LI 11TES - LI 16TES
12 Device Information
1
Type and order code
LI 11TES
LI 16TES
2
Design
Heat source
Air
Air
2.1
Model
Universall
Universall
2.2
Controller
Integrated
Integrated
2.3
Thermal energy metering
Optional (as an accessory)
Optional (as an accessory)
2.4
Installation location
Indoors
Indoors
2.5
Performance levels
1
1
3
Operating limits
3.1
Heating water flow / return
° C
up to 60
1
± 2 / from 18
up to 60
1
± 2 / from 18
3.2
Air °
C
-20 to +35
-20 to +35
4
Flow / sound
4.1
Heating water flow internal pressure differential
Nominal flow according to EN 14511 at A7 / W35-30
m³/h / Pa
1,9 / 17400
3,1 / 22300
at A7 / W45-40
m³/h / Pa
1,8 / 15500
2,9 / 18900
at A7 / W55-47
m³/h / Pa
1,1 / 6100
2,0 / 9000
Minimum heating water flow
m³/h / Pa
1,0 / 5100
1,4 / 4400
4.2
Sound power level according to EN 12102
device/external
dB(A)
51 / 53
54 / 55
4.3
Sound pressure level at a distance of 1 m indoors
2
dB(A)
46
49
4.4
Heating water flow
m³/h / Pa
with an internal pressure differential of
m³/h / Pa
3800 / 0
3200 / 25
5000 / 0
4000 / 25
5
Dimensions, weight and filling quantities
5.1
Device dimensions
3
H x B x T mm
1360 x 750 x 880
1570 x 750 x 880
5.2
Weight of the transportable unit(s) incl. packaging
kg
216
235
5.3
Device connections for heating system
Inches
R 1¼“
R 1¼“
5.4
Air duct connection (air intake side)
mm
500 x 500
650 x 650
Air duct connection (air outlet side)
mm
500 x 500
650 x 650
5.5
Refrigerant; total filling weight
type / kg
R410A / 2,3
R410A / 3,5
5.6
Lubricant; total filling quantity
type / litres
Polyolester (POE) / 1,2
Polyolester (POE) / 1,9
5.7
Volume of heating water in device
litres
3,4
3,5
6
Electrical connection
6.1
Supply voltage / fuse protection
separate infeed:
heat pump
3~/PE 400 V (50 Hz) / C10 A
3~/PE 400 V (50 Hz) / C16 A
separate infeed:
2nd heat generator
3~/PE 400 V (50 Hz) / C10 A
3~/PE 400 V (50 Hz) / C10 A
combined infeed:
heat pump + 2nd heat generator
3~/PE 400 V (50 Hz) / C20 A
3~/PE 400 V (50 Hz) / C25 A
RCD-Type
A
A
6.2
Control voltage; fuse protection
1~/N/PE 230 V (50 Hz) / C13 A
1~/N/PE 230 V (50 Hz) / C13 A
6.3
Degree of protection according to EN 60 529
IP 21
IP 21
6.4
Starting current limiter
Soft starter
Soft starter
6.5
Rotary field monitoring
yes
yes
6.6
Starting current
A
19
28
6.7
Nominal power consumption at A7/W35 / max. consumption
4
(without 2nd heat generator)
kW
2,4 / 4,1
4,1 / 6,9
6.8
Nominal current at A7/W35 / cos
A / --
4,5 / 0,76
7,4 / 0,8
6.9
Power consumption of compressor protection (per compressor)W
--
--
6.10 Power consumption of fan
W
up to 250
up to 300
6.11 Output of electric heating element (2nd heat generator)
kW
6
6