DuroSite
®
Emergency Stainless Steel LED Linear Luminaire r industrial areas
Conformity with Standards
This equipment conforms to the standards specified in
the Declaration of Conformity.
It has been designed, manufactured and tested in
accordance with BS EN 9001.
2004/108/EC:EC Directive for electromagnetic
compatibility.
Equipment Application
This lighting equipment is intended for use in an
industrial area.
The product can be used inside or outside to
illuminate industrial areas
Mounting the Luminaire
Assemble the mounting bracket to the luminaire with 2 off
M8 x 1.25 by 16mm bolts. Torque specification: 2.0 Nm
maximum.
Installation
Ensure that the mains voltage supply is disconnected
before connecting the luminaire. Install the
equipment in accordance with the manufacturer’s
instructions as well as any other applicable electrical
codes.
Always transport and store the equipment in its original
packaging and keep in a dry location.
When unpacking check for any cracks or damage in the
housing, end covers and lens. If in doubt, do not install!
All EL and ELE luminaires come complete with through wire
capabilities and as such, the mains can enter the luminaire
from either end. All EL and ELE luminaires come with two
entry points at each end to allow for mains in, switched live
in and through wires out on separate cables if required.
Opening the terminal tray
To open the tray, completely remove the two 4mm HEX
socket screws at either the emergency module end or the
luminaire end. Once these are removed, the tray can be
slid out exposing the terminal block. The terminal blocks are
mounted to the front sides of the trays (where the front side
is the light output side) This gives easy access to the
terminals when the luminaire is mounted in position.
The terminal tray is captive and will not fall out when slid
open to its max position.
The terminal tray slides back into position once the wires are
connected to the terminal block (See Electrical
connections on Page 3). The gear tray should be slid back
with care ensuring no cables or wires are overstressed or
trapped. When replacing the end covers, ensure the seals
are clean and undamaged. If the covers are not fully in
place the screws may be difficult to engage and can be
cross-threaded. Do not allow any cables to be trapped by
the end covers or terminal tray. Ensure that all wires are
clear from the screw entry points.
The cable glands used with this fixture must be rated
IP66/67 or better to maintain the protection level of the
luminaire. A locknut is required for each cable gland to
ensure they are securely fastened to the end covers.
Cable gland with O-ring min. thread length C = 10mm.
P
= M20 x 1,5mm
P
= M25 x 1,5mm (add 4
suffix to part code)
The cable used must be suitable for the site application
and/or the site requirements.
When assembling the cable entries for the mains
connection, always observe the manufacturers
specifications for the glands used.
Note:- This fixture is supplied with one dust cap. Unused
cable entries must be closed off with blanking
plugs or stoppers to maintain the IP rating. (3 supplied).
The cable entries should be securely tightened to ensure
that the minimum protection rating is achieved. The cable
entry should be rated to minimum of IP66 / IP67 to maintain
the protection level of the fixture.
Do not over tighten as the protection rating may be
compromised. Always refer to gland manufacturers data
for torque settings.
Electrical Connections
The terminal block is suitable for multi-stranded and single
core cables up to a maximum of 4mm
²
, strip length 10mm
The LIVE 1, LIVE 2, NEUTRAL and EARTH connections are
clearly marked on the terminal block or label.
When terminating the conductors, the insulation of the
conductors shall reach up to the terminal block. The
conductor itself shall not be damaged. The connectable
minimum and maximum conductor cross sections shall be
observed (see technical data box).
The L1 connection is a permanent live feed. It powers the
main normal mode operation, battery charger and is used
to activate emergency mode. The L2 connection is a
switched live feed to control the luminaire normal mode on
or off. It is a signal input that consumes negligible current.
Single Luminaire Electrical Connections:-
Push down at the ‘cross point’ on the terminal block, insert
correct cable and release, ensuring the cable has been
securely retained.
Loop Through Electrical Connections:-
Connect incoming cable as above then connect the
outgoing cable to the associated adjoining connection to
pass to the next luminaire.
3 phase connection
Connect the designated load phase (e.g. L1) to L on the
terminal block and the other 2 phases for loop thru L2 / L3
respectively to the terminal block as shown in the diagram
ONLY SINGLE CABLES TO BE USED ON EACH TERMINAL ENTRY
POINT.
The improper installation, operation, or maintenance of
these luminaries may result in the invalidation of the
warranty.
Use the dimensions in Section 1 provided to locate the
luminaire into the desired position.
Maximum screw / bolt size M8 x 16 (screws are supplied with
the mounting hardware and are supplied separately).
Battery
A 3.6V 10Ah (part ref ELX-BATT-KIT) is provided with both the
35W and 70W versions. The 10Ah battery is mounted on a
completely removable tray which only requires removing
when battery pack replacement is required. To remove the
battery tray, DISCONNECT the 2-pole battery connector
and loosen the battery tray retaining screw. The screw is
retained to the tray, un-hook the tray to remove the battery
pack.
Safety Instruction:
The installation, operation and
maintenance must be carried out
by a suitably trained electrician.
• The technical data indicated on the
LED luminaires are to be observed.
• Changes of the design and
modifications to the LED luminaire
are not permitted
• Observe the national electrical
safety rules and regulations during
installation.
• No user serviceable parts inside.
• Only the battery pack is field
replaceable