background image

DTK-TSS2 

Total Surge Solution

User Guide 

DITEK CORPORATION

One DITEK Center

1720 Starkey Road

  Largo, Fl 33771

DTK-2MHTP (2-Pair Modular Hybrid Line Protector)

Note: Connect this device in series between the field wiring and the 
alarm panel supply wiring.
1. Connect the communication loop circuit from the field to the side marked INPUT. 
    The first pair is connected to the terminals marked 1+ and 1- . If a second pair is 
    used, connect to the terminals marked 2+ and 2-  . 
2. Connect the communication loop for the alarm panel supply wiring to the side 
    marked OUTPUT. 

DTK-2MHLPXXB (2-Pair Modular Hybrid Line Protector)

Note: Connect this device in series between the field wiring and the 
alarm panel supply wiring.
1. Connect the IDC (Initiating), NAC (Notifying), or SLC (Signaling) circuit wiring from 
    the field to the side marked INPUT. The first pair is connected to the terminals 
    marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ 
    and 2-  . 
2. Connect the IDC (Initiating), NAC (Notifying), or SLC (Signaling) alarm panel 
    wiring to the side marked OUTPUT. 

Note:

 This module may be used for protection of any IDC (Initiating), NAC (Notifying), 

or SLC (Signaling) circuits. Each module will protect 2 pairs of the same circuit.

Note:

 All modules have been factory pre-wired for ground.  It is not necessary to

make any additional ground connections.
After all connections have been made and no hazards exist, restore power

DITEK CORPORATION

One DITEK Center 1720 Starkey Road Largo, Fl 33771

       1-800-753-2345         www.ditekcorp.com

Sales: 1-800-753-2345

Technical Support: 1-888-472-6100

P/N 191520 INT-100088-001 Rev 5  3-27-13

UNPROTECTED

    1+   1-    2+   2-   

PROTECTED

3

    1+   1-    2+   2-   

Reviews: