ENGLISH
- 11 -
TECHNICAL FEATURES
Dimensions
•
Box 90x90X130 mm included terminal blocks.
•
Front panel 96X96 mm.
•
Weight 0,6 Kg.
Power Supply
•
Power supply (24÷240) Volt AC/DC ± 10% 50/60 Hz without polarity respect,
absorption 4 VA.
Inputs
•
Eight analogical inputs, temperature control and mapping with PT100 sensor at
three wires inside range from -10 °C to +200 °C.
Outputs
•
Four relays 250V AC, 5A max (resistive load), free switch contact
•
Serial communication port RS485 full duplex protocol of MODBUS – RTU.
Characteristics
•
Self-extinguishable NORYL Box.
•
Display with light segments.
•
Visualisation of max temperature and the relevant channel in the automatic mode.
•
Alerts of pre-alarm, alarm, probes fault, fanning, manual function, historic highs.
•
System programming directly by frontal panel.
•
Possibility to select independently each channel.
•
Limit of alarm and pre-alarm settable in the range (-9°C ÷ 199°C).
•
Precision ± 1% on full scale ± 1 digit.
•
Cooling fan control on three or four channels.
•
Comparison of temperature for cooling fan between two different levels (L and H).
•
Four selectable operating modes.
•
Detection of fault probes, maximum flexibility of managing and semplicity of
programming, checking of validity of the insert data during programming phase.
•
Continuos storage of planned and reached values by each channel (limits and
historic highs).