background image

 

 

Page 2/4

 

Press button A 

❻ 

or button B 

❼ 

long to exit the manual opera-

tion mode. 

Manual operation RF 

Pressing button B 

 short, enters the manual operation for RF 

mode. 

By pressing button A 

, routing runtime telegrams (group 

telegrams) will be enabled/disabled. This will be indicated by 
LEDs 5 and 6 

By pressing button B 

, routing management telegrams (indi-

vidual addressed, broadcast and system broadcast telegrams) 
will be enabled/disabled. This will be indicated by LEDs 7 and 8 

Press button A 

❻ 

or button B 

❼ 

long to exit the manual opera-

tion mode. 

 

Factory default settings 

 
The following configuration is set by factory default: 

Individual device address:  

 

 

15.15.0 

Routing (TP line 

 RF line): 

Individual addressed telegrams: 

 

Filter

 

Group addressed telegrams:   

 

Block 

Routing (RF line 

 TP line): 

Individual addressed telegrams: 

 

Filter

 

Group addressed telegrams:   

 

Block 

Reset to factory device settings

 

It is possible to reset the device to its factory settings: 

 

Disconnect the KNX Bus connector 

 

from device 

 

Press the KNX programming button 

 

and keep it 

pressed down 

 

Reconnect the KNX Bus connector 

 

of device 

 

Keep the KNX programming button 

 

pressed for at 

least another 6 seconds 

 

A short flashing of the all LEDs 

❹ 

and 

 visualizes 

the successful reset of the device to factory default set-
tings. 

 

 

ETS database 

The ETS database (for ETS 5) can be downloaded from the 
product website of the KNX RF/TP Coupler: www.dinuy.com. 

 
ETS parameter dialogue 

The following parameters can be set using the ETS.

 

Description 

 

The first page shows general information about the device. 

General settings 

 

Device name (30 Characters) 

An arbitrary name can be assigned for the KNX RF/TP Coupler. 
The device name 

should be meaningful, e.g. “Living Room”. 

 

Manual operation on device

 

This parameter sets the duration of the manual mode. Upon 
completion the normal display mode is restored. 

Repeater 

Disabled:

 

Received telegrams will not be repeated. 

Enabled:

 

Received telegrams will be repeated to 
extend the RF range. 

The KNX RF/TP Coupler can also be used as a repeater. In this 
case, the individual address has the form x.y.z, where z must not 
be equal to 0. The filter settings in the parameter dialog of the 
ETS are ineffective in repeater mode. 

 
 

 