88
Network Guide
Setting the EC-Multi-Sensor Series' Subnet ID
Address
Each EC-Multi-Sensor connected to a controller's Subnet Port must be set to a unique subnet
ID address. This address should correspond to the block number of the associated Multi Sen-
sor block in EC-
gfx
Program. The address is set through the rotary selector located next to the
Subnet Port connector.
Figure 56: Setting the EC-Multi-Sensor Series' Subnet ID Address
Use a small screwdriver (for example, a precision or jeweler's screwdriver) to set the selector.
shows an example of how to set the EC-Multi-Sensor Series' Subnet ID address DIP
switch to 1 and the EOL termination is ON.
Once an EC-Multi-Sensor is installed, the following tip can be used during system
commissioning to verify if the EC-Multi-Sensor is set to the correct subnet ID
address for the zone in which it is physically located.
Run EC-
gfx
Program in debug mode for the controller with 4 Multi Sensor block
instances, 1 to 4. Set a remote control to zone ID 0, then aim it at the EC-Multi-Sen-
sor and press a command (fan speed button for example). In EC-
gfx
Program, see
which block instance shows an output (RemoteFanSpeed).
Usually it is easier to reassign Multi Sensor block numbers in EC-
gfx
Program code
than it is to change the Subnet ID Address of an installed EC-Multi-Sensor.
Back of
EC-Multi-Sensor
EOL Jumper: EOL is enabled
when present; remove to
disable EOL
RJ-45 Subnet Connector
Set the Subnet
ID Address with
a Small
Screwdriver
1
0
2 3 4
5
6
7
8
9
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...