Dimplex UPH 120-32 PK Installation And Operating Instruction Download Page 16

EN-4

452115.66.46 · FD 0004

 

English

UPH 120-32PK

CAUTION!

!!

Danger of damage to property!
If impermissible media are pumped, the pump may be
destroyed.

Table 5.2:

Minimum inlet pressure (above atmospheric pressure) at the
inlet stub to prevent cavitation noise (with medium temperature
T1)

Table 5.3:

The values are valid up to 300 m above sea level; the values
above this height are higher: 0.01 bar/100 m added height.

5.3 Scope of supply

Pump, complete

Installation and operating instructions

2 x flat gasket

Coupling relay

Connection cable 1.5 m (three-core load, two-core control)

Permissible media to be pumped

Media to be pumped:

Heating water (according to VDI 2035/VdTÜV Tch 1466)

Water-glycol mixtures, maximum mixing ratio 1:1 (when glycol is added,
the output data of the pump must be adjusted based on the higher vis-
cosity (depending on the proportional mixing ratio)).

Ethylene/propylene glycols with corrosion protection inhibitor

Standard oxygen binder

1

Standard anticorrosive

1

Standard combination products

1

Standard cooling brines

1

Permissible medium temperature

Table 5.2 on page 4

Max. operating pressure of the pump

PN 10

Sound pressure level

< 35 dB(A)

Energy efficiency index

 0.23

EMC (electromagnetic compatibility)

General EMC: (2004/108/EC); EN 61800-3; EN 61000-6-1 to EN 61000-6-4

Emitted interference

EN 61000-6-3, formerly EN 50081-1 (building standard)

Interference immunity

EN 61000-6-2, formerly EN 50082-2 (industry standard)

Motor protection

Integrated motor protection as standard

Fault current



3.5 mA

1. Observe the manufacturer's specifications regarding mixing ratios. Add any additives to the medium to be pumped on the pressure side of the pump. 

Permissible 

Medium temperature

Permissible

Max. ambient temperature

-10 °C ... +95 °C

+ 40 °C

-10 °C ... +90 °C

+ 50 °C

-10 °C ... +80 °C

+ 55 °C

-10 °C ... +70 °C

+ 60 °C

0 °C ... +65 °C

+ 65 °C

Nominal width

Med

T

Med

-10 °C...+50 °C

+95 °C

G 2“AG

0.3 bar

1.0 bar

Summary of Contents for UPH 120-32 PK

Page 1: ...und Gebrauchsanweisung Installation and Operating Instruction Instruction d installation et d utilisation Umw lzpumpe mit automatischer Leistungs anpassung mittels PWM Circulating pump with automatic...

Page 2: ......

Page 3: ...aten DE 3 5 3 Lieferumfang DE 4 6 Beschreibung und Funktion DE 5 6 1 Beschreibung der Pumpe Abb 1 1 Anhang Seite II Abb 1 2 Anhang Seite II DE 5 6 2 Funktion der Pumpe DE 5 7 Installation und elektris...

Page 4: ...haben 2 3 Sicherheitshinweise f r den Betreiber Die bestehenden Vorschriften zur Unfallverh tung sind zu be achten Gef hrdungen durch elektrische Energie sind auszuschlie en Weisungen lokaler oder gen...

Page 5: ...e entsprechend der h heren Viskosit t zu korrigieren ACHTUNG Gefahr von Gesundheitssch den Die Werkstoffe der Pumpe k nnen Gesundheitssch den hervorrufen da sie nicht f r den Einsatz in Trinkwasser Zi...

Page 6: ...verh ltnis zu korrigieren thylen Propylenglykole mit Korrosionsschutzinhibitoren Handels bliche Sauerstoffbindemittel1 Handels bliche Korrosionsschutzmittel1 Handels bliche Kombinationsprodukte1 Hande...

Page 7: ...zdruck Sollwert HS bis zur Maximal Kennlinie p v Die Elektronik ver ndert den von der Pumpe einzu haltenden Differenzdruck Sollwert linear zwischen Hs und Hs Der Differenzdruck Sollwert H nimmt mit de...

Page 8: ...iten leicht m glich sind Die Montage ist so durchzuf hren das kein Tropfwasser auf den Pumpenmotor bzw Klemmenkasten tropfen kann 7 1 1 nderung der Modulposition Soll das Regelmodul in eine andere Pos...

Page 9: ...orderungen zu erf l len Nennstrom 10 A Nennspannung 250 V AC Ableitstrom je Pumpe Ieff 3 5 mA gem EN 60335 Ein bauseitiger Motorschutzschalter ist nicht erforderlich Ist ein solcher in der Installatio...

Page 10: ...tellung durch PWM Signal wird der f r eine Regelung erforderliche Soll Istwertvergleich von einem externen Regler bernommen Als Stellgr e wird den Pumpen von dem externen Heizungsregler ein Signal PWM...

Page 11: ...Intervallen von jeweils 30 Sekunden Wenn der Motor weiterhin blockiert wird er dauerhaft ausgeschaltet Dies kann nur durch Stromabschal tung ber mehr als 30 sec und anschlie endes Wiedereinschalten e...

Page 12: ...DE 10 452115 66 46 FD 0004 Deutsch UPH 120 32PK...

Page 13: ...5 3 Scope of supply EN 4 6 Description and function EN 5 6 1 Description of the pump Fig 1 1 Appendix on page II Fig 1 2 Appendix on page II EN 5 6 2 Pump functions EN 5 7 Installation and electrical...

Page 14: ...y notes for the operator Observe the valid accident prevention regulations It must be ensured that there are no risks resulting from electri cal energy Instructions resulting from local or general reg...

Page 15: ...damage to health The materials used in the pump can cause damage to health as they are not approved for use in domestic water circulating systems The pump is not approved for use in pure domestic wate...

Page 16: ...on the proportional mixing ratio Ethylene propylene glycols with corrosion protection inhibitor Standard oxygen binder1 Standard anticorrosive1 Standard combination products1 Standard cooling brines1...

Page 17: ...cross the entire permissible volume flow range p v The electronics change the differential pressure set point value to be maintained by the pump linearly between Hs and Hs The differential pressure se...

Page 18: ...an easily accessible position in order to facilitate subsequent service work The pump must be installed such that no water can drip onto the pump motor and or the terminal box 7 1 1 Module position ch...

Page 19: ...al voltage 250 V AC Leakage current per pump Ieff 3 5 mA according to EN 60335 No on site motor circuit breaker is necessary If a motor cir cuit breaker is already part of the system this must be by p...

Page 20: ...tion is carried out by an external controller A signal PWM is sent to the pumps from the external heating controller as a manipulated variable If the signal cable is disconnected from the pump PWM set...

Page 21: ...mum of 5 restarts take place at intervals of 30 seconds each If the motor still stalls it is switched off The power must be switched off for 30 seconds and then the sys tem must be restarted The deblo...

Page 22: ...EN 10 452115 66 46 FD 0004 English UPH 120 32PK...

Page 23: ...ristiques techniques FR 3 5 3 Fournitures FR 4 6 Description et fonction FR 5 6 1 Description de la pompe Fig 1 1 Annexes page II Fig 1 2 Annexes page II FR 5 6 2 Fonction de la pompe FR 5 7 Installat...

Page 24: ...ion 2 3 Consignes de s curit pour l exploitant Respecter les prescriptions existantes concernant la pr vention des accidents carter tous risques pouvant tre caus s par l nergie lec trique Respecter le...

Page 25: ...es selon la viscosit lev e ATTENTION Risque de dommages pour la sant Les mat riaux de la pompe peuvent entra ner des dommages pour la sant car ils ne sont pas con us pour l utilisation dans des syst m...

