❖Adjusting Press cam signals
Feed signal adjusting
Set the feed start position to feed signal OFF position.
Press cam signal
When you make the feed starts on 270°,
0°
Set the ON angle of feed to 240°, and set the OFF angle to 270°
270°
90°
ON
240°
Release signal adjusting
180°
0°
When the release angle is assumed to 200°from 200°,
60°
you turn on the press cam signal in 110 degress,
and turn off in 200 degress.
270°
90°
110°
200°
180°
❖Release setting in the controller 【 (_Release Mode) 】
【 (_Release Mode) 】 The display is the back screen of 【 Feed Length 】.
Using "+" or "-" switch, Set the release mode.
The Release mode are as follows, Release OFF, Synchronization press cam signal, Timer finish.
Display and contents
Invalid the release signal, Release off state.
Release angles setting. It can be input from 1°to 50°.
Input the release strat using the press cam signal.
Release timer setting. It can be input from 0.001sec to 0.05 sec.
Input time period, the release carry out.
Input the release strat using the press cam signal.
The delay time will vary depending in the springs pressure.
NOTE
Need to set the ON of the feed signal to the
feed completed angles when using option
"Overrun-Function".
Set the ON to the release start angle, and set
the OFF to the finish.
The retention angles of the release ON must
be 25 degrees or more.
Need to adjust the signal of the release
start even if the release system is used a
time setting of timer or angles.
The Release mode is supposed to display on the "Feed Length" after displaying digit of lowest of "Feed
Length"
the control calculates the release time from the setting SPM and the
anggles, the release will operate in the time range.
~
Feed Length (_Release Mode )
Contents
_ _ Sync
Synchronization press cam signal
_ _ _ OFF
_ _ _ A01
NOTE
The release operation is delayed due to air cylinder.
_ _ _ A50
_ _ _ T01
~
_ _ _ T50