www.glendimplex.de

452163.66.89-EN · FD 0103

EN-5

LA 60S-TU 

English

4

Transport

CAUTION!

!!

When transporting the heat pump, ensure that it is not tilted
more than 45° (in any direction).

Transport to the final installation location should be carried out
with a pallet. The basic device can be transported with a lift
truck or a crane.
The transport eyebolts must be removed after crane transport,
and the openings must be closed using the vent plugs supplied.
After transportation, the transport fastening in the device is to
be removed from both sides of the base.

CAUTION!

!!

Before start-up, the transport fastening must be removed.

5

Installation

5.1 General

The device must be installed on a permanently level, smooth
and horizontal surface. The frame around the device must lie
tightly against the floor to guarantee adequate sound insula-
tion, to prevent water-bearing parts from cooling out and to
protect the inside of the device from small animals. If this is not
the case, additional insulation measures may be necessary. To
prevent small animals from entering the inside of the device, it
may be necessary to seal the connection hole in the base plate,
for example. Furthermore, the heat pump should be set up so
that the air outlet direction of the ventilator is perpendicular to
the main wind direction to allow unrestricted defrosting of the
evaporator. The heat pump is designed for installation on even
ground. If the installation conditions differ (installation on a
platform or flat roof) or there is a greater risk of the heat pump
tipping over (due to an exposed position or high wind expo-
sure), additional protection against tipping over must be pro-
vided. The responsibility for the
heat pump installation lies with the specialist system construc-
tion company. During the installation, local requirements such
as building regulations, static load of the building, and wind ex-
posure must be accounted for. 
It must be possible to carry out maintenance work without hin-
drance. This is ensured when observing the distances to solid
walls as shown in the figure.

The specified dimensions are valid for stand-alone installation
only.

CAUTION!

!!

Do not restrict or block the area around the air intake or outlet.

CAUTION!

!!

Observe country-specific building regulations!

CAUTION!

!!

For installation close to walls the physical influences of the
building must be considered. No windows or doors should be
present in the area surrounding the air outlet of the ventilator.

Remove/screw in  
transport lock 

(4x)

1,0 m

2 m

0

m

0

,8

m

Summary of Contents for LA 60S-TU

Page 1: ...Order no 452163 66 89 EN EN FD 0103 LA 60S TU Installation and Operating Instruction Air to Water Heat Pump for Outdoor Installation Glen Dimplex Deutschland Dimplex ...

Page 2: ......

Page 3: ...N 6 6 2 Connection on heating side EN 6 6 3 Electrical connection EN 7 7 Start up EN 8 7 1 General EN 8 7 2 Preparation EN 8 7 3 Procedure EN 8 8 Cleaning maintenance EN 8 8 1 Maintenance EN 8 8 2 Cleaning the heating system EN 8 8 3 Cleaning the air system EN 9 9 Faults troubleshooting EN 9 10 Decommissioning disposal EN 9 11 Device information EN 10 12 Product information as per Regulation EU No...

Page 4: ...cal sensory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been instructed in the safe use of the unit and understand the associated potential dangers Children must not play with the device Cleaning and user maintenance must not be carried out by children without su pervision CAUTION When operating or maintaining a heat pump the legal requirements o...

Page 5: ...rrounding air is drawn in by the fan and fed through the evap orator heat exchanger The evaporator cools the air i e it ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is brought to a higher temperature level by increasing its pressure with the aid of the electrically driven compressor It is then transferred to the heating...

Page 6: ...e swung out after removing the lower front cover and loosening the fasten ing screw located in the upper left hand corner The switch box contains the supply connection terminals as well the power contactors and the soft starter unit 3 3 Heat pump manager Use the heat pump manager included in the scope of supply to operate the air to water heat pump The heat pump manager is a convenient electronic ...

Page 7: ...xample Furthermore the heat pump should be set up so that the air outlet direction of the ventilator is perpendicular to the main wind direction to allow unrestricted defrosting of the evaporator The heat pump is designed for installation on even ground If the installation conditions differ installation on a platform or flat roof or there is a greater risk of the heat pump tipping over due to an e...

Page 8: ... system must be flushed to remove any impurities residue from sealants etc Any accumulation of deposits in the liquefier could cause the heat pump to completely break down Once the heat pump has been connected to the heating sys tem it must be filled de aerated and pressure tested Consideration must be given to the following when filling the system Untreated filling water and make up water must be...

Page 9: ...nection 3 lines cables must be routed to the heat pump in total A standard 5 core cable is used to connect the heat pump to the power supply The cable must be provided on site The conductor cross section is selected in accordance with the power con sumption of the heat pump see attachment Device Infor mation and the applicable VDE EN and VNB regulations An all pole disconnecting device with a cont...

Page 10: ...y time 7 When all heat circuits are fully open and a return tempera ture of at least 22 C is maintained the heat pump start up is complete CAUTION Operating the heat pump at low system temperatures may cause the heat pump to break down completely 8 Cleaning maintenance 8 1 Maintenance To protect the paintwork avoid leaning anything against the device or putting objects on the device External heat ...

Page 11: ...ved in the vicinity of the air intake and air outlet grids to ensure that the minimum air flow is maintained To ensure proper drainage from the condensate tray it must be regularly inspected and cleaned if necessary All panelling can be removed to allow accessing the inside of the device The two sash fasteners must be opened for this purpose The cover must then be slightly tilted forward and lifte...

Page 12: ...g quantities 5 1 Device dimensions without connections5 H x W x L mm 2300 x 1900 x 1000 5 2 Weight of the transportable unit s incl packaging kg 870 5 3 Device connections for heating Inches Rp 2 5 4 Refrigerant total filling weight Type kg R407C 15 7 5 5 GWP value CO2 equivalent t 1774 27 5 6 Refrigeration circuit hermetically sealed yes 5 7 Lubricant total filling quantity Type litres POE RL32 3...

Page 13: ...ow temperature applies to a set minimum heating water flow 3 The heat output and COP is reduced by approx 5 in lower operation 4 The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 55 C The specified sound pressure level represents the free sound area level The measured value can deviate by up to 16 dB A depending o...

Page 14: ... Emissions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency ηwh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen the default degradation is Cdh 0 9 not applicable For air to water heat pumps Rated air flow rate outdoors For water brine to water heat pumps Rated brine or water fl...

Page 15: ...asservorlauf Ausgang aus Wärmepumpe R 2 2 Heizwasserrücklauf Eingang in Wärmepumpe R 2 3 Durchführungsbereich Elektroleitungen Kondensat 4 Optionale Durchführung Elektroleitungen 5 Optionale Durchführung Kondensat Frostschutz erforderlich Heating water flow Output from heat pump R 2 Heating water return flow Input into the heat pump R 2 Feedthrough area Electrical lines condensate Optional feedthr...

Page 16: ...on en Pa Verflüssiger Condenser Condenseur 0 1 2 3 4 5 6 7 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 Lufteintrittstemperatur in C Air inlet temperature in C Température d entrée d air en C 35 Leistungszahl incl Pumpenleistungsanteil Coefficient of performance incl power input to pump Coefficient de performance y compris part de consommation de la pompe 45 55 0 5 10 15 20 25 30 35 40 45 50 55 60 65...

Page 17: ...K Water outlet 0 2 K Sortie d eau 0 2 K Die maximalen Vorlauftemperaturen werden beim geforderten Mindestheizwasserdurchfluss erreicht The maximum flow temperatures are achieved at the specified minimum heating water flow Les températures départ maximales sont atteintes en cas de débit minimum d eau de chauffage donné Wassereintritt Water inlet Entrée d eau Bei Luft Wasser Wärmepumpen stellt die m...

Page 18: ...EN 16 452163 66 89 EN FD 0103 www glendimplex de English LA 60S TU 15 Integration diagram 15 1 Hydraulic integration diagrams R2 2 ...

Page 19: ...lve Temperature sensor Flexible connection hose Check valve Three way mixer Air to water heat pump Heat pump manager Buffer tank connected in series Hot water cylinder E9 Flange heater hot water E10 1 Immersion heater K20 Contactor for HG2 K21 Contactor for flange heater M15 Heat circulating pump for heating circuit 2 M16 auxiliary circulating pump M18 Hot water loading pump M22 Mixer for heating ...

Page 20: ...nical support After sales service technical support and spare parts Assistance before and after installation of your equipment T 49 9221 709 545 F 49 9221 709 924545 Mon Thu 7 30 to 16 30 Fri 7 30 to 15 00 service dimplex glendimplex de Our 24 hr hotline is available for emergencies outside normal opening times Request after sales service on the internet www glendimplex de dienstleistungen dimplex...

Reviews: