background image

Enclosure cooling unit

Model

14ACU/005

User's guide

Summary of Contents for 14ACU/005

Page 1: ...Enclosure cooling unit Model 14ACU 005 User s guide...

Page 2: ...m VIETNAM Space Cooling Co Ltd Room 0311 C1 Mandarin Garden Complex Hoang Minh Giam Street Cau Giay District Hanoi Vietnam Tel 84 46 664 3395 Fax 84 46 664 3398 E mail hotro spacecooling com vn Websit...

Page 3: ...1 Content Page 1 Over view 3 5 2 Specifications 6 7 3 Notification 8 4 Technical information 9 10 5 Installation 11 19 6 Maintenance 20 7 Fault Indication 21 8 Assembly and part number 22...

Page 4: ...by providing cool air to the control cabinet that can protect sensitive equipment It is specially designed to resist surrounding temperature as high as 40 50 o C and can function well in any factorie...

Page 5: ...3 14ACU 005 1 Over view...

Page 6: ...box Compressor Condensor coil Condensor fan Drain pan Temperature display Evaporator coil Evaporator fan Filter Temperature setting LED status display Switch on off Hiprosent control Main controller...

Page 7: ...iate with Cooling Unit Cable and signal B1 Temperature sensor B2 Drainage failure sensor B3 Ice Sensor B4 Over heat sensor 220VAC C1 Capacitor M1 Compressor M2 Condenser Fan M3 Evaporator Fan S1 On Of...

Page 8: ...r yes compressor overheat detector none water detector none Protection over drain protect system yes Display thermometer red 7 segment 19 mm yes system status 2 colour LED yes Electrical equip safety...

Page 9: ...Out In 300 133 REAR VIEW Out Warm Air Drain Overdrain hole 40 Installation Plate Templet for cutting Area View From Outside of Cabinet 450 12 Cutting Area 379 6 mm 450 mm heigh 384 mm width 37 Cutting...

Page 10: ...8 In order to minimize water condensation cabinet doors should be tightly closed during operation Circulation fan should be installed in cabinet if various equipment is densely installed inside In ord...

Page 11: ...es should be disposed of properly or other under direction given by distributor 4 Technical information Protective equipment Refrigeration system has been tested with high pressure device at 350 PSI T...

Page 12: ...m shall be done by inserting drain tube under drainpan see page 18 and trying not to left it twisted Make sure the other end of drain tube is not lower than water level in the container in order to av...

Page 13: ...Foam gasket 1 Air filte 1 Socket plug cover circle 1 Installing plate 1 3 8 Drain Tube 200 cm 1 3 x 1 Sq mm VCT power cord 200 cm 1 Self tapping screw 1 8 x 3 8 for Installation plate 17 Fiber washer...

Page 14: ...move Installation plate B front plate from Installation plate A back plate 2 Align installation plate rear plate in the position to be installed 12 Installation plate B front plate Installation plate...

Page 15: ...line with Jigsaw 4 Cover eqipments inside cabinet with clean and dry cloth and cover with paper boxes at position will be drilled and cutted in order to prevent metal scrapt falling in cabinet 13 Pape...

Page 16: ...14 5 Drill and cut the holes and area as be pointed out from installation plate 6 Chamfer the cutted edge and paint rust proff colour...

Page 17: ...llation plate attachment 8 1 Install the Installation plate A rear plate with 14 self tapping screws 8 2 Connect main power line with 220VAC which be connected to 10 Amp breaker Main power is 1 Sq mm...

Page 18: ...ation plate B front plate to Installation plate A rear plate 10 Install the socket plug cover 16 socket plug cover Fiber washer Self tapping screw 1 8 x 3 8 Installation plate A rear plate Installatio...

Page 19: ...ders on it and then hang the cooling unit on this holders fasten another 2 screws M6 x 20 mm at the bottom of the cooling unit 12 Uncover the frontal case of cooling unit then plug in the plug 17 foam...

Page 20: ...eware Avoid dipping draing tube below than water level which be clogged its drainage 14 Turn on breaker for operation Tire with 6 CABLE TIE Fixed with 1 2 CABLE CLAMP Fixed with 1 2 CABLE CLAMP 3 8 Dr...

Page 21: ...ow the drill and fix it 2 Divert air to left and right Turn air diverter to left or turn air diverter to right Drill and fix the diverter as shown below Note Air diverter is the additional not appropr...

Page 22: ...ndensor coil not to be clogged up The cleaning interval for the air filter depends on how dirty it is of the area where it is installed In case of abnormal function it can be noticed from LED light wh...

Page 23: ...fective Replace Red color blink Risk of icing Operational indication icing up Raise the set point value of the internal temperature Automatically shut off Evaporator contaminated Clean Evaporator fan...

Page 24: ...PTION PART NUNMBER Qty PART AVAILABLE 1 main casing 1 No 2 drain pan 1 No 3 condenser coil 1 No 4 evaporator coil 1 No 5 servo fan 6 EP 03 012 1 Yes 6 servo fan 4 EP 03 102 1 Yes 7 compressor EP 04 10...