Chapter 2 - Specifications
2-2
Flex Network User Manual
Flex Network I/F Unit
Flex Network I/O Unit
2.1.2
Environmental
Operating Temperature
0
o
C to 50
o
C (cannot be higher than GLC unit)
Storage Temperature
-20
o
C to +60
o
C
Operating Humidity
20%RH to 85%RH (non-condensing)
Storage Humidity
20%RH to 85%RH (non-condensing)
Air Purity (Dust)
0.1mg/m
3
or less (non-conductive levels)
Corrosive Gasses
Free of corrosive gasses
Vibration Endurance
10Hz to 25Hz 19.6m/s
2
(in X,Y,Z directions for 30min. each)
Noise Immunity
(via noise simulator)
Noise Duration: 1000Vp-p
Pulse Duration: 1
µ
s
Rise Time: 1ns
Electrostatic Discharge
Immunity
GLC100-FN11: 4kV (contact discharge)
GLC100-FN41: 6kV (IEC61000-4-2, RH-1/ESD-3)
FN-X16TS11/FN-X16TS41
FN-XY08TS11/FN-XY08TS41
FN-Y16SK41
FN-Y16SC41
FN-Y08RL11/FN-Y08RL41
FN-X32TS41
FN-XY16SK41
FN-XY16SC41
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Air Purity (Dust)
Corrosive Gasses
Vibration Endurance
5Hz to 55Hz
60m/s
2
(in X,Y,Z directions for 2 hours each)
IEC61131-2 (JIS B 3501) compliant
When vibration IS NOT continuous:
10Hz to 57Hz 0.075mm,
57Hz to 150Hz 9.8m/s
2
When vibration IS continuous:
10Hz to 57Hz 0.035mm,
57Hz to 150Hz 4.9m/s
2
X,Y,Z directions for 10 times (80 min.)
Shock Endurance
300m/s
2
(for 10ms in X,Y, Z directions -
3 times each)
IEC61131-2 (JIS B 3501) compliant
147 m/s
2
(for 11ms in X, Y, Z directions
- 2 times each)
Noise Immunity
(via noise simulator)
Electrostatic Discharge
Immunity
Noise Voltage: 1000Vp-p, Pulse Duration: 1
µ
s, Rise Time: 1ns
6kV (IEC61000-4-2, RH-1/ESD-3)
0
o
C to 55
o
C
-25
o
C to +70
o
C
5%RH to 95%RH (non-condensing) (wet bulb temperature: less than 39°C)
0.1mg/m
3
or less (non-conductive levels)
5%RH to 95%RH (non-condensing) (wet bulb temperature: less than 39°C)
Free of corrosive gasses