3. TESTING THE AUTOMATIC SYSTEM WITH 192C ELECTRONIC BOARD
3.1 Checking the dip-switches
3.2 Functional test
Wire up as shown in fig. 2, close the contacts 1-8, 1-9.
Connect the transformer to mains (230 V~/50 Hz).
Give the following commands to the electric board and visually check for correct response and straight and smooth running.
3.3 Chaos test
Send repeated open and close commands so as to cause the wing or wings to continuously reverse direction of movement without
stopping (for at least 1 minute). Check that the automation system does not fail to appropriately keep wing position under control
nor cause the wing or wings to slam, and that no logic malfunction occurs.
3.4 Checking the trimmers
3.5 Default setting
At the end of the test, make the following settings:
-
all the trimmers set to minimum;
-
all the dip-switches in the OFF position (the position of DIP2 depends on the type of automatic system);
-
disconnect batteries (if installed), checking that the electric board is not being powered by them (press RESET command).
3.6 General controls
-
Control the length of the casing, the passage width and the width of the leaf.
-
Tie the power supply cable and command cables with related channels.
-
Apply the casing seal.
-
Perform a general check (belt tension, screw tightness, etc).
-
Fill-in and apply the CE label.
ACTION
OUTCOME
Electronic board turned on
- green LED lit
- red amplifier card LED lit
Command 1-2 permanent and TC trimmer at minimum
- closure manoeuvre
Command 1-3 (impulsive)
- opening manoeuvre
Command 27-3 (impulsive) and RP trimmer at minimum
- partial opening manoeuvre
Command 1-8 during closure (contact open)
- re-opening
Control of the photocell card during the closure phase:
- connect the 1CelA photocell amplifier to the electronic board
- connect the CelPR
- the gate should open when the optical alignment between TX
and RX is broken.
Command 1-9 (contact open)
- stop for the duration of the command
RESET pushbutton (of the electrical control panel)
- reset, encoder zero setting
ACTION
OUTCOME
DIP1 = OFF
- lock not powered with closed door
- a command powers the lock throughout the opening manoe-
uvre
Warning: DIP1 must be set to OFF.
DIP2 = OFF for REX2 and REX1-DX
DIP2 = ON for REX1-SX
- variation of the opening direction
DIP3 = ON
- battery function, if present, in the event of blackout
DIP3 = OFF
- in the event of blackout, the automation with the batteries pre-
sent performs the last opening manoeuvre and then switches
off
ACTION
OUTCOME
RP trimmer adjustment
- variation of the partial opening
TC trimmer adjustment
- variation of the automatic closure time
R1 trimmer adjustment and opposition to the movement of the
door leaves
- variation of motor power / obstacle detection (reopening and
stopping)