background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Doc # INT-100141-001

Part No. 191563 Rev.4

     INSTALL INSTRUCTIONS

D200-2403D

       

DITEK Corporation

ONE DITEK CENTER

1720 Starkey Road

Largo, FL 33771

INSTALLATION

This Surge Protective Device (SPD) is a high performance device, designed to provide protection

for sensitive electronic loads connected to service panels, fire panels, or where the SPD is 

directly connected to the electronic device. Maximum protection will only be achieved if the SPD

is properly installed.  Please read and follow the installation instructions carefully.

NOTICE:

 This SPD should be installed by a licensed contractor in accordance with the National and 

Local Electrical Codes and the following instructions.

APPLICATION:

Type 1 SPD, Type 2 SPD for hardwired parallel installations on 

240 VAC 3 phase Delta circuits.

INSTRUCTIONS:

Caution

: Measure all voltages to insure applied voltage does not exceed the voltage rating of 

              the unit. Improper installation voids the warranty.

NOTE

: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical

            Amperes.

This SPD Contains no serviceable parts.

  1. Turn off the power at the circuit breaker or main disconnect before beginning installation.

  2. Remove front cover from the panel.

  3. Remove 3/4" knockout on side of panel box

  4. Make sure the leads are as short as possible with the ground wire being the shortest of all.

  5. Unscrew locknut “A” from the Push-On Connector. The flexible conduit between the connectors can be

      cut down to size as necessary. See the Illustrations Page on the back side of this document for more

      information.

  6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit.

  7. Connect the Ground wire (Green) to the ground bus making sure the ground wire is as short as

       possible.

      Ground Resistance Rule

: Max ground resistance is 25 ohms, 5 ohms or less is optimum.

      This cannot be an assumed value and must be measured to assure proper grounding.

  8. Connect the Phase wires (Black) to the line side or load side of the Phase A, Phase B and

      Phase C, 3 pole breaker.

  9. Securely mount the enclosure using the mounting feet located at each corner.

10. After all connections have been made and no hazards exist, replace panel cover and restore power.

 11.This device features an internal protection that will disconnect the surge protective component

      but will maintain power to the load - now unprotected.  If this situation is undesirable for the

      application, follow the manufacturer’s instructions for replacing the device.

Drawn By: B. Aycock 5-18-16

Approved By: R. Mitchell 4-15-2020

Expected System Voltages

L - L HiL-G,N L - G

L - N

N - G

120V Single Ø

NA

NA

120

120

0

120/240V Split Ø

240

NA

120

120

0

120/240V Hi Leg  

Δ

240

240

120

120

0

120/208V 3 Ø Wye

208

NA

120

120

0

277/480V 3 Ø Wye

480

NA

277

277

0

240V 3 Ø 

Δ

240

NA

240

Max

NA

0

480V 3 Ø 

Δ

480

NA

480

Max

NA

0

600V 3 Ø 

Δ

600

NA

600

Max

NA

0

240V Single Ø

NA

NA

240

240

0

347/600V 3 Ø Wye

600

NA

347

347

0

Dry Contact Connection: 

This is a Form C Dry Contact Circuit, 0.9A, 240VAC maximum input.

Normally Open (NO)=Black Wire, Common (COM)= Red Wire, Normally Closed (NC)=White Wire.

Note: 

Remote Alarm Wires To Be Connected To Class 1 Circuits Only.

NEUTRAL BUS

GROUND BUS

BREAKER PANEL

GREEN WIRE

BLACK WIRE

D200-2403D

3 POLE BREAKER

DITEK

MADE

 IN THE USA

       DITEK Technical Support Available 24/7

1-888-472-6100 www.diteksurgeprotection.com

LOCKNUT “A”

Reviews: