EN-12
English
13
Device information for brine-to-water heat pumps for heating purposes SI 14TE - SI 21TE
1
Type and order code
SI 14TE
SI 17TE
SI 21TE
2
Design
2.1
Degree of protection according to EN 60 529
IP 20
IP 20
IP 20
2.2
Installation Location
Indoors
Indoors
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow
°C
Up to 58
Up to 58
Up to 58
Brine (heat source)
°C
-5 to +25
-5 to +25
-5 to +25
Antifreeze
Mono-ethylene glycol Mono-ethylene glycol Mono-ethylene glycol
Minimum brine concentration (-13 °C freezing temperature)
25%
25%
25%
3.2
Temperature spread of heating water (flow/return flow)
at B0 / W35
K
9.6
5.0
9.3
5.0
11.3
5.0
3.3
Heat output / COP
at B-5 / W55
1
kW / ---
12.5 / 2.6
14.4 / 2.6
17.9 / 2.5
at B0 / W45
1
kW / ---
14.1 / 3.5
16.2 / 3.4
19.8 / 3.2
at B0 / W50
1
kW / ---
14.2 / 3.4
16.7 / 3.2
20.4 / 3.1
at B0 / W35
1
kW / ---
14.5 / 4.5
14.4 / 4.3
17.1 / 4.6
16.9 / 4.4
21.1 / 4.3
20.8 / 4.1
3.4
Sound power level
dB(A)
56
58
59
3.5
Heating water flow with an internal pressure differential of m³/h / Pa
1.3 / 4800 2.5 / 17600 1.5 / 4000 2.9 / 15000 1.6 / 4600 3.6 / 23000
3.6
Brine throughput with an internal pressure
differential (heat source) of
m³/h / Pa
3.5 / 20000 3.3 / 18000 3.8 / 18000 3.8 / 18000 5.5 / 10000 5.4 / 9800
3.7
Refrigerant; total filling weight
type / kg
R407C / 2.1
R407C / 2.3
R407C / 4.5
3.8
Lubricant; total filling weight
type / litres
Polyolester
(POE) / 1.95
Polyolester
(POE) / 1.77
Polyolester
(POE) / 4.1
4
Dimensions, connections and weight
4.1
Device dimensions without connections
2
H x W x L mm
805
×
650
×
462
805
×
650
×
462
1445
×
650
×
575
4.2
Device connections to heating system
Inch
G 1¼" external
G 1¼" external
G 1¼" external
4.3
Device connections to heat source
Inch
G 1¼" external
G 1¼" external
G 1½" external
4.4
Weight of the transportable unit(s) incl. packing
kg
130
133
225
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
400 / 16
400 / 16
400 / 20
5.2
Nominal power consumption
1
B0 W35
kW
3.22
3.37
3.72
3.86
4.91
5.10
5.3
Starting current with soft starter
A
26
27
29
5.4
Nominal current B0 W35 / cos
ϕ
A / ---
5.81 / 0.8
6.08 / 0.8
6.35 / 0.8
6.64 / 0.8
8.86 / 0.8
9.2 / 0.8
6
Complies with the European safety regulations
3
3
3
7
Additional model features
7.1
Water in device protected against freezing
4
Yes
Yes
Yes
7.2
Performance levels
1
1
1
7.3
Controller internal/external
Internal
Internal
Internal
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should
also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
2. Note that additional space is required for pipe connections, operation and maintenance.
3. See CE declaration of conformity
4. The heat circulating pump and the heat pump manager must always be ready for operation.