background image

 

Installation (Read the IMPORTANT SAFETY REQUIREMENTS)

 

isolation switch

The equipment must be mounted on a DIN rail style DIN EN 50022 inside a plastic 

or metal enclosure with a protection level >= IP65. All wiring must be secured. Max cable 
sizes 2.5 mm. Connection via two-part screw terminals. 

      ELECTRICAL CONNECTION - Ensure the supply is isolated before carrying out any installation or wiring. This equipment must be 

installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of 
installation. 

CH1 Input 

CH2 Input 

CH2 Output 

CH1 Output 

USB
CPU

Power Supply

USB

SUPPLY
(20 to 240) V dc 50/60 Hz
(20 to 240) V dc
Max Power 3W

S1 -

S2 +

205

206

207

208

105

106

107

108

104

103

102

101

204

203

202

201

INPUTS

Thermocouple

203

103

204

104

+

-

RTD

202

102

203

103

203

103

201

101

Slide Wire

208

108

OUTPUTS

Vdc

LOAD

207

107

External Powered mA

+

-

207

107

205

105

Internal Powered mA

LOAD

207

107

Vout

206

106

Voltage Output

+

-

205

105

201

101

204

104

202

102

+

Input Connections For cable length >3 metres use screen or twisted pair cables. Maximum cable run 30 metres.

Output connections for cable length >3 metres use screen or twisted pair cables. For current outputs max cable run 1000 metres, Voltage 
output 30 metres. 

Supply maximum cable run 30 metres if using a DC supply. As stated in the IMPORTANT SAFETY REQUIREMENTS the supply must be fused with 
a 1 A (T) fuse and provision provided to isolate the circuit when hazardous voltages are being switched. 

MT-KOS1720_EN_20181217 

 

 

 

 

 

 

 

 

 

 

            30727725

Ambient Range

+ 70 °C Max

- 20 °C Min

Ø 3mm