84
Network Guide
Figure 54: Setting the EOL Terminations on the Allure Series sensor Subnetwork Data Bus for the ECB/
ECL-600
If an ECx-4XX Series I/O Extension Module is used with both a Cat 5e room device and an
ECB/ECL-600 controller, see
on page 92 for how to set the EOL
terminations.
Setting the Subnet ID Addressing for Room Devices
Each type of room device connected to a controller's Subnet Port must be set to a unique sub-
net ID address. The permitted subnet ID addressing range according to controller model is
shown in
. The method to use to set a room device's subnet ID address is shown in
the table below.
Cat 5e Cable Subnetwork Bus
Controller Series:
· ECB-600
· ECL-600
For ECB-600 / ECL-600, set the
Subnetwork EOL to ON
EOL OFF
EOL ON
Inside
ECB/ECL-600
EOL set to ON
at the last
sensor at the
end of the Bus
ON
EO
L
OFF
Back of Allure
EC-Smart-Vue
Table 19: Subnetwork Module Compatibility and Maximum Supported Quantity Chart
Room Device Type
Configuration Method
See
Allure EC-Smart-Vue
series
Configured in an on-screen menu.
Setting the Allure EC-Smart-Vue
Sensor's Subnet ID Address
on
page 98.
Allure EC-Smart-Comfort
series
Dip Switch located next to the RJ-
45 subnet connectors
Setting the Allure EC-Smart-Air
and EC-Smart-Comfort Commu-
nicating Sensor Series' Subnet ID
Address
on page 86
Allure EC-Smart-Air
series
EC-Multi-Sensor series
Rotary selector located next to
the RJ-45 subnet connector
Setting the EC-Multi-Sensor
Series' Subnet ID Address
page 88.
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...