9
If connecting to an existing masonry chimney
it is recommended that a flue forming pipe
(short length of flue pipe) is used and the void
between the flue forming pipe and the
chimney is filled with vermiculite concrete.
A suitable access hole will need to be made in
the chimney breast to allow the back filling to
be carried out and then filled and sealed once
the installation is complete.
Alternatively a connection can be made using
a register plate although it will be necessary
to allow access for fitting the flue pipe to the
register plate and sealing all joints.
I
NSTALLING THE FIREBOX
For information on installing the firebox and
completing the installation go to page 12
I
NSTALLATION INTO A NON
-
COMBUSTIBLE
ENCLOSURE
The Di Lusso R6 has been designed, tested
and approved to be installed either into solid
non-combustible material or into an
enclosure according to the following
specification. It is the duty of the installer to
ensure that the requirements of this
specification and all relevant standards are
met.
•
There must be no combustible
material within the construction of
the enclosure.
•
The stove should be supported on
the Di Lusso Enclosure Stand (Part
Number HMR05ARRT013).
•
The enclosure must be produced
from 30mm Skamol Super Isol board
held together with a non-
combustible framework and finished
in heat resistant plaster.
•
Particular attention must be paid to
the size and position of ventilation
openings. These openings must be
kept clear at all times.