background image

A1000 &  A2000 USERS MANUAL  6

BAUD RATE
The A1000 and A2000 series converters each contain a 10-position DIP
switch located on the rear panel. The DIP switch is used to select the
correct communications baud rate and  must be set to the same value as
the devices connected to the RS-485 OUT connector. Only one baud
rate switch may be turned on at one time.

L E D S
The A1000 contains three status LEDs labelled FAULT, POWER  and
TRANSMIT located on the converter front panel. The A2000 contains
two status LEDs labelled PWR and  TX  located  on  the  converter  rear
panel. The status indicators are useful while troubleshooting suspected
system faults and provide visual status indication during normal system
operation.

The  A2000  converter  LEDs  may  be  disabled  internally.  Low  power
applications, typically powered by batteries or solar panels, can benefit
significantly  by  disabling  the  status  LEDs.  The  A2000  power
consumption may be reduced by up to 50% with the LEDs disabled. To
disable the status LEDs, remove the A2000 top cover and locate the 3-
pin strip on the PC board directly behind the LEDs. Lift the jumper bar
from the pin strip and place it over the two pins located closest to 'LEDS
OFF' written on the PC board.

The  POWER  (A1000)  and  PWR  (A2000)  LEDs  are  pilot  lights  that
indicate adequate power supply voltage is applied to the converter.

The  TRANSMIT  (A1000)  and  TX  (A2000)  LEDs  illuminate  as  data  is
transmitted from a host computer onto the RS-485 communications bus.
The illumination intensity will vary and may become hard to detect as the
baud rate increases.

The A1000 FAULT LED will illuminate if excessive current is being drawn
from the in24Vdc one amp power supply.

RS-485 TERMINATIONS
The proper termination techniques for any RS-485 system require two
biasing resistors and two termination resistors. There must be one pull-up
resistor between the DATA+ line and +5Vdc on each RS-485 network.
There should also be a pull-down resistor from the DATA- line to ground.
These two resistors are the biasing resistors and are normally positioned
at the HOST end of the cable. The RS-485 standard also requires two
resistors across the data lines for proper termination. Two 220 

 resistors

should be placed across the data lines DATA+ and DATA-. The resistors

Summary of Contents for A1000 series

Page 1: ...information in this publication has been carefully checked and is believed to be accurate however no responsibility is assumed for possible inaccuracies or omissions Applications information in this m...

Page 2: ...nal handshaking signals from the host Therefore host software written for RS 232 may be used without modification RS 485 bus control is completely transparent to the user The A1000 and A2000 can also...

Page 3: ...ns 8 08 W x 2 50 H x 6 25 D A1000 7 06 W x 1 53 H x 5 30 D A2000 RS 485 Connectors Phoenix screw terminal barrier plug supplied Replace with Phoenix MSTB 2 5 4 ST 5 08 or equivalent Warranty 12 months...

Page 4: ...OUND 6 DSR DATA SET READY 7 NC NO CONNECTION 8 CTS CLEAR TO SEND 9 NC NO CONNECTION The RS 232 connector is left open when the A1000 or A2000 is used as an RS 485 Repeater The only connections normall...

Page 5: ...485 converter A1000 2000 RS 485 OUT CONNECTOR The A1000 and A2000 converters contain a four pin screw terminal plug labelled RS 485 OUT This connector is the RS 485 output for the A1000 and A2000 whe...

Page 6: ...e the 3 pin strip on the PC board directly behind the LEDs Lift the jumper bar from the pin strip and place it over the two pins located closest to LEDS OFF written on the PC board The POWER A1000 and...

Page 7: ...n of a RS 485 system The resistors are enabled or disabled via two 3 position DIP switches located on the A1000 rear panel One three position switch enables termination resistors for the RS 485 IN HOS...

Page 8: ...a resistor insert a jumper into the jack position adjacent to the resistor nomenclature written on the A2000 printed circuit board NOTE The RS 485 IN 1K and 1K jumpers should be installed when the A20...

Page 9: ...wiring diagrams for both the A1000 and A2000 used as RS 232 RS 85 converters and RS 485 repeaters Figure 4a Wiring diagram for RS 232 RS 485 converter with host DB 9 connector Figure 4a Wiring diagra...

Page 10: ...A1000 A2000 USERS MANUAL 10 Figure 4c Wiring diagram for RS 232 RS 485 converter and RS 485 repeater...

Reviews: