background image

Ø 3mm

Screw Driver

20

20

20

20....000 

000 

000 

000 

Digital mA meter

Power supply (10 to 30) Vdc

Resistor Decade box

User adjust function allows manual adjustment of the output current, 

this  is  useful  for  minor  calibration  adjustment  or  trimming  out  any 

sensor error, ± 5% of range adjustment is available at both offset and 

span.  Raise and lower buttons are provided on the front panel of the 

transmitter, accessed using a 3 mm flat blade screw driver. Insert the 

screw  driver  into  the  appropriate  slot  to  operate  the  button.  The 

button has a click action. 

METHOD

1.0   In USBSPeedLink software  set the  “Buttons”  drop  box  to 

trim (this is the default setting).

Connect    transmitter  to  a  suitable  Resistor  decade  box  or 

sensor. Connect output to a dc supply, connecting a digital mA 

current meter in series  with  the output.  Turn  supply on, set 

input to either offset or span calibration point. 

+

-

20

20

20

20 .

...000 

000 

000 

000 

+

-

SEM1605P

or

23.0  Adjust 

output 

current  by  pressing 

either the raise or lower 

button,  single  click  to 

step  advance  ,  or  press 

continuously  to  auto 

advance.

Raise

Lower

34.0  Once  adjust  is 

complete 

allow 

30 

seconds  with  no  button 

press, the transmitter will 

time  out  and  return  to 

normal operation.

> 30 s

The 

transmitter 

will 

automatically  detect  the 

correct  adjust  point  (offset 

or  span)  based  on  the 

output current drive. Offset 

will  be  adjusted  when  the 

current   is between (3.8 to 

6)  mA,    span  when  the 

current  is  between  (18  to 

22)  mA.  No  trim  action 

occurs at any other current.

offset

span

3.8

6

18

22 mA

 or sensor

ADJUST

STATE

ADJUST

STATE

ADJUST

STATE

Button Configuration options.

The 

KOS

1605P has three options selectabe in the USB Speed Link software, Trim, Range and off

Ω

Ω

Ø 3mm

Screw Driver

Power supply (10 to 30) Vdc

Resistor Decade box

User range function allows manual adjustment of the 4 mA and 20 mA 

output range in relation to the input value.

Method  In USBSPeedLink software set the “Buttons” drop box 

to active range (this is not the default setting).

1.0 Connect the resistor decade box or the input sensor to the 

SEM1605P using the three connection terminals.  Connect the 

SEM1605P to a (10 to 30) VDC power supply, a digital ammeter 

connected  in  series  with  the 

KOS

1605P  will  be  useful  to 

monitor the (4 to 20) mA current but is not essential.

Turn on the supply and allow 1 minute warm up period.

2.0 Set the resistance decade box to the equivalent resistance 

of the sensor for the required low range temperature, or apply 

required low range temperature to the sensor.

Allow 10 seconds for the 

KOS

1605P to settle.

3.0 Press and hold the Low range ADJUST button, marked with 

a  blue  down  arrow,  until  the  STATE  LED  starts  to  flash,  then 

release the button.

Press  and  release  the  Low  range  ADJUST  button  again,  the 

STATE LED will flash quickly for a short time and the new low 

range will be stored. The output current will go to 4.0 mA.

4.0 Set the resistance decade box to the equivalent resistance 

of the sensor for the required high range temperature, or apply 

required high range temperature to the sensor.

Allow 10 seconds for the SEM1605P to settle.

5.0 Press and hold the High range ADJUST button, marked with 

a  Red  up  arrow,  until  the  STATE  LED  starts  to  flash,  then 

release the button.

Press  and  release  the  High  range  ADJUST  button  again,  the 

STATE LED will flash quickly for a short time and the new high 

range will be stored. The output current will go to 20.0 mA. The 

ranging of the 

KOS

1605P is now complete.

Note:- The Low and High user adjust can be set individually and 

in any order as required.

+

-

+

-

KOS

1605P

or

 or sensor

Ω

Ω

Pressing the button has no action.

USER ADJUST

USER RANGE

OFF

2.0  Press  and  hold  the 

red  up  arrow  for  10  s 

until  the  STATE  LED 

starts  to  flash,  then 

release the button

MT-KOS1605

P

_EN_

20190606

User Guide

307277

2

3

Reviews: