background image

dIXEL

 

Installing and Operating Instructions 

1598029050

 

 

1598029050 XW40L NFR GB r1.0 11.07.2008.doc 

XW40L 

2/3 

6.5.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” 
(user level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.6

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the 

UP

 +  

DOWN

 keys. 

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it will be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.7

 

TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

 keys, till the 

“Pon” 

message will be 

displayed. 

6.8

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the “

o

” key pressed for about 3 

seconds. The compressor operates to maintain the “

ccS

” set point for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

 

6.9

 

THE ON/OFF FUNCTION 

 

 

With “

onF = oFF

”, pushing the 

ON/OFF

 key, the instrument is switched off. The 

“OFF” 

message is displayed. In this configuration, the regulation is disabled.  
To switch the instrument on, push again the ON/OFF key. 

 

WARNING: Loads connected to the normally closed contacts of the relays are always 

supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

REGULATION 
Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN 

is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set 
point. 

LS  Minimum set point:

 (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 

US Maximum set point: 

(SET÷110°C/ SET÷230°F). Set the maximum value for set point. 

Ot  Thermostat probe calibration

: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Evaporator probe presence: n

= not present: the defrost stops by time; 

y=

 present: the defrost 

stops by temperature. 

OE Evaporator probe calibration:

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the evaporator probe. 

OdS Outputs activation delay at start up:

 (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC  Anti-short cycle delay

: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

CCt Compressor ON time during continuous  cycle: 

(0.0÷24.0h; res. 10min) Allows to set the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 
used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: 

(-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF Temperature measurement unit: 

 

°C=

Celsius; 

°F

=Fahrenheit. WARNING: When the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

DEFROST 
tdF   Defrost type

: EL = electrical heater; in = hot gas 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator 
probe, which causes the end of defrost. 

IdF  Interval between defrost cycles

: (0÷120h) Determines the time interval between the 

beginning of two defrost cycles. 

MdF  (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not evaporator probe: timed 

defrost) it sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dFd  Temperature displayed during defrost

: (

rt

 = real temperature; 

it

 = temperature at defrost 

start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd MAX display delay after defrost

: (0÷255min). Sets the maximum time between the end of 

defrost and the restarting of the real room temperature display. 

Fdt Drip time

: (0

÷

120 min) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 
drops that might have formed due to defrost. 

dPo  First defrost after start-up

: (y = immediately; n = after the IdF time) 

dAF Defrost delay after continuous cycle

: (0

÷

23.5h) time interval between the end of the fast 

freezing cycle and the following defrost related to it. 

ALARMS 
ALC  Temperature alarms configuration:

 (Ab; rE) 

 

Ab

= absolute temperature: alarm temperature is given by the ALL or ALU values.  

rE

 = 

temperature alarms are referred to the set point. Temperature alarm is enabled when the 
temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET °C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at start-up

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

OTHER 
Adr   Serial  address

 (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

rEL Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the external 
TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 

compatible  such as the  X-WEB500/3000/300. 

9.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the dedicated 
connector. 

 

 

To connect the X-REP to the 
instrument the following 
connectors must be used 
CAB/REP1(1m), CAB/REP2 
(2m), CAB/REP5 (5m), 

10.

 

INSTALLATION AND MOUNTING 

The controller 

XW40L

, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 

screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-

L). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong 
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 
Let the air circulate by the cooling holes. 

 

10.1

 

CUT OUT 

 

10.2

 

STEEL FINISHING MOUNTING  

1

1

2

2

3

3

4

4

RG-LX gascke

(optional)

 

11.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 
2,5 mm

for the digital and analogue inputs. Relays and power supply have a Faston connection 

(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power 
supply complies with the instrument’s requirements. Separate the probe cables from the power 
supply cables, from the outputs and the power connections. Do not exceed the maximum current 
allowed on each relay, in case of heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

11.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure the average room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

Reviews: