background image

            DTK-DF120M 
          (Surge Module)

The DTK-DF120S1 is a series connected Surge Protective Device with a replaceable
surge module.The LED indicators on the top face of the DTK-DF120M provide power, 
ground and surge module health status.   When the DTK-DF120M surge module has 
gone end of life, the large “REPLACE” RED LED will illuminate and the “GOOD” LED 
will turn off. Also, the audible alarm will sound to provide an extra alert as to the surge 
module’s health.  To silence the alarm, remove the dead module and replace it with a 
new, unused module.  If a new module is not available,  the alarm can be silenced by 
moving the toggle switch into the A, or BYPASS position.  When a new DTK-DF120M 
surge module is available, this toggle switch must be moved to the B, or the NORMAL 
position before installing the new module. This action will also require the cover to be 
removed to gain access to this switch.  The red polarizing keys insure that the correct 
voltage module will mate with its corresponding base. 

CAUTION:

 By removing the cover, you will be exposed to live metal parts and there is 

a risk of electrocution.

WARNING:

  Removing the cover should only be performed by a licensed electrician.

WARNING:  When the DTK-120M module has gone end of life, or is missing, the
base is susceptible to damage from surge energy. Make sure you always have a
spare module available. No substitutions shall be permitted.

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  
Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA
MCOV Rating: 150 L-N, 150 L-G
VPR: 600 L-N, 600 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, 120 Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 120 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

R

IN

OUT

SW1

A

B

BUZZER SWITCH

POSITION

B

Y

P

A
S
S

N
O

R

M

A

L

A

B

BUZ1

TB2

NC   C   NO

TB1

EARTH
NEUTRAL
LINE

EARTH

NEUTRAL

LINE

OUT TO CONNECTED 

EQUIPTMENT

LINE IN 120V

SW1

A

B

BUZZER SWITCH

POSITION

B

Y

P

A
S
S

N
O

R

M

A

L

A

B

NO
C

NC

Front

Back

MODULE

STATUS

ENERGIZED

GROUNDED

GOOD

REPLACE

Reviews: