User manual - METER PDU-4x0-W
Register Write
Range
Register description
16h
Yes
0 ÷ 999
“
Lo r
” parameter in “
InPt
” menu, in 0.1%
17h
Yes
0 ÷ 199
“
Hi r
” parameter in “
InPt
” menu, in 0.1%
18h
Yes
0 ÷ 9999
“
t h1
” parameter in “
InPt
” menu, no decimal point included
19h
Yes
0 ÷ 9999
“
t h2
” parameter in “
InPt
” menu, no decimal point included
1Ah
Yes
0 ÷ 9999
“
t h3
” parameter in “
InPt
” menu, no decimal point included
1Bh
Yes
0 ÷ 9999
“
t d
” parameter in “
InPt
” menu, no decimal point included
1Ch
Yes
0 ÷ 9999
“
t Sn
” parameter in “
InPt
” menu, no decimal point included
1Dh
Yes
0 ÷ 9999
“
t Sh
” parameter in “
InPt
” menu, no decimal point included
20h
2
Yes
0 ÷ 199
Device address
21h
No
Device identification code (ID)
22h
3
Yes
0 ÷ 7
“bAud”
parameter in
“rS”
menu (baud rate);
0
- 1200 baud;
1
- 2400 baud;
2
- 4800 baud;
3
- 9600 baud;
4
- 19200 baud;
5
- 38400 baud;
6
- 57600 baud;
7
- 115200 baud
23h
4
Yes
0 ÷ 1
“mbAc”
parameter in
“rS”
menu (permission to write registers via
RS-485 interface);
0
- write denied ;
1
- write allowed
24h
Yes
see descr.
Parameters of “
SECU
” menu (binary format (0 - „
oFF
”, 1 - „
on
”):
bit 0
- “
A r1
” parameter;
bit 1
- “
A r2
” parameter
25h
Yes
0 ÷ 5
“rESP”
parameter in
“rS”
menu (additional response delay);
0
- no additional delay;
1
- ”
10c
” option;
2
- ”
20c
” option;
3
- ”
50c
” option;
4
- ”
100c
” option;
5
- ”
200c
” option;
27h
Yes
0 ÷ 99
“mbtO”
parameter in
“rS”
menu (maximum delay between
received frames);
0
- no delay checking;
1
÷
99
- maximum delay expressed in seconds
2Dh
Yes
1 ÷ 8
“
bri
” parameter (display brightness);
1
- the lowest brightness;
8
- the highest brightness
2Fh
Yes
0 ÷ 1
“
Edit
” parameter (numerical parameters edit mode);
0
- „
dig
” mode;
1
- „
SLid
” mode
30h
Yes
-999 ÷ 9999 “
SEtP
” parameter in “
rEL1
” menu, no decimal point included
31h
Yes
-999 ÷ 999
“
HySt
” parameter in “
rEL1
” menu, no decimal point included
32h
Yes
0 ÷ 5
“
modE
” parameter in “
rEL1
” menu:
0
- “
noAC
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modb
” mode
33h
Yes
0 ÷ 999
“t on”
parameter in
“rEL1”
menu, expressed in tenth of seconds or
tenth of minutes depend on
“unit”
parameter - register no. 35h)
34h
Yes
0 ÷ 999
“toFF”
parameter in
“rEL1”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 35h)
35h
Yes
0 ÷ 1
“unit”
parameter in
“rEL1”
menu:
0
- seconds;
1
- minutes
36h
Yes
0 ÷ 2
“AL”
parameter in
“rEL1”
menu:
0
- no changes;
1
- on;
2
- off
49