IPP-S Installation guide Digipower Inc.
17
Event Action
Event:
DO trigger conditions, the four options can only be chosen one by click check box.
DI:
Select DI1 ~ 4, then choose open or close.
Circuit: Select Circuit1 ~ 12, select the Warning threshold or Overload threshold, and then
select Occurs or Removed.
ENV:
Select ENV1~2, Select Temperature Overrun or Temperature Underrun or Humidity
Overrun or Humidity Underrun, and then select Occurs or Removed.
Trap:
First enter the object code, the options of Value are Ignore, Integer and String, then
enter Integer or String, finally enter Trap IP address.
Action:
DO will be actuated by Event trigger conditions are met, can be multiple selected by
click check box. Enter the delay seconds, then select Open or Close.
Event List:
All the pre-define events are saved in this list.
Delete: Click the check box for all or single event, then click delete button.
Enable: Click the enable check box, activate the action of event.