Description  

The APCO Air/Vacuum Valve mounted on top of a Surge Check Valve is designed to eliminate critical 
shock conditions occurring in those installations where the operating conditions cause a regular air valve 
to slam closed.  This slow closing feature protects the Air/Vacuum valve and also prevents the 
Air/Vacuum valve from creating a surge in the pipeline by slamming shut.  

This type Air/Vacuum Valve with Surge Check Valve should not be considered as relief for shock 
conditions which develop elsewhere in the system.  However, actual field tests prove the Surge Check 
Valve may protect the Air/Vacuum Valve from damage by severe shut-off shock. 

Handling and Storage  

Lifting the valve improperly may damage it. Do not fasten lifting devices to piping or attached 
components. Lift the valve with

 

slings, chains or cables fastened around the valve body, or fastened to 

bolts or

 

rods through bolt holes in the flanges. 

If installation will be delayed, place valve indoors in secure, weather tight storage. If temporary outside 
storage is unavoidable, make sure a vermin proof rain cover (water shedding tarp, etc.) is secured 
around/over the valve to keep off rain and mud.  Skid and set the assembly on a flat, solid, and well 
drained surface for protection from ground moisture, runoff and pooled rain water. 

Installation 

The Air/Vacuum Valve with Surge Check Valve should always be installed in a vertical position.  An 
isolation valve between this unit and the transmission (pipeline) system is recommended.  Where to use: 

  High points in pipelines where the hydraulic gradient and flow conditions are such that a negative 

pressure can possibly occur. 

  High points on sections of pipeline having water velocities in excess of 10 F.P.S.  

  Adjacent to any quick closing valve in a pipeline such as a check or gate valve where vacuum 

can occur upon closure. 

  On the discharge of larger deep well turbine pumps between the pump and the check valve. 

  If an Air/Vacuum Valve is to be installed inside a pump house, use threaded or flanged 

connections and pipe back into the well or to outside.  This will greatly muffle the high noise level 
caused by the air being discharged and provide for drainage of any small amount of water or 
water vapor that may accumulate.   

  Before installation, remove foreign material such as weld spatter, oil, grease, and dirt from the 

pipeline. 

  Prepare pipe ends and install valves in accordance with the pipe manufacture’s instructions for 

the joint used. 

  Tighten the flange bolts or studs in a crisscross pattern and minimum of four stages. 

 

Summary of Contents for APCO AVV-140

Page 1: ...DeZURIK Inc Sartell Minnesota USA Phone 320 259 2000 www dezurik com info dezurik com APCO AVV 140 150 AIR VACUUM VALVE WITH OPTIONAL CSV SURGE CHECK VALVE Instruction D12021 June 2019 ...

Page 2: ...ion during shipment however items can be damaged in transport Carefully inspect the unit for damage upon arrival and file a claim with the carrier if damage is apparent Parts Replaceable wear parts are listed on the assembly drawing These parts can be stocked to minimize downtime Order parts from your local DeZURIK sales representative or directly from DeZURIK When ordering parts please provide th...

Page 3: ...tion 4 Handling and Storage 4 Installation 4 Fusion Powder Coated Valves 5 Maintenance 5 Disassembly Procedure 5 Air Vacuum Valve 1 20 25 500mm Only 5 Surge Check Valve 3 24 80 600mm Only 6 Assembly Procedure 6 Surge Check Valve 3 24 80 600mm Only 6 Air Vacuum Valve 1 20 25 500mm Only 6 Operation 7 Drawings 8 Troubleshooting 12 ...

Page 4: ...red around over the valve to keep off rain and mud Skid and set the assembly on a flat solid and well drained surface for protection from ground moisture runoff and pooled rain water Installation The Air Vacuum Valve with Surge Check Valve should always be installed in a vertical position An isolation valve between this unit and the transmission pipeline system is recommended Where to use High poi...

Page 5: ...valve Disassembly Procedure Air Vacuum Valve 1 20 25 500mm Only See Figures 1 2 for part identification For information regarding 24 600mm Air Vacuum Valves contact your local DeZURIK sales representative Servicing the Air Vacuum Valve while the pipeline is under pressure can cause personal injury or equipment damage Relieve pipeline pressure or shut off isolation valve before servicing the Air Va...

Page 6: ...available for the 1 2 25 50mm Surge Check Valves It is recommended to replace the complete valve 1 Install the parts inside the body S1 in the following order a Bushing S5 at the center of the hub b Spring S4 centering on the bushing S5 Note If conical spring smaller diameter of spring should fit the outside diameter of bushing c Plug S3 with the concave side facing upward d Seat S2 Tighten seat r...

Page 7: ...loaded so that air passes through unrestricted When water rushes into the Surge Check Valve the disc begins to close against the spring tension and reduces the rate of flow of water into the air valve by means of throttling holes in the disc This ensures normal gentle closing of the Air Vacuum Valve regardless of the initial velocity flows involved and minimizes pressure surges when the valve clos...

Page 8: ...DeZURIK APCO AVV 140 150 with CSV 1600 Option Slow Closing Air Vacuum Valves D12021 Page 8 June 2019 Drawings Figure 1 AVV 140 1 3 25 80mm Air Vacuum Valve ...

Page 9: ...DeZURIK APCO AVV 140 150 Air Vacuum Valve with Optional CSV Surge Check Valve June 2019 Page 9 D12021 Drawings Continued Figure 2 AVV 150 4 20 100 500mm Air Vacuum Valve ...

Page 10: ...DeZURIK APCO AVV 140 150 with CSV 1600 Option Slow Closing Air Vacuum Valves D12021 Page 10 June 2019 Drawings Continued Figure 3 CSV 3 24 80 600mm Surge Check Valve ...

Page 11: ...DeZURIK APCO AVV 140 150 Air Vacuum Valve with Optional CSV Surge Check Valve June 2019 Page 11 D12021 Drawings Continued Figure 4 Connecting Parts ...

Page 12: ...ange gasket Misalignment or damage to field piping and supports Adjust misalignment or repair piping or supports Damaged flange face s or improper flange connections Repair flange replace valve body or adjust flange connections Valve leaks out of outlet port Dirty seat and or float Clean seat and or float Worn seat and or float Replace seat and or float Line pressure is under 10 psi 70KPa Replace ...

Page 13: ...ll be the only effective guarantee or warranty binding on Seller despite anything to the contrary contained in the purchase order or represented by any agent or employee of Seller in writing or otherwise notwithstanding including but not limited to implied warranties THE FOREGOING REPAIR AND REPLACEMENT LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OBLIGATIONS AND LIABILITIES INCLUDING ALL W...

Reviews: