4/4

“P3”

Auxiliary probe failure

Alarm output ON; Other outputs unchanged

“HA”

Maximum temperature alarm

Alarm output ON; Other outputs unchanged

“LA”

Minimum temperature alarm

Alarm output ON; Other outputs unchanged

“EE”

Data or memory failure

Alarm output ON; Other outputs unchanged

“dA”

Defrost timeout alarm

Alarm output ON; Other outputs unchanged

“dAL”

Door switch alarm

Alarm output ON; Other outputs unchanged

“EAL”

External alarm

Alarm output ON; Other outputs unchanged

“BAL”

Serious external alarm

Alarm output ON; Other outputs OFF

“PAL”

Pressure switch alarm

Alarm output ON; Other outputs OFF

The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing.
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for about
3s.

SILENCING BUZZER / ALARM RELAY OUTPUT
If “tbA = y”, once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key.
If “tbA n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers.

“EE” ALARM
The 

 instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a

failure in the memory data occurs. In such cases the alarm output is enabled.

ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal
operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal
values or when the defrost starts.
Door switch alarm “dA”  stop as soon as the door is closed.
External alarms “EAL”, “BAL”  stop as soon as the external digital input is disabled “PAL” alarm is recovered by
switching OFF the instrument.

TECHNICAL DATA

Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 76mm
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm.

Distance between the holes 165mm

Protection: IP20.
Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston

Power supply: 230Vac or. 110Vac 

±

 10%

Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 3 NTC probes
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 16(3) A, 250Vac
fans: relay SPST 8(3) A, 250Vac
defrost: relay SPST 8(3) A, 250Vac
alarm: SPST relay 8(3) A, 250Vac
auxiliary: SPST relay 16(3) A, 250Vac
Other output : alarm buzzer
Serial output : TTL standard
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20

÷

85% (no condensing)

Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C):  ±0,5 °C ±1 digit

CONNECTIONS

XW270L/XW271L

(*) In XW271L, AUX is an anticondensing heater

 

  

C

o

mmo

n

D

o

o

r sw

it

ch

D

igit

a

l in

p. 

De

f.

Di

sp

la

y

R

oom

;:/;:/

ALARM

AUX

(*)

Def.

Comp

Fan

Light

Line

Ne

u

tr

a

l

         

   

20A

250Vac

MA X

20A

8A

250Vac

16A

250Vac

8A

250Vac

8A

250Vac

16A

250Vac

DEFAULT SETTING VALUES

Label Name

  Range

Default

Level

REGULATION

°C/°F

XW270L XW271L

Set

Set point

LS÷US

-5

Pr1

Pr1

Hy

Differential

0,1÷25,5 °C / 1÷45°F

2

Pr1

Pr1

LS

Minimum set point

 -50,0°C÷SET / -58°F÷SET

-30

Pr2

Pr2

US

Maximum set point

SET ÷ 110°C / SET ÷ 230°F

20

Pr2

Pr2

OdS

Outputs activation delay at start up

0÷255 min.

1

Pr2

Pr2

AC

Anti-short cycle delay

0÷30 min.

1

Pr1

Pr1

CCt

Compressor ON time during fast freezing

0 ÷ 23h 50 min.

0

Pr2

Pr2

COn

Compressor ON time with faulty probe

0÷255 min.

15

Pr2

Pr2

COF

Compressor OFF time with faulty probe

0÷255 min.

30

Pr2

Pr2

DISPLAY

CF

Temperature measurement unit

°C ÷ °F

°C

Pr2

Pr2

rES

Resolution (integer/decimal point)

in ÷ de

de

Pr1

Pr1

Lod

Local display

P1 ÷ 1r2

P1

Pr2

Pr2

Red

Remote display

P1 ÷ 1r2

P1

Pr2

Pr2

DEFROST

tdF

Defrost type

rE,  rT,  in

rE

Pr1

Pr1

EdF

Defrost mode

In, Sd

In

Pr2

Pr2

SdF

Set point for SMART DEFROST

-30 ÷ +30°C / -22÷+86°F

0

Pr2

Pr2

dtE

Defrost termination temperature
(1°Evaporator)

-50,0÷110°C/ -58÷230°F

8

Pr1

Pr1

IdF

Interval between defrost cycles

1÷120h

6

Pr1

Pr1

MdF

(Maximum) length for 1° defrost

0÷255 min.

30

Pr1

Pr1

dFd

Displaying during defrost

rt, it, SEt, dEF, dEG

it

Pr2

Pr2

dAd

MAX display delay after defrost

0÷255 min.

30

Pr2

Pr2

Fdt

Draining time

0÷60 min.

0

Pr2

Pr2

dPO

First defrost after start up

n ÷ y

n

Pr2

Pr2

dAF

Defrost delay after fast freezing

0 ÷ 23h 50 min.

2

Pr2

Pr2

FANS

FnC

Fans operating mode

C-n, C-y, O-n, O-y

O-n

Pr2

Pr2

Fnd

Fans delay after defrost

0÷255 min.

10

Pr2

Pr2

FSt

Fans stop temperature

-50,0÷110°C/ -58÷230°F

2

Pr2

Pr2

ALARMS

ALC

Temperature alarms configuration

rE÷Ab

rE

Pr2

Pr2

ALU

MAXIMUM temperature alarm

-50,0÷110°C/ -58÷230°F

10

Pr1

Pr1

ALL

minimum temperature alarm

-50,0÷110°C/ -58÷230°F

10

Pr1

Pr1

AFH

Temperature alarm and fan differential

0,1÷25,5 °C / 1÷45°F

2

ALd

Temperature alarm delay

0÷255 min.

15

Pr2

Pr2

dAO

Delay of temperature alarm at start up

0 ÷ 23h 50 min.

1,3

Pr2

Pr2

EdA

Alarm delay at the end of defrost

0÷255 min.

30

Pr2

Pr2

dot

Delay of temperature alarm after closing
the door

0÷255 min.

15

Pr2

Pr2

dOA

Open door alarm delay

0÷255 min.

15

Pr2

Pr2

tBA

Alarm relay silencing

y ÷ n

y

Pr2

Pr2

nPS

Pressure switch activation number

0÷15

0

Pr2

Pr2

ANALOGUE INPUTS

Ot

Thermostat probe calibration

-12,0÷12,0°C / -21÷21°F

0

Pr1

Pr1

OE

Evaporator probe calibration

-12,0÷12,0°C / -21÷21°F

0

Pr2

Pr2

O3

Auxiliary probe calibration

-12,0÷12,0°C / -21÷21°F

0

Pr2

Pr2

P2P

Evaporator probe presence

n ÷ y

y

Pr2

Pr2

P3P

Auxiliary probe presence

n ÷ y

n

Pr2

Pr2

HES

Temperature increase during the Energy
Saving cycle

-30÷30°C / -22÷86°F

0

Pr2

Pr2

DIGITAL INPUTS

Odc

Open door control

no, Fan, CPr, F_C

Fan

Pr2

Pr2

I1P

Door switch polarity

CL÷OP

CL

Pr2

Pr2

I2P

Configurable digital input polarity

CL÷OP

CL

Pr2

Pr2

i2F

Digital input configuration

EAL, bAL, PAL, dFr,

AUS, ES, OnF

EAL

Pr2

Pr2

dId

Digital input alarm delay

0÷255 min.

5

Pr2

Pr2

SAA

Set point for anti-condensing heater

-50,0÷110°C/ -58÷230°F

-20.0

- - -

Pr2

OTHER

Adr

Serial address

0÷247

1

Pr1

Pr1

rEL

Software release

- - -

1.0

Pr2

Pr2

Ptb

Map code

- - -

- - -

Pr2

Pr2

Prd

Probes display

Pb1÷Pb3

- - -

Pr2

Pr2

Pr2

Access parameter list

- - -

- - -

Pr2

Pr2

Dixell S.p.A. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 - 

(PDLOGL[HOO#GL[HOOFRP  KWWSZZZGL[HOOFRP

Summary of Contents for Wing XW270L

Page 1: ... 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuously but not during defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC O n fans will switch ON and OFF with the compressor and run du...

Page 2: ...pending on the evaporator temperature and dtE value in hot gas Compressor and defrost relays ON EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smartfrost mode The time IdF interval between defrosts is increased only when the compressor is running even non consecutively and only if the evaporator temperature is less than the value in SdF set point for SMARTFROS...

Page 3: ... The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact INSTALLATION AND MOUNTING Instruments XW270L XW271L shall be mounted on vertical panel in a 150x31 mm hole and fixed using two screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG L The...

Page 4: ...mmon Door switch Digital inp Def Display Room ALARM AUX Def Comp Fan Light Line N eutral 20A 250Vac MAX 20A 8A 250Vac 16A 250Vac 8A 250Vac 8A 250Vac 16A 250Vac DEFAULT SETTING VALUES Label Name Range Default Level REGULATION C F XW270L XW271L Set Set point LS US 5 Pr1 Pr1 Hy Differential 0 1 25 5 C 1 45 F 2 Pr1 Pr1 LS Minimum set point 50 0 C SET 58 F SET 30 Pr2 Pr2 US Maximum set point SET 110 C ...

Reviews: