Network Guide
BACnet MS/TP Data Transmission Essentials
The BACnet MS/TP data bus protocol is part of the BACnet® ANSI/ASHRAE™ Standard 135-
2008 that uses the EIA-485 (RS-485) physical layer standard for data transmission (herein
called the data bus). Multiple data buses can be logically tied together as each BACnet MS/TP
data bus is assigned a unique Network Instance that distinguishes it from other data buses in
the BACnet MS/TP Local Area Network (LAN). An example of an interconnected BACnet MS/
TP data bus is shown in
.
EIA-485 is a standard that defines the electrical characteristics of the receivers and drivers to
be used to transmit data in a differential (balanced) multipoint data bus that provides high
noise immunity with relatively long cable lengths which makes it ideal for use in industrial envi-
ronments. The transmission medium is inexpensive and readily-available twisted pair shielded
cable.
While there are many possible LAN topologies for an EIA-485 data bus, only devices that are
daisy-chained together are allowed with BACnet MS/TP (see
). A spur is only permit-
ted when it is connected to the data bus through a repeater (see
End-of-line (EOL) terminations are critical to error-free EIA-485 data bus operation. The
impedance of the cable used for the data bus should be equal to the value of the EOL termina-
tion resistors (typically 120 ohms). Cable impedance is usually specified by the cable manu-
facturer.
BACnet MS/TP Data Bus is Polarity Sensitive
The polarity of all devices that are connected to the two-wire BACnet MS/TP data bus must be
respected. The markings to identify the polarity can vary by manufacturer. The following table
summarizes the most common identification labels for BACnet MS/TP data bus polarity.
Table 1: Common Identification Labels for BACnet MS/TP Data Bus Polarity for Distech Controls' Products
Distech Controls Product
Typical Data Bus Connection Terminals
Inverting
Non-inverting
Reference
ECB Series Controllers
ECB/ECL-VAVS
NET -
NET +
24V COM
ECB/ECL-VAV
NET -
NET +
(Ground symbol)
ECB-PTU Series Line-Powered
Controllers
NET -
NET +
COM
EC-BOS
-
+
S
Thermostat
-
+
Ref
Repeater
Data-
Data1-
Data+
Data1+
N/A
Summary of Contents for ECB-VAV
Page 1: ...User Guide Network Guide...
Page 6: ...Table of Contents 4 Network Guide...
Page 52: ...50 Network Guide...
Page 70: ...68 Network Guide...
Page 110: ...108 Network Guide...
Page 121: ...LonWorks Troubleshooting Network Guide 119...
Page 122: ...120 Network Guide...
Page 124: ...122 Network Guide...
Page 128: ...126 Network Guide...
Page 136: ...134 Network Guide...
Page 137: ...Network Guide...
Page 138: ...Network Guide_UG_24_EN...