System Overview
TSS2 (Total Surge Solution)

The TSS2 is an integrated surge protection solution for alarm panels. This device 

provides transient voltage surge protection for two pairs of communication 

circuits, up to two pairs of initiating circuits, notifying, or signaling circuits, and AC 

power protection .  This product also features field replaceable modules and an 

edge card connection circuit that shields the AC power circuit from the loop and 

comminication circuits .

Installation

Cabinet

Caution:

 This installation should be performed by a licensed electrician.

Note:

 Install this device between the field wiring and the alarm panel.

Disconnect system power and loop circuits before beginning installation.

1. Locate an appropriate area for the cabinet near the alarm panel to be protected.

2. Position the TSS cabinet on the finished wall surface and fasten the cabinet 

    to the wall.

3. Remove the appropriate knockouts from the cabinet to facilitate the routing of

    the field wiring and alarm panel supply wiring . Make sure the field wiring and the

    protected wiring to the alarm panel occupy separate conduit feeds. 

    

Optional:

Use a Nema 4X rated connector if you wish to maintain the NEMA 4X 

    rating of the enclosure.

4. Pull the field wiring and the alarm panel supply wiring through the appropriate

    knockouts on the cabinet. Make sure to route the AC power wires separately 

    from the loop circuit wires.

Note:

 When using the TSS2, the enclosure can be mounted directly onto

a panel, frame or other mounting surface through corner mounting holes. Corner

hole mounting is required to maintain the NEMA 4X rating.

7.28"

3.74"

10.43"

TSS2 Nema 

120 VAC Power To 
Protected Equipment.

120 VAC Power In.
Enclosed In Conduit.

Supply Wiring

3' Of Conductor 
Length

Ground In

Ground Buss

Ground Out

DTK-120SRD (120V Series Surge Protector)

Warning !! 

Turn power off at the main circuit breaker panel.

Note: Connect this device in series between the AC power supply wiring and the 

alarm panel AC inputs.

1. Crimp the supplied ring terminals to the connection wires.

2. Connect the Ground (green or bare) supply wire to the ground buss on the 

    back plane. The GROUND on the DTK-120SRD has been factory pre-wired. It is not 

    necessary to make any additional ground connections.

3. Connect the Neutral (white) supply wire to the NEUTRAL terminal on the Input side. 

4. Connect the Phase (black) supply wire to the LINE terminal on the Input side.

5. Connect the Ground, Neutral and Phase wires from the Output side to the alarm

    panel AC inputs.

6. After all connections have been made and metal nuts have been torqued to 10 

    inch pounds, install the plastic protective cover and fasten with the included nylon 

    nuts until snug.

SURGE PROTECTIVE DEVICE

DTK-120SRD

CAUTION !!!

HIGH VOLTAGE

MADE IN USA

WWW.DITEKCORP.COM

NC C NO

NO         C          NC

DRY CONTACT

)

NEUTRAL(

-

)

LOAD: 120VAC, 0.5AMP (MAX)

EXAMPLE MONITORING CIRCUIT

EXAMPLE REMOTE MONITORING

USING FACP FOR NOTIFICATION

DTK-120SRD

DRY CONTACT CIRCUIT INFORMATION