EN-8
452237.66.49 · FD 9912
www.gdts.one
English
WI 35TU - WI 45TU
7.5.2 Electrical installation work
1) The four-core electrical supply cable for the heat pump
power part is fed from the heat pump electricity meter into
the heat pump via the utility company blocking contactor
(if required) (for supply voltage, see heat pump manual).
The mains cable is connected to the heat pump contact
plate via terminals X1: L1/L2/L3/PE.
ATTENTION!
!!
Ensure that there is a clockwise rotating field: With incorrect
wiring the starting of the heat pump is prevented. A
corresponding warning is indicated on the display of the heat
pump manager (adjust wiring).
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility company blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for all
external conductors must be installed in the power supply for
the heat pump (tripping current and characteristic in compli-
ance with the device information).
2) The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump. Connec-
tion of the control cable to the contact plate of the heat
pump via terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a continuous voltage. For this reason,
it should be tapped upstream from the utility company
blocking contactor or be connected to the household cur-
rent, as important protection functions could otherwise be
lost during a utility block.
3) The utility company blocking contactor (K22) with main
contacts and an auxiliary contact must be designed and
provided by the customer in accordance with the heat
pump output.
The NO contact of the utility company blocking contactor
is looped from the terminal strip X3/G to the plug-in termi-
nal X3/A3.
CAUTION! Extra-low voltage
!
4) The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K20.
5) The contactor (K21) for the flange heater (E9) in the do-
mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be supplied by the cus-
tomer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K21.
6) The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system.
7) All installed electric cables must have permanent wiring.
8) The heat circulating pump (M13) is activated via the con-
tact N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.
9) The auxiliary circulating pump (M16) is activated via the
contact N1-J16/NO9. The connection points for the pump
are X2/M16 and X2/N. A coupling relay is already inte-
grated in this output.
10) The domestic hot water circulating pump (M18) is acti-
vated via the contact N1-J13/NO6. The connection points
for the pump are X2/M18 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.
11) The brine or well pump (M11) is activated via the contact
N1-J12/NO3. The connection points for the pump are X2/
M11 and X2/N. A coupling relay is already integrated in this
output.
12) The return sensor (R2) is integrated in the heat pumps for
indoor installation.
The heat pump manager is connected via the following ter-
minals: X3/GND and X3/R2.
13) The external sensor (R1) is connected to terminals X3/GND
and X3/R1.
14) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/GND and X3/R3.
7.5.3 Connection of electronically
regulated circulating pumps
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and
the electronically regulated circulating pump. This is not neces-
sary if the permissible operating current of 2 A and a maximum
starting current of 12 A are not exceeded in the electronically
regulated circulating pump or if express approval has been is-
sued by the pump manufacturer.
ATTENTION!
!!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.