S=6 4800 bps, S=7 9600 bps, S=8 14400 bps, S=9 19200 bps.
Others communications parameters (not settable) are parity NONE,
data bit 8, stop bit 1.
It is possible in addition to set a delay d in 1/100 seconds between
the end of reception of a valid command (data and address right)
and the following ME100 V3 transmission, to permit to the supervisor
system to put it in receive mode.
The default delay is 25 1/100 seconds.
At the end the device asks an address U to work correctly in a RS485
network; the default address is zero, for this reason it is better not
to use this address as a valid address on the network to avoid that
other devices, not yet configured, can cause a conflict.
Default configurations:
F=0, P=140, A=160, L=90, H=100, t=0, d=25, S=9, U=0
Anyway the necessary time for programming is checked.
Over 1 minute from beginning of the programming phase, the same
is interrupted and not saved so the previous set limits remain active.
At the end of programming the new data will be saved in memory,
the device executes a display test and the system is prearranged in
automatic way and visualises the maximum measured temperature
and the relative channel.
DATA VISUALIZATION
Referring to F it is possible to show all parameters of interest by
buttons UP and DOWN. To show one specific parameter, or one
specific measure of temperature, select it and push the button
AUTO/MANUAL, the MANUAL LED turns on to flag a manual
status mode. To return to the normal automatic mode push again
AUTO/MANUAL button.
During automatic working the higher temperature and the relative
number of channel appear on the display. To visualize the
maximum values of the machine push and hold the buttons AUTO/
MANUAL and ENTER/TEST at the same time. The visualisation of
16
ENGLISH