background image

dIXEL

 

Installing and Operating Instructions 

             cod. 

1592009520

 

 

1592009520 XW260K GB a4_rel.1.0 25.10.2000.doc 

                       

XW260 

2/5 

 

value; 

2. 

The SET LED start blinking; 

3. 

To change the Set value push the 

or

 n

 arrows within 10s. 

4. 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

4.6

 

TO START A MANUAL DEFROST  

 

 
1. Push 

the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

 
1.  Enter the Programming mode by pressing the Set and DOWN key 

for few seconds (

 and 

 start blinking). 

 
2. 

The instrument will show the first parameter present in “Pr1” 

 
 
 
 

4.8

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

SET

” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

or

 n

 to input the security code in the flashing digit; confirm the figure by pressing “

SET

”. 

The security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET

” on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN 
keys within 30 seconds. 
 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

“SET”

 + 

à

When a parameter is present in “Pr1” LED 

 is on. 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

or

 n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

è

 or 

à

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

and

 n

 keys pressed together for more than 3 s the 

and

 n

 

keys. 

2.  

The “POF” message will be displayed and the keyboard is locked. At this point it is 
only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

and

 n

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 

 

By pushing the 

ON/OFF

 key, the instrument shows “OFF” for 5 sec. and the ON/OFF 

LED is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped; 
if a monitoring system is connected, it does not record the instrument data and alarms. 

N.B. During the OFF status the Light and AUX buttons are active. 

 

4.12

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr2

” level. 

2. 

Select “

Prd

” parameter with 

or

 n

3. 

Press the “

SET

” key to display “

Pb1” 

label alternate with Pb1 value. 

4. 

Use 

and

 n

 keys to display the other probe values.  

5. 

Press “

SET

” to move to the following parameter. 

5.

 

PARAMETER LIST 

REGULATION 
Hy Differential: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. 

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the 
temperature reaches the set point. 

LS  Minimum set point limit: 

(-50,0°C

÷

SET; -58°F÷SET) Sets the minimum acceptable value for the 

set point. 

US  Maximum set point limit: 

(SET

÷

110°C; SET÷230°F) Set the maximum acceptable value for set 

point. 

OdS  Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter. (AUX 
and Light can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following restart. 

CCt Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be 

used, for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is active in 

case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off in 

case of faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF  Temperature measurement unit:

 °C = Celsius; °F = Fahrenheit . When the measurement unit is 

changed the SET point and the values  of the regulation parameters have to be modified

 

rES  Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

de

 = 0,1°C 

in

 = 1 °C  

Red  Remote display : 

select which probe is displayed by the remote display (

T620

)

  

P1

 = Thermostat probe 

P2

 = Evaporator probe 

P3

 = auxiliary probe 

1r2

 = difference between P1 and P2 (P1-P2) 

 

DEFROST 
tdF   Defrost type:  

rE

 = electrical heater (Compressor OFF) 

rT

 = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending 

on the evaporator temperature and “dtE” value. 

in

 = hot gas (Compressor and defrost relays ON) 

EdF Defrost mode:

  

 

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

 = 

Smartfrost mode

. The time IdF (interval between defrosts) is increased only when the 

compressor is running (even non consecutively) and only if the evaporator temperature is less than 
the value in "

SdF

” (set point for SMARTFROST).  

SdF  Set point for SMARTFROST

: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the IdF 

counting (interval between defrosts) in SMARTFROST mode. 

 dtE   Defrost termination temperature:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator 

probe is present) sets the temperature measured by the evaporator probe which causes the end of 
defrost. 

IdF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the 

defrost duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for 

defrost. 

dFd   Display during defrost:  
 rt

 = real temperature;  

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 dEG

 = “dEG” label;

 

dAd  Defrost display time out:

 (0

÷

255 min) Sets the maximum time between the end of defrost and the 

restarting of the real room temperature display. 

Fdt Drain down time:

 (0÷60 min.) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops 
that might have formed due to defrost.

 

dPO First defrost after start-up:   
 y 

= Immediately;  

n

 = after the IdF time 

dAF  Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, the first defrost 

will be delayed for this time. 

 

FANS 
FnC  Fan operating mode: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end and evaporator fans 

start.

 

FSt Fan stop temperature:

 (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator 

probe, above which the fan is always OFF. 

 

ALARMS 
ALC  Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:

  

 

ALC= rE, 0 

÷

 

50°C or 90°F 

 

ALC= Ab, ALL 

÷

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting:

 

 

ALC = rE , 0 

÷

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

÷

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH Temperature alarm and fan differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for 

temperature alarm set point and fan regulation set point, always positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection of 

the temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm delay at the end of defrost: 

(0

÷

255 min) Time interval between the detection of the 

temperature alarm condition at the end of defrost and the alarm signalling. 

dot   Delay of temperature alarm after closing the door : 

(0

÷

255 min) Time delay to signal the 

temperature alarm condition after closing the door. 

doA   Open door alarm delay:

(0÷255 min) delay between the detection of the open door condition and its 

alarm signalling: the flashing message “

dA

” is displayed. 

nPS  Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL). 

 

PROBE INPUTS 
Ot  Thermostat probe calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the 

thermostat probe. 

OE    Evaporator  probe  calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

evaporator probe. 

O3  Auxiliary probe calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

evaporator probe. 

P2P  Evaporator probe presence:  

n

= not present: the defrost stops only by time; 

y=

 present: the defrost stops by temperature and 

time. 

P3P  Auxiliary probe presence: n

= not present; 

y=

 present. 

HES  Temperature increase during the Energy Saving cycle :

 (-30,0°C 

÷

 30,0°C / -22÷86°F) sets the 

increasing value of the set point during the Energy Saving cycle.  

 

 

 

DIGITAL INPUTS 
odc  Compressor and fan status when open door:

  

Summary of Contents for WING XW260K

Page 1: ...me activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is control by means of parameter EdF EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temper...

Page 2: ...1 and P2 P1 P2 DEFROST tdF Defrost type rE electrical heater Compressor OFF rT thermostat defrost During the defrost time MdF the heater switches On and OFF depending on the evaporator temperature and dtE value in hot gas Compressor and defrost relays ON EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smartfrost mode The time IdF interval between defrosts is in...

Page 3: ...igital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING T620 keyboard shall be mounted on vertical panel in a 150x31 mm hole and fixed using two screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG L Power module XW260K...

Page 4: ...Optional output buzzer Power module XW260K Case OS open board 132x 94 mm height 40mm OA open board with aluminium protection 176x 123mm height 52mm GS case 155x114 height 70mm Self extinguishing ABS IP55 PS case 147x110 height 47mm Self extinguishing ABS IP55 UL approved Connections Screw terminal block 2 5 mm2 heat resistant wiring and 6 3mm Faston Power supply 230Vac or 110Vac 10 Power absorptio...

Page 5: ...UE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 O3 Auxiliary probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 P3P Auxiliary probe presence n y n Pr2 HES Temperature increase during the Energy Saving cycle 30 30 C 22 86 F 0 Pr2 DIGITAL INPUTS Odc Open door control No Fan CPr F_C Fan Pr2 ...

Reviews: