Adjustment 

See Figure 1 for part identification. 

 

The setting on the Double Acting Throttling Device must be tolerable to the collapsing 

pressure on the system. 

Confirm that the DAT is firmly screwed to the valve outlet (top).  
To adjust the DAT, close the Teflon plug (5) by turning the adjustable stem (3) 

clockwise

 to be fully 

extended. Note that the device is designed so as it cannot completely close. Open the Teflon plug by 

turning the adjustment stem 

counter clockwise

, three (3) full turns. 

Start pump. Listen and observe the Air/Vacuum Valve closing when water column reaches the valve. If 

the valve gently closes and no surge is apparent, lock the position setting in by turning the lock nut (6) 

against the cover (2).   
If there is a "thunk" when valve is closing, turn the adjustable stem (3) one full turn 

clockwise

 to farther 

close the devise and restrict the amount of air evacuating. Depending on the application, more than one 

turn towards the closed position may be necessary. This will establish a back pressure on the rising 

column of liquid to reduce shock, pressure surge and water hammer to the system.  

    

 

 

NO  DESCRIPTION 

1  Housing 

2  Cover 

3  Adjustable Stem 

4  Spring 

5  Plug 

6  Lock Nut 

7  Nipple 

Figure 1:  DAT Double Acting Throttling Device 

 