Operating manual 

cod. 1592

cod. 1592

cod. 1592

cod. 1592017

017

017

017050

050

050

050    

 

1592017050  XLR470 GB r1.0 24.05.07.doc 

XLR470 

5/18 

6.

 

CONTROL OF EVAPORATOR FANS FOR SECTION 2 

Section 2 has 1 relay to control evaporator fan (26-27)   
The fan control mode is selected by means of the “

FnC2

” parameter: 

FnC2=C-n

  

fans will switch ON and OFF with the compressor 2and

 not run

 during defrost

:

FnC2= O-n

 

 fans will run continuously, but not during defrost  

 

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd2” parameter. 

FnC1=C-y

  

fans will switch ON and OFF with the compressor 2 and 

run

 during defrost; 

FnC1=O-y

  

fans will run continuously also during defrost 

 

An additional parameter “

FSt2

” provides the setting of temperature, detected by the evaporator probe 2, above which the fans are always OFF. This 

can be used to make sure circulation of air only if his temperature is lower than set in “FSt2”. 
 

7.

 

DISPLAY 

 

1.3

 

THE KEYBOARD 

 

To display and modify target set point 1. During programming it selects a parameter or it confirms a value. 

 

To display and modify target set point 2 

 

in programming mode it browses the parameter codes or decreases the displayed value. By holding it pressed for 3s the defrost for 
section 1  is started 

 

In  programming  mode  it  browses  the  parameter  codes  or  increases  the  displayed value. By holding it pressed for 3s the defrost for 
section 2 is started

 

It activates light 1 

 

It activates light 2 

 

Section 1 Stand-by 

 

Section 2 Stand-by 

 

KEYS COMBINATIONS 

Summary of Contents for COOL MATE XLR470

Page 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Page 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Page 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Page 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Page 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Page 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Page 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Page 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Page 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Page 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Page 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Page 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Page 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Page 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Page 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Page 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Page 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Page 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Reviews: