7.5.3  Connection of electronically 

regulated circulating pumps

Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and
the electronically regulated circulating pump. This is not neces-
sary if the permissible operating current of 2 A and a maximum
starting current of 12 A are not exceeded in the electronically
regulated circulating pump or if express approval has been is-
sued by the pump manufacturer. 

ATTENTION!

!!

It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.

8

Commissioning

8.1 General Information

To ensure that commissioning is performed correctly, it should
only be carried out by an after-sales service technician author-
ised by the manufacturer. This may be a condition for an addi-
tional guarantee (see warranty service).

8.2 Preparation

The following items must be checked prior to commissioning:

All of the heat pump connections must be installed as de-
scribed in chapter 7.

The heat source system and the heating circuit must have
been filled and checked.

The dirt trap must be inserted in the brine inlet of the heat
pump.

All valves that could impair proper flow in the brine and
heating circuits must be open.

The heat pump manager must be adapted to the heating
system in accordance with the controller's operating in-
structions.

8.3 Commissioning procedure

The heat pump is commissioned via the heat pump manager.

ATTENTION!

!!

Start-up must be performed in accordance with the
installation and operating instructions of the heat pump
manager.

9

Cleaning / maintenance

9.1 Maintenance

To prevent faults due to sediment in the heat exchangers, care
must be taken to ensure that no impurities can enter either the
heat source system or the heating system. In the event that op-
erating malfunctions due to contamination occur nevertheless,
the system should be cleaned as described below.

9.2 Cleaning the heating system

The ingress of oxygen into the heating water circuit may result
in the formation of oxidation products (rust), particularly if steel
components are used. These enter the heating system via the
valves, the circulating pumps and/or plastic pipes. A diffusion-
resistant installation is therefore essential, especially with re-
gard to the piping of underfloor heating systems.

NOTE

º

We recommend the installation of a suitable corrosion
protection system to prevent the formation of deposits (e.g.
rust) in the condenser of the heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.
In the event of severe contamination leading to a reduction in
the performance of the liquefier in the heat pump, the system
must be cleaned by a heating technician.
Based on current information, we recommend using a 5%
phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5% formic
acid solution should be used.
In both cases, the cleaning fluid  should  be at room tempera-
ture. We recommend flushing the heat exchanger in the direc-
tion opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating
system circuit, we recommend connecting the flushing device
directly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the sys-
tem.
Acids must be used with care and the regulations of the em-
ployers liability insurance associations must be adhered to.
The instructions of the cleaning agent manufacturer must al-
ways be observed.

9.3 Cleaning the heat source 

system

ATTENTION!

!!

The supplied dirt trap must be inserted in the heat source inlet
of the heat pump to protect the evaporator against the ingress
of impurities.

The filter sieve of the dirt trap should be cleaned one day after
start-up. Further checks must be set according to the level of
dirt. If no more signs of contamination are evident, the filter can
be removed to reduce pressure drops.

Summary of Contents for SIH 90TU

Page 1: ...rauchsanweisung Sole Wasser W rmepumpe f r Innenaufstellung Installation and Operating Instruction Brine to Water Heat Pump for Indoor Installation Instuctionsd installation et d utilisation Pompe cha...

Page 2: ......

Page 3: ...Anschluss DE 6 7 4 Temperaturf hler DE 6 7 5 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 9 8 1 Allgemeine Hinweise DE 9 8 2 Vorbereitung DE 9 8 3 Vorgehensweise bei Inbetriebnahme DE 9 9 Pflege Re...

Page 4: ...en ACHTUNG Im W rmequelleneintritt der W rmepumpe ist der beiliegende Schmutzf nger zu montieren um den Verdampfer gegen Verunreinigungen zu sch tzen ACHTUNG Die Sole muss mindestens zu 25 aus einem F...

Page 5: ...zu berpr fen und zu protokollieren N here Angaben dazu befinden sich im beiliegenden Logbuch 1 4 Energiesparende Handhabung der W rmepumpe Durch das Betreiben dieser W rmepumpe tragen Sie zur Scho nun...

Page 6: ...Verfl ssiger 4 Verdichter 5 Filtertrockner 6 Economizer 4 Zubeh r 4 1 Anschlussflansche Durch den Einsatz der flachdichtenden Anschlussflansche kann das Ger t optional auf Flanschanschluss umgestellt...

Page 7: ...e Sole Wasser W rmepumpe muss in einem frostfreien und trockenen Raum auf einer ebenen glatten und waagerechten Fl che aufgestellt werden Dabei sollte der Rahmen rundum dicht am Boden anliegen um eine...

Page 8: ...zustand der Heizungsanlage sicherzustellen Dieses kann z B durch Installation eines doppelt differenz drucklosen Verteilers erreicht werden Sofern W rmepumpenmanager und Heizungsumw lzpumpen betriebsb...

Page 9: ...hren zu Fehlfunktionen und thermisch isolieren 7 4 4 Verteilsystem Hydraulik Kompaktverteiler und doppelt differenzdruckloser Verteiler fungieren als Schnittstelle zwischen der W rmepumpe dem Heizung...

Page 10: ...an den Haushaltsstrom anzuschlie en da sonst w hrend der EVU Sperre wichtige Schutzfunktionen au er Betrieb sind 3 Das EVU Sperrsch tz K22 mit Hauptkontakten und einem Hilfskontakt ist entsprechend d...

Page 11: ...en Sollte es dennoch zu derartigen Betriebsst rungen kommen ist die Anlage wie unten angege ben zu reinigen 9 2 Reinigung Heizungsseite Sauerstoff kann im Heizwasserkreis insbesondere bei Verwen dung...

Page 12: ...Kundendienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise spannungsfrei zu scha...

Page 13: ...5 55 m h Pa 15 5 93400 Mindestsoledurchfluss m h Pa 15 5 93400 4 3 Schall Leistungspegel nach EN 12102 dB A 70 4 4 Schalldruck Pegel in 1 m Entfernung2 dB A 55 5 Abmessungen Gewicht und F llmenge 5 1...

Page 14: ...ntspricht dem Betriebsger usch der W rmepumpe im Heizbetreib bei 35 C Vorlauftemperatur Der angegebene Schalldruckpegel stellt den Freifeldpegel dar Je nach Aufstellungsort kann der Messwert um bis zu...

Page 15: ...h Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestimmt gilt...

Page 16: ...eile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten Im...

Page 17: ...t source connection EN 6 7 4 Temperature sensor EN 6 7 5 Electrical connection EN 8 8 Commissioning EN 9 8 1 General Information EN 9 8 2 Preparation EN 9 8 3 Commissioning procedure EN 9 9 Cleaning m...

Page 18: ...st be inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities ATTENTION The brine must contain at least a 25 concentration of a monoethylene glyc...

Page 19: ...found in the accompanying log book 1 4 Energy efficient use of the heat pump By operating this heat pump you are helping to protect our en vironment Both the heating system and the heat source must be...

Page 20: ...Switch box 2 Evaporator 3 Liquefier 4 Compressor 5 Filter dryer 6 Economiser 4 Accessories 4 1 Connection flange The device can optionally be switched to flange connection using the flat sealing conne...

Page 21: ...r heat pump must be installed in a frost free dry room on an even smooth and horizontal surface The entire base of the frame should lie directly on the floor to ensure an adequate soundproof seal If t...

Page 22: ...eating system This can be accomplished for example by installing a dual dif ferential pressureless manifold The frost protection function of the heat pump manager is ac tive whenever the heat pump man...

Page 23: ...se malfunctions and thermally insulate 7 4 4 Hydraulic distribution system The compact manifold and the dual differential pressureless manifold function as an interface between the heat pump the heati...

Page 24: ...tream from the utility company blocking contactor or be connected to the household cur rent as important protection functions could otherwise be lost during a utility block 3 The utility company block...

Page 25: ...tion occur nevertheless the system should be cleaned as described below 9 2 Cleaning the heating system The ingress of oxygen into the heating water circuit may result in the formation of oxidation pr...

Page 26: ...an ATTENTION Work on the heat pump must only be performed by authorised and qualified after sales service technicians ATTENTION Disconnect all electrical circuits from the power source prior to openin...

Page 27: ...ound power level according to EN 12102 dB A 70 4 4 Sound pressure level at a distance of 1m2 dB A 55 5 Dimensions weight and filling quantity 5 1 Device dimensions 3 H x W x L mm 1890 x 1350 x 750 5 2...

Page 28: ...tion at 35 C flow temperature The specified sound pressure level represents the free sound area level The measured value can deviate by up to 16 dB A depending on the installation location 3 Note that...

Page 29: ...sions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not dete...

Page 30: ...EN 14 452234 66 73 FD 9910 www gdts one English SIH 90TU...

Page 31: ...c t source de chaleur FR 6 7 4 Sonde de temp rature FR 6 7 5 Branchements lectriques FR 8 8 Mise en service FR 9 8 1 Remarques d ordre g n ral FR 9 8 2 Pr paratifs FR 9 8 3 Proc dures suivre lors de...

Page 32: ...l entr e de la source de chaleur de la pompe chaleur le collecteur d impuret s fourni afin de prot ger l vaporateur ATTENTION La teneur de l eau glycol e en produit antigel base de mono thyl ne glycol...

Page 33: ...de la pompe chaleur pour conomiser de l nergie En utilisant cette pompe chaleur vous contribuez pr server l environnement Pour obtenir un fonctionnement efficace il est tr s important de dimensionner...

Page 34: ...par le client 1 Bo tier lectrique 2 vaporateur 3 Condenseur 4 Compresseur 5 Filtre d shydrateur 6 conomiseur 4 Accessoires 4 1 Brides de raccordement Les brides de raccordement joint plat permettent...

Page 35: ...leur eau glycol e eau doit tre install e dans un local sec l abri du gel sur une surface plane lisse et horizon tale Le ch ssis de la pompe chaleur doit adh rer au sol sur toute sa circonf rence afin...

Page 36: ...que soit l tat de fonctionnement de l installation de chauffage Ce d bit peut tre obtenu en instal lant un distributeur double sans pression diff rentielle La fonction de protection antigel du gestio...

Page 37: ...fix e avec un collier serrer fond des sondes mal fix es engendrent des d fauts et isol e 7 4 4 Syst me de distribution hydraulique Le distributeur compact et le distributeur double sans pression diff...

Page 38: ...oit tre sous tension perma nente Elle doit donc tre plac e en amont du contacteur de blocage de la soci t d lectricit ou reli e au courant domestique faute de quoi certaines fonctions de protec tion e...

Page 39: ...en service 8 1 Remarques d ordre g n ral Pour garantir une mise en service en r gle cette derni re doit tre effectu e par un SAV agr par le constructeur Le respect de cette clause permet de b n ficier...

Page 40: ...condenseur de la pompe chaleur Il faut ensuite soigneusement rincer les tuyauteries l aide de produits neutralisants ad quats afin d viter tous dommages provoqu s par d ventuels restes de d tergent d...

Page 41: ...00 4 3 Niveau de puissance acoustique selon EN 12102 dB A 70 4 4 Niveau de pression sonore 1m de distance2 dB A 55 5 Dimensions poids et capacit 5 1 Dimensions de l appareil3 H x l x L mm 1890 x 1350...

Page 42: ...au bruit de fonctionnement de la pompe chaleur en mode chauffage avec une temp rature d part de 35 C Le niveau de pression sonore indiqu est celui d une propagation en champ libre La valeur mesur e p...

Page 43: ...mation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Exigences d informat...

Page 44: ...FR 14 452234 66 73 FD 9910 www gdts one Fran ais SIH 90TU...

Page 45: ...nal diagram Sch ma de branchement A IX 3 6 Legende Legend L gende A X 4 Hydraulische Einbindungsschemen Hydraulic integration diagrams Sch mas d int ration hydraulique A XII 4 1 Monovalente W rmepumpe...

Page 46: ...ing water supply Heat pump outlet Filetage int ext 3 Source de chaleur Entr e dans la PAC Filetage int ext 3 Source de chaleur Sortie de la PAC Filetage int ext 2 Retour eau de chauffage Entr e dans l...

Page 47: ...in kW incl power input to pump Consommation de puissance in kW y compris part de consommation de la pompe Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Verdampfer Evaporator Evaporate...

Page 48: ...euils d utilisation 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 10 5 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperature C Temp rature d eau de chauffage C W rmequelleneintrittstempe...

Page 49: ...www gdts one 452234 66 73 FD 9910 A V SIH 90TU Anhang Appendix Annexes 3 Stromlaufpl ne Wiring diagrams Sch mas lectriques 3 1 Steuerung Control Commande...

Page 50: ...A VI 452234 66 73 FD 9910 www gdts one Anhang Appendix Annexes SIH 90TU 3 2 Steuerung Control Commande...

Page 51: ...www gdts one 452234 66 73 FD 9910 A VII SIH 90TU Anhang Appendix Annexes 3 3 Last Load Charge...

Page 52: ...A VIII 452234 66 73 FD 9910 www gdts one Anhang Appendix Annexes SIH 90TU 3 4 Anschlussplan Terminal diagram Sch ma de branchement...

Page 53: ...www gdts one 452234 66 73 FD 9910 A IX SIH 90TU Anhang Appendix Annexes 3 5 Anschlussplan Terminal diagram Sch ma de branchement...

Page 54: ...itch water to water heat pump Pressostat basse pression pompe chaleur eau eau F7 Hei gasthermostat F10 1 Durchflussschalter Prim rkreis Flow rate switch for primary circuit Commutateur de d bit circui...

Page 55: ...sonde d ambiance sonde 3 me circuit de chauffage R18 Hei gasf hler Hot gas sensor Sonde de gaz chaud R20 Schwimmbadf hler Swimming pool sensor Sonde de piscine R24 R cklauff hler Prim rkreis Return se...

Page 56: ...serbereitung Monovalent heat pump system with three heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur avec trois circuits de chauffage et production d eau c...

Page 57: ...system with two heating circuits and domestic hot water preparation Installation bivalente avec deux circuits de chauffage et production d eau chaude sanitaire R1T DDV X3 R1 X2 M18 M18 K2 K21 E9 R3 X...

Page 58: ...lycol e eau Reihen Pufferspeicher Buffer tank connected in series Ballon tampon en s rie Warmwasserspeicher Hot water cylinder Ballon d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater...

Page 59: ...rkl rung Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous...

Page 60: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Reviews: