background image

Enclosure cooling unit

Model

40ACU/004-3

User's guide

ภาษาไทย

English

Summary of Contents for 40ACU/004-3

Page 1: ...Enclosure cooling unit Model 40ACU 004 3 User s guide English...

Page 2: ...1 Contents Page 1 Over view 3 5 2 Specification 6 7 3 Notification 8 4 Technical information 9 10 5 Installation 11 19 6 Maintenance 20 7 Fault indication 21 8 Assembly and parts number 22...

Page 3: ...by providing cool air to the control cabinet that can protect sensitive equipment It is specially designed to resist surrounding temperature as high as 40 50 o C and can function well in any factorie...

Page 4: ...1 Over view 40ACU 004 3 3...

Page 5: ...Drain pan Evaporator fan Condensor fan Condensor coil Compressor Filter Hiprosent control Evaporator coil Filter 4...

Page 6: ...it is working LED3 Power on Cable and signal S1 Cooling space temp sensor S2 Condensing temp sensor 220VAC C1 Capacitor M1 Compressor M2 Condenser Fan M3 Evaporator Fan SR1 Solid State Relay 5 1 2 3 4...

Page 7: ...sor thermal detector yes freeze protection yes overflow condensate drain protection yes Protection secondary drainpan yes Electrical equip safety device 7A slow blow fuse Evaporator coil face area x r...

Page 8: ...rills 9 105 5 90 90 90 90 105 5 Cutting area Templet for drill cutting 320 390 LEFT REAR TOP FRONT RIGHT Ambient Air In Ambient Air In Warm Air Out Cold Air Out Return Air In BOTTOM 608 388 403 40 194...

Page 9: ...9 In order to minimize water condensation cabinet doors should be tightly closed during operation Circulation fan should be installed in cabinet if various equipment is densely installed inside In ord...

Page 10: ...es should be disposed of properly or other under direction given by distributor 4 Technical information Protective equipment Refrigeration system has been tested with high pressure device at 350 PSI T...

Page 11: ...shall be done by inserting drain tube under drainpan see page 19 and trying not to left it twisted Make sure the other end of drain tube is not lower than water level in the container in order to avoi...

Page 12: ...Liquid gasket 1 Air filter 182x340 mm 1 Air filter 182x488 mm 1 1 2 drain tube 200 cm for secondery drain 1 1 2 drain tube 250 cm for primary drain 1 Self tapping screw 1 8 x 3 8 for Installation base...

Page 13: ...Installation procedures 1 ADAPTER overview 2 Loose 4 screws from each corners 3 Take off the upper part from the lower part 12...

Page 14: ...NT LOWER of ADAPTER on the position that you want to install the cooling unit 5 Layout as templet for fix the lower part to the control cabinet FRONT LOWER 20 drills 1 8 hole for cooling air circulati...

Page 15: ...n dry cloth or the inventory doesn t lead the electricity and cover with paper box at position will be drilling and cutting in order to prevent metal scrapt falling in cabinet see figure below 7 Drill...

Page 16: ...8 File to eliminate sharp edges 9 Apply the LIQUID GASKET round the air circulation port in order to protect water into control cabinet S e a l 15...

Page 17: ...arefully locate lower part FRONT LOWER on the cooling air circulation port and tighten 20 screws until LIQUID GASKET appear to outside 11 Place the upper part FRONT UPPER on the lower part FRONT LOWER...

Page 18: ...this step tighten 4 screws from 2 while adjust level and incline angle for appropriate water flow direction to water drain pipe 13 Stick foam tape strat at position No 1 and end at position No 2 Fron...

Page 19: ...nto the Rivet nuts which are positioned under the cooling unit Instruction Please use the screws that are provided by the company In case of using different screws the length should not be too long Do...

Page 20: ...tank 8 Elbow 90o 9 fix this position lower than the cooling unit to protect flood back of condensate drain water Caution Avoid immerse drain tube under water level see page 10 17 Connecting electrical...

Page 21: ...nsor coil not to be clogged up The cleaning interval for the air filter depends on how dirty it is of the area where it is installed In case of abnormal function it can be noticed from LED light which...

Page 22: ...replace Condenser fan defective Replace Red Green Flood of water Obstruction in condensate drain Clean or replace drain hose Automatically shut off alternately blink Unit is not fitted vertically Adj...

Page 23: ...8 Assembly and part number ITEM DESCRIPTION PART NUNMBER Qty 1 servo fan EP 03 012 6 2 compressor EP 04 008 1 3 control board XEE 22 502 1 4 filter mat CR 15 002 1 5 filter mat CR 15 001 1 22...