INSTRUCTIONS MANUAL
CONSTANT LIGHT CONTROLLER
& MOTION DETECTOR
for 1/10V
DC
ELECTRONIC BALLASTS
RE DMS 001
2
DESCRIPTION
3
WORKING
RE DMS 001
Constant Light Control
ON / OFF
· Flush ceiling mounting.
· Built in LED Which is lighted upon detecting movement.
· 1/10V
DC
output For dimmable electronic ballasts.
· Possibility of extending the coverage area of motion detection with
extra sensors (only AUTO mode).
Technical Specifications
· Power supply:
230V~ 50Hz
· Consumption:
2W
· Load type:
80 dimmable 1/10V
DC
electronic ballasts
· Relay operating voltage:
250V
AC
· Relay cutout capacity:
16A
· Max. absorption current:
500mA
· Max. injection current:
40mA
· Coverage:
360º and
Æ
6m max. at 2,4m high
· Time delay:
AUTO mode: 10min ~ 30min
MOV mode: 5sec ~ 10min
· Number of motion sensors:
Up to 15 units
(14 x DM SEN T03)
- Only in Automatic mode
· Sensor dimensions:
Æ
65mm
· Control dimensions:
107 x 53 x 34mm
· Weight:
205g
· Protection degree:
IP20 according to EN60529
· Operating temperature:
0ºC ~ +40ºC
· Storage temperature:
-10ºC ~ +45ºC
· Connection terminals:
Wires of up to 6mm
2
cross section
· According to:
EN60730
It consists in a constant light control for installations with fluorescent
lamps, associated to 1/10V dimmable electronic ballasts.
These type of systems are usually used in offices, conference halls,
hotels,...
Consists of 2 elements:
Sensor:
- Flush ceiling sensor, just like a 65mm diameter halogen lamp.
- With built-in brigthness sensor and motion detector.
- RJ12 connector.
- Four settings:
· Mode selector: Automatic (constant light c motion detection),
only constant light control or only motion detection (see point 5A).
· Switch-off % level setting (see point 5B).
· Time delay setting (see point 5C).
· Programming setting (see point 5D).
Control:
- Can be mounted over the false ceiling, connected to the sensor.
- 1/10V
DC
output signal for dimmable electronic ballasts.
- Incorporates a relay which disconnects physically the ballasts. It
allows to switch-off completely the lamps.
Extra motion sensor DM SEN T03:
- Extra motion sensor that can extend the coverage area.
Attention! Only for AUTO mode.
- RJ12 connector that allows quick and easy installation.
B. Installation procedure:
Before doing the wiring disconnect the mains supply in order to
do the installation without voltage.
C. Wiring diagrams:
C.1. Installation using K relay (L' output)
Doing this wiring, the fluorescents will be physically disconnected when
dimming level reaches a value lower than the 10%.
C.2. Installation without K relay (L' output)
Doing this wiring, the fluorescents will keep turned-on to its minimum
level when the regulation signal reaches to its lowest value (enough
natural light).
The user sets the desired light level and the system dims the ballasts in
order to maintain the brightness level.
The system can operate with or without motion detection. If this
function is activated, the system will begin to run as soon as motion is
detected and it will continue working until the selected time finishes.
If motion detection is not applied, the system will allways run whereas
it is supplied.
The RE DMS 001 can also work as only motion detector with the
Corridor function (adjustable switch-off level %).
4
INSTALLATION
AND WIRING
A. Select a appropiate location:
Depending on the use and operation mode:
- If the constant light control is used:
Distribute the installation by zones depending on the daylight.
In each clearly differentiated area it should be installed a sensor/control.
In case of making use of both functions (motion detection and constant
light control) it is necessary to fulfill the above-cited requirements.
If the current is highest than 16A, it will be
necessary to build in a contactor at L' output.
C.3. Installation of an auxiliary switch to turn-off manually
It is possible to install an auxiliary switch to turn on/off manually the
system. At installations, for example, with the movement detection
function cancelled, this swith will allow to turn on/off the system
voluntarily at any time.
Access to the terminals:
Easy installation on false ceilings. It is only necessary 48mm height, if
the orifice has a diameter of 68mm:
and 60mm height if the orifice is 55mm.
2,4M
Install the sensor over the place that is desired to take as brightness
reference (normally the desk).
In order to get an optimal operation of the system, the sensor should be
installed at a distance of 2 ~ 3m from the window.
Avoid placing the sensor over dark surfaces (dark furniture or carpets)
or highly reflecting (polished tables and floors).
Avoid pointing light onto the sensor (sunray, reflexions of windows or
mirrors, lamps focused to the sensor,...).
- Installation criteria for optimal performance of motion detection:
Install the sensor taking into account the range of vision or detection
area.
Nota: after supplying the dimmer the lamps will turn-on to its
maximum level. The system is self-regulate to the adjusted light
level with some inertia.
This inertia last, approximately, 10min, from the maximum level
(100%) to the minimum (<10%).
Considering that motion detector responds temperature changes,
please avoid next conditions:
- Avoid pointing the sensor towards areas or objects whose surfaces
are highly reflective or are subject to rapid temperature changes.
- Avoid mounting the sensor near heat sources, such as heating vents,
air conditioners, dryers, vents or lights.
- Avoid directing the sensor towards light sources.
- Avoid aiming the sensor towards objects, which may move by wind,
such as curtains, small trees or bushes.
Switch
1
CHARACTERISTICS
LATERAL VIEW
TOP VIEW
4 elements
· Insert the two long spring-fixing clips into the hole and once
released they will keep adjusted automatically.
· Adjust the position of the sensor. Be sure that bottom of sensor is
tightly stacked on the ceiling.
Note
L
L
N
+
-
L
N
L
L
N
+
-
L
N
L
L
N
+
-
L
N
BALLAST
FLUORESCENT TUBE
BALLAST
FLUORESCENT TUBE
BALLAST
FLUORESCENT TUBE
BALLAST
FLUORESCENT TUBE
BALLAST
FLUORESCENT TUBE
BALLAST
FLUORESCENT TUBE
L
N
+
-
L
N
+
-
L
N
+
-
L
N
+
-
L
N
+
-
L
N
+
-
RE DMS 001
RE DMS 001
RE DMS 001