Line Interactive UPS
400VA-
8
00VA
This UPS utilizes voltage that may be hazardous. Do not
attempt to disassemble the unit. The unit contains no user
replaceable parts. Only factory service personnel may
perform repairs.
This pluggable type A equipment with battery already installed
by the supplier is operator installable and may be operated by
laymen.
The mains socket outlet that supplies the UPS shall be installed
near the UPS and shall be easily accessible.
During the installation of this equipment it should be assured
that the sum of the leakage currents of the UPS and the
connected loads does not exceed 3.5mA.
Connection to any other type of receptacle other than a
two-pole, three-wire grounded receptacle may result in shock
hazard as well as violate local electrical codes.
In the event of an emergency, press the "OFF" button and
disconnect the power cord from the AC power supply to
properly disable the UPS.
Do not allow any liquids or any foreign object to enter the UPS.
Do not place beverages or any other liquid-containing vessels
on or near the unit.
(temperature controlled, indoor area free of conductive
contaminants). Avoid installing the UPS in locations where
there is standing or running water, or excessive humidity.
Do not plug the UPS input into its own output.
Do not attach a power strip or surge suppressor to the UPS.
Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or
vacuum cleaners to UPS.
MODEL
DTK-UPS
400
DTK-UPS
600
DTK-UPS
800
CAPACITY
400VA/240W 600VA/360W 800VA/480W
Input Voltage
110/120 VAC
Input Voltage Range
81-145 VAC
Output Voltage
Regulation
± 10 % (Bat. mode)
Transfer Time
Typical 2-6 ms
Waveform
Simulated Sine Wave
Battery Type & No
12V/4.5Ahx1
12V/7Ahx1
12V/9Ahx1
Charging Time
6 hours recover to 90% capacity
Dimension (DxWxH)
300 x 101 x 142 mm
Net Weight (kgs)
3.7
4.4
5
Humidity
0-90% RH @ 0-40°C non-condensing)
Noise Level
Less than 40dB
*Specifications are subject to change without notice.
Do not dispose of batteries in a fire as they may explode.
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or
disconnecting batteries terminal.
6)
Remove battery grounds during installation and maintenance
to reduce likelihood of shock.
Internal battery voltage is 12VDC.Sealed, lead-acid, 6-cell
battery.
Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away from
batteries.
When replacing batteries, replace with the same number and
type of sealed lead-acid battery.
This unit intended for installation in a controlled environment
Do not open or mutilate the battery or batteries. Release
d
electrolyte is harmful to the skin and eyes. It may be toxic.
Caution:
Hazardous voltage could result in
electric shock.
Al
though UPS power is disconnected
, hazardous voltage still
may be accessible through supply from battery. The battery
supply should be therefore disconnected in the plus and minus
pole at the connectors of the battery when maintenance or
service work inside the UPS is necessary.
To reduce the risk of overheating the UPS, do not cover the
UPS' cooling vents and avoid exposing the unit to direct
sunlight or installing the unit near heat emitting appliances such
as space heater or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
Problem
Possible Cause
Solutions
Nothing is
displayed on
LCD panel.
The UPS is not on.
Press the power switch
again to turn on the UPS.
Battery voltage is too
low.
Charge the battery at least
6 hours.
Battery fault.
Replace the battery.
The UPS
is
always
i
n
battery mode.
Power cord loose.
Re-plug the power cord.
The UPS
continuously
beeps.
Please check the fault
code for the details.
Please check the fault code
for the details.
Backup time
too short.
Battery voltage is too
low.
Charge the battery at least
6 hours.
Overload.
Remove some unnecessary
loads. Before reconnecting
equipment, please verify
that the load matches the
UPS capability specified in
the specs.
Battery defect.
Replace the battery.
If any abnormal situations occur that are not listed above, please
call for service immediately.
SAVE THESE INSTRUCTION-This manual contains important instructions that should be followed
during installation and maintenance of the UPS and batteries.
www.diteksurgeprotection.com
1-800-753-2345
INT-100177-001 PN: 191-608
REV 01