Defrost termination temperature
-50.0 to 50.0°C
MdF
20
Pr2
Maximum length for defrost
0 to 255 min
dFd
rt
Pr2
Temperature displayed during defrost
rt; it; SET; dEF
Fdt
0
Pr2
Drip time
0 to 60 min
dAd
20
Pr2
Temperature display time after defrost
0 to 120 min
FnC
c_n
Pr2
Fan operating mode during hold
o-n; C1n; C2n; Cn; o-Y; C1Y;
C2Y; Cy