Dialight DuroSite Operating Instructions Manual Download Page 5

 
 

 
 

9100127275499 REV A 

Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727 

Tel: 

732 919 3119

  Fax: 732 751 5778  www.dialight.com 

  

 

DuroSite

®

  Emergency Stainless Steel LED Linear Luminaire r industrial areas 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
Conformity with Standards

 

This equipment conforms to the standards specified in 
the Declaration of Conformity.  
  
It has been designed, manufactured and tested in 
accordance with BS EN 9001.  
  
2004/108/EC:EC Directive for electromagnetic 
compatibility. 
 
Equipment Application 
This lighting equipment is intended for use in an 
industrial area. 
The product can be used inside or outside to  
illuminate industrial areas  
 
Mounting the Luminaire 
Assemble the mounting bracket to the luminaire with 2 off 
M8 x 1.25 by 16mm bolts. Torque specification: 2.0 Nm 
maximum. 
 
Installation 
Ensure that the mains voltage supply is disconnected 
before connecting the luminaire. Install the  
equipment in accordance with the manufacturer’s 
instructions as well as any other applicable electrical 
codes.  
  
Always transport and store the equipment in its original 
packaging and keep in a dry location.  
  
When unpacking check for any cracks or damage in the 
housing, end covers and lens. If in doubt, do not install!  
  
All EL and ELE luminaires come complete with through wire 
capabilities and as such, the mains can enter the luminaire 
from either end. All EL and ELE luminaires come with two 
entry points at each end to allow for mains in, switched live 
in and through wires out on separate cables if required. 
 
Opening the terminal tray  
To open the tray, completely remove the two 4mm HEX 
socket screws at either the emergency module end or the 
luminaire end. Once these are removed, the tray can be 
slid out exposing the terminal block. The terminal blocks are 
mounted to the front sides of the trays (where the front side 
is the light output side) This gives easy access to the 
terminals when the luminaire is mounted in position. 
 
The terminal tray is captive and will not fall out when slid 
open to its max position.  
  
The terminal tray slides back into position once the wires are 
connected to the terminal block (See Electrical 
connections on Page 3). The gear tray should be slid back 
with care ensuring no cables or wires are overstressed or 
trapped. When replacing the end covers, ensure the seals 
are clean and undamaged. If the covers are not fully in 
place the screws may be difficult to engage and can be 
cross-threaded. Do not allow any cables to be trapped by 
the end covers or terminal tray. Ensure that all wires are 
clear from the screw entry points.  
 
 
The cable glands used with this fixture must be rated  
IP66/67 or better to maintain the protection level of the 
luminaire. A locknut is required for each cable gland to 
ensure they are securely fastened to the end covers. 
 
Cable gland with O-ring min. thread length C = 10mm. 

P

 = M20 x 1,5mm 

P

 = M25 x 1,5mm (add 4  

       suffix to part code) 
 
 
 
 
  
 
 
 
 

 
 
 
 
The cable used must be suitable for the site application 
and/or the site requirements.  
  
When assembling the cable entries for the mains 
connection, always observe the manufacturers 
specifications for the glands used.  
  
Note:- This fixture is supplied with one dust cap. Unused 
cable entries must be closed off with blanking   
plugs or stoppers to maintain the IP rating. (3 supplied).  
  
The cable entries should be securely tightened to ensure 
that the minimum protection rating is achieved. The cable 
entry should be rated to minimum of IP66 / IP67 to maintain 
the protection level of the fixture.  
  
Do not over tighten as the protection rating may be 
compromised. Always refer to gland manufacturers data 
for torque settings.  
  
Electrical Connections  
The terminal block is suitable for multi-stranded and single 

core cables up to a maximum of 4mm

²

, strip length 10mm  

  
The LIVE 1, LIVE 2, NEUTRAL and EARTH connections are 
clearly marked on the terminal block or label. 
 
When terminating the conductors, the insulation of the 
conductors shall reach up to the terminal block. The 
conductor itself shall not be damaged. The connectable 
minimum and maximum conductor cross sections shall be 
observed (see technical data box). 
 
The L1 connection is a permanent live feed. It powers the 
main normal mode operation, battery charger and is used 
to activate emergency mode. The L2 connection is a 
switched live feed to control the luminaire normal mode on 
or off. It is a signal input that consumes negligible current.  
 
Single Luminaire Electrical Connections:-  
Push down at the ‘cross point’ on the terminal block, insert 
correct cable and release, ensuring the cable has been 
securely retained.  
  
Loop Through Electrical Connections:-  
  
Connect incoming cable as above then connect the 
outgoing cable to the associated adjoining connection to 
pass to the next luminaire. 
 
3 phase connection 
Connect the designated load phase (e.g. L1) to L on the 
terminal block and the other 2 phases for loop thru L2 / L3 
respectively to the terminal block as shown in the diagram 
 
 
ONLY SINGLE CABLES TO BE USED ON EACH TERMINAL ENTRY 
POINT.                                                                                        
The improper installation, operation, or maintenance of 
these luminaries may result in the invalidation of the 
warranty.                                                                                     
Use the dimensions in Section 1 provided to locate the 
luminaire into the desired position.                                       
Maximum screw / bolt size M8 x 16 (screws are supplied with 
the mounting hardware and are supplied separately).  
  
Battery                                                                                            
A 3.6V 10Ah (part ref ELX-BATT-KIT) is provided with both the 
35W and 70W versions. The 10Ah battery is mounted on a 
completely removable tray which only requires removing 
when battery pack replacement is required. To remove the 
battery tray, DISCONNECT the 2-pole battery connector 
and loosen the battery tray retaining screw. The screw is 
retained to the tray, un-hook the tray to remove the battery 
pack. 
 

 

 

Safety Instruction: 
The installation, operation and 

maintenance must be carried out  
by a suitably trained electrician.  
 
• The technical data indicated on the    

     LED luminaires are to be observed.    
     
• Changes of the design and 
   modifications to the LED luminaire 

   are not permitted 
 
• Observe the national electrical 

safety rules and regulations during 

installation. 

 
• No user serviceable parts inside. 
 

• Only the battery pack is field                                                   

replaceable 