Page 26: ...pourcentage du m lange thyl ne propyl ne glycol avec inhibiteurs de corrosion liant d oxyg ne disponible dans le commerce1 produits anticorrosion disponibles dans le commerce1 produits de combinaison...

Page 27: ...one de d bit de refoulement autoris e p v l lectronique modifie la valeur consigne de pression diff rentielle respecter par la pompe de mani re lin aire entre Hs et Hs La valeur consigne de pression d...

Page 28: ...es positions de montage suivant la Fig 2 1 Annexes page III sont autoris es L arbre de la pompe doit tre l horizontale En cas de montage particulier il est possible en tournant le moteur de positionne...

Page 29: ...collier de fixation et assurer l tanch it contre les gouttes d eau la condensation Si n cessaire le c ble doit tre quip d un anneau d coulement des gouttes d eau pour emp cher que l eau ne p n tre dan...

Page 30: ...aleur r elle est prise en charge par un r gulateur externe En guise de grandeur de r glage un signal PWM est mis par le r gulateur de chauffage externe en direction des pompes Si le c ble de signal es...

Page 31: ...ffectu s des intervalles de 30 secondes Lorsque le moteur continue se bloquer il est mis hors tension de fa on durable Cela peut unique ment tre effectu en l arr tant pendant plus de 30 s et en la rem...

Page 32: ...FR 10 452115 66 46 FD 0004 Fran ais UPH 120 32PK...

Page 33: ...ounting position Emplacement de montage A III 3 Diagramme Diagrams Diagrammes A IV 3 1 Kennlinie Characteristic curve Courbe caract ristique UPH 120 32 PK A IV 4 Stromlaufpl ne Circuit diagrams Sch ma...

Page 34: ...Fig Fig 1 1 1 2 Legende Legend L gende Abb Fig Fig 1 2 Regelungsart p V aktiv Control type p V active Type de r gulation p V activ Regelungsart p C aktiv Control type p C active Type de r gulation p...

Page 35: ...452115 66 46 FD 0004 A III UPH 120 32PK Anhang Appendix Annexes 2 Einbaulage Mounting position Emplacement de montage Abb Fig Fig 2 1 Abb Fig Fig 2 2...

Page 36: ...2 PK 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 0 0 2 0 4 0 6 0 8 0 10 0 12 0 p C PWM 30 1 12 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 0 0 2 0 4 0 6 0 8 0 10 0 12 0 Durchflu in m h Flow rate in m h D bit en m h p V...

Page 37: ...0 320 360 0 0 2 0 4 0 6 0 8 0 10 0 12 0 P 1 W 30 1 12 Maximum 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 0 0 2 0 4 0 6 0 8 0 10 0 12 0 PWM p C 30 1 12 Durchflu in m h Flow rate in m h D bit en m h F rderh he...

Page 38: ...fpl ne Circuit diagrams Sch mas lectriques 4 1 Aderbelegung Pin configuration Brin occupation Lastkabel Load cable C ble de charge Abb Fig Fig 4 1 Signalkabel Signal cable C ble de signal Abb Fig Fig...

Page 39: ...t ATTENTION The pump wire is either placed directly on the heat pump manager or on the designated 3 level terminal block depending on the heat pump type ATTENTION Suivant le type de pompe chaleur le f...

Page 40: ...end for Circuit Diagrams L gendes des sch mas lectriques Jx Stecker von Nx Plug from Nx Connecteur de Nx K5 Sch tz Prim rpumpe Contactor primary pump contacteur pompe primaire KMx Koppelrelais Pumpe P...

Page 41: ...452115 66 46 FD 0004 A IX UPH 120 32PK Anhang Appendix Annexes...

Page 42: ...A X 452115 66 46 FD 0004 Anhang Appendix Annexes UPH 120 32PK...

Page 43: ...452115 66 46 FD 0004 A XI UPH 120 32PK Anhang Appendix Annexes...

Page 44: ...ales service addresses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d utilis...

Reviews: