EN-12
452237.66.52 · FD 9912
www.gdts.one
English
SI 90TU - SI 130TU
12 Device information
1
Type and order code
SI 90TU
2
Design
Heat source
Brine
2.1
Model
Universal
2.2
Controller
integrated
2.3
Thermal energy meter
Integrated
2.4
Installation location
Indoors
2.5
Performance levels
2
3
Operating limits
3.1
Heating water flow
1
2
°C
20 to 62 ± 2
3.2
Brine (heat source)
°C
-5 to 25
3.3
Antifreeze
Monoethyleneglycol
3.4
Minimum brine concentration (-13 °C freezing temperature)
25 %
4
Flow / sound
4.1
Heating water flow / free compression (max).
Nominal flow in accordance
with EN 14511
at B0...-3 / W35...30
m³/h / Pa
15.1 / 61000
at B0...-3 / W45...40
m³/h / Pa
14.3 / 64000
at B0...-3 / W55...47
m³/h / Pa
8.6 / 78000
Minimum heating water flow
m³/h / Pa
8.6 / 78000
4.2
Brine flow rate / free compression (max).
Nominal flow in accordance
with EN 14511
at B0...-3 / W35...30
m³/h / Pa
21.6 / 57000
at B0...-3 / W45...40
m³/h / Pa
19.4 / 67000
at B0...-3 / W55...47
m³/h / Pa
17.1 / 78000
Minimum brine flow rate
m³/h / Pa
17.1 / 78000
4.3
Sound power level according to EN 12102
dB(A)
66
4.4
Sound pressure level at a distance of 1m
3
dB(A)
53
5
Dimensions, weight and filling quantity
5.1
Device dimensions
4
H x W x L mm
1890 x 1350 x 750
5.2
Weight of the transportable unit(s) incl. packaging
kg
604
5.3
Device connections for heating
inches
Rp 2½“
5.4
Device connections for heat source
Inches
Rp 2½“
5.5
Refrigerant / total filling weight
type/kg
R410A / 23.0
5.6
GWP value / CO
2
equivalent
--- / t
2088 / 48
5.7
Refrigeration circuit hermetically sealed
yes
5.8
Lubricant / total filling quantity
type/litres
Polyolester (POE) / 7.3
5.9
Volume of heating water in device
Litres
21
5.10 Volume of heat transfer medium in device
Litres
21
6
Electrical connection
6.1
Supply voltage / fuse protection / RCD-Type
3~/PE 400 V (50 Hz) / C 80A / A
6.2
Control voltage / fuse protection / RCD-Type
1~/N/PE 230 V (50 Hz) / C 13A / A
6.3
Degree of protection according to EN 60 529
IP 21
6.4
Starting current with soft starter
A
53
6.5
Nominal power consumption B0 W35 / max. power consumption
5
kW
18.5 / 35.3
6.6
Nominal current B0 W35 / cos
A / ---
33.4 / 0.8
6.7
Power consumption of compressor protection
(per compressor)
W
90 / thermostatically controlled
6.8
Power consumption of pumps
kW
up to 1.25