background image

R

User Manual

SUN-80K-G03

SUN-110K-G03

SUN-75K-G03

Grid-connected PV Inverter

SUN-70K-G03
SUN-90K-G03

Summary of Contents for SUN-100K-G03

Page 1: ...R User Manual SUN 80K G03 SUN 110K G03 SUN 75K G03 Grid connected PV Inverter SUN 70K G03 SUN 90K G03 ...

Page 2: ...n 6 Start up and shut off 6 1 Start up the inverter 6 2 Shut off the inverter 7 Zero export function via energy meter 7 1 Multiple strings and parallel connection meters 8 1 The initial interface 8 2 Statistics information 8 3 Fault Record 8 4 ON OFF setting 8 5 Parameter setting 8 General Operation 9 Repair and Maintenance 10 1 Error code 10 Error information and processing 11 Specifications 5 3 ...

Page 3: ...arefully and be available at all mes Contents may be periodically updated or revised due to product development The informa on in this manual is subject to change without no ce The latest manual can be acquired via service deye com cn On grid inverter can convert solar panel DC power into AC power which can directly input to the grid Its appearance is shown below These models contain SUN 70K G03 S...

Page 4: ... ng stainless steel screws M4 12 x 5 Grid ed PV String Inverter x 1 Wrench x 1 User manual User manual x1 Datalogger op onal x1 Meter op onal x 1 Three Phase Smart Meter SET ESC Sensor Clamp op onal x 3 Stainless steel an collision bolt M12 80 x 4 UP Enter Down Esc DC AC Nomal Alarm DC DC Plug connectors including metal terminal x N pairs ...

Page 5: ...e Hazard Cau on hot surface symbol indicates safety instruc ons which if not correctly followed could result in burns Safety Hint Note symbol indicates important safety instruc ons which if not correctly followed could result in some damage or the destruc on of the inverter Warning Warning symbol indicates important safety instruc ons which if not correctly followed could result in serious injury ...

Page 6: ...3 Local temperature of the inverter may exceed 80 while under opera ng Do not touch to avoid ge ng injured 4 All electrical installa on must be in accordance with local electrical standards and achieved permission of local power company 5 Please take appropriate an sta c measure 6 Please install where children can not touch Shock Hazard When PV module is exposed to sunlight the output will generat...

Page 7: ...ica ng normal ac connec on Beside the AC indicator is the opera ng indicator green indica ng normal output The right indicator is alarm red indicates alarming Explanation Inverter detects DC input Low DC input voltage Grid Connected Grid Unavailable Under normal opera ng Stop opera ng Detected faults or report faults Under normal opera ng Indicator status DC AC NORMAL ALARM on off on off on off on off...

Page 8: ...ght is Enter bu on ENTER Achieving below func ons by the four bu ons Three phase string inverter use 256 128 dot forma on display Display below content Page turning use UP and DOWN bu on Modify adjustable parameters use ESC and ENTER bu on 3 4 LCD Display Inverter opera on status and informa on Opera ng informa on Warning message and malfunc on display ...

Page 9: ...freely To avoid overhea ng always make sure the flow of air around the inverter is not blocked Exposure to direct sunlight will increase the opera onal temperature of the inverter and may cause output power limi ng It is recommended that inverter installed to avoid direct sunlight or raining To avoid overhea ng ambient air temperature must be considered when choosing the inverter installa on loca o...

Page 10: ...ne inverter must leave at least 500mm gap between each inverter And each inverter must be at least 500mm above and below And must install the inverter at the place where children cannot touch Please see picture 4 3 Consider whether the installa on environment is helpful to see the inverter LCD display and indicator status clearly Must offer a ven late environment if inverter installed in the air gh...

Page 11: ... 09 4 2 Inverter of inverter 500mm 500mm Pic 4 3 Installa on Gap Pic 4 4 Mou ng bracket dimensions ...

Page 12: ...i on of the holes should be suitable for the expansion bolts 2 Make sure the bracket is horizontal and the moun ng holes are in the correct points Drilling the holes on the wall according the marks 3 Using the expansion bolts to fix the bracket to the wall Pic 4 5 Inverter Installa on Anchoring Mounting bracket Stainless steel screws Inverter ...

Page 13: ...d to the system ground bar Safety Hint Before connec ng inverter please make sure the PV array open circuit voltage is within the 1000V of the inverter Safety Hint Before connec on please make sure the polarity of the output voltage of PV array matches the DC and DC symbols Safety Hint Please use approved DC cable for PV system Cable type Range Recommended value Cross section mm Industry generic P...

Page 14: ... 3 b Crimping metal terminals with crimping pliers as shown in picture 5 4 c Insert the contact pin to the top part of the connector and screw up the cap nut to the top part of the connector as shown in picture 5 5 Pic 5 3 Disassemble the connector cap nut 7mm 7mm Pic 5 5 connector with cap nut screwed on Pic 5 4 Crimp the contact pin to the wire ...

Page 15: ...he high voltage of the inverter may lead to life threatening condi ons Pic 5 6 DC input connec on 5 2 AC terminal connec on Warning The AC cable line L1 is connected to socket 1 L2 is connected to socket 2 L3 is connected to socket 3 the PE line is connected to the earth the N wire is connected to the socket of N Table 5 2 Recommened cable specifica ons Conductor cross sectional area mm Recommended...

Page 16: ...Pic 5 8 2 Connect the cable through the junc on box waterproof jacket and insert into the terminal The picture shows the connec on mode of three phase lines connected to the junc on box ground wire screwed on the inverter shell Pic5 9 and use hexagon screwdriver to presses the wiring harness to the connect terminal as shown in Pic5 10 Pic 5 7 AC junc on box Pic 5 8 AC terminal Pic 5 9 AC cable con...

Page 17: ...3 Recommended current protector specifica ons Pic 5 11 Tighten the AC junc on box Table 5 3 Recommended current protector specifica ons Inverter SUN 70K G03 SUN 75K G03 SUN 80K G03 SUN 90K G03 Rated voltage 400 400 400 400 Rated output power KW 70 75 80 90 Current protection device A 150 160 170 200 SUN 100K G03 SUN 110K G03 400 400 100 110 200 250 ...

Page 18: ... ground line Inverter has the func on of wireless remote monitoring inverter The inverter has Wifi func on and Wifi Plug in the accessories is used to realize the connec on between the inverter and the network The opera on installa on networking APP download are detailed in the WIFI PLUG instruc ons Figure 5 13 is the Internet monitoring solu on 5 4 Inverter monitoring connec on Warning Inverter has...

Page 19: ...ws Insert the datalogger into the interface and fix it with a screw The configura on of the datalogger needs to be performed a er various electrical connec ons have been completed and the inverter DC power on When the inverter is on the DC power it is determined whether the datalogger is normally electrified The LED light shines out of the shell 5 4 1 Installa on of datalogger Router WIFI GPRS Web Se...

Page 20: ...inverter should fellow below steps 1 First switch on the AC breaker 2 Turn on the DC switch of the PV module and if the panel provides sufficient star ng voltage and power the inverter will start 3 When the AC voltage and DC voltage are normal the inverter start up is ready to begin The inverter will first check the internal parameters and the grid parameters while the liquid crystal will show that t...

Page 21: ...we believe that you have completed the connec on according to the requirements of chapter 5 if you have been running your inverter at this me and you want to use the zero export func on please turn off AC and DC switch of the inverter and wait for 5 minutes un l the inverter completely discharged For system wiring diagram the red line refers to L line L1 L2 L3 the black line refers to the neutral l...

Page 22: ...stron meter Solar Panel array Inverter meter AC Breaker Grid RS485 Communication Family load L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N N L3 L2 L1 VCC_5V 485_B 485_B 485_A 485_A GND GND RS 485 Male connector RS 485 Female connector 1 2 3 4 5 6 7 8 Note In final installa on breaker cer fied according to IEC 60947 1 and IEC 60947 2 shall be installed with the equipment ...

Page 23: ...Eastron Pic 7 4 Connec on diagram of Eastron meter Solar Panel array Inverter meter AC Breaker Grid RS485 Communication Family load N L3 L2 L1 LA NA S2 S1 S2 S1 S2 S1 GND B A CT2 CT1 CT3 White line black line White line black line White line black line L1 L2 L3 N N L3 L2 L1 VCC_5V 485_B 485_A 485_A 485_B GND GND RS 485 Male connector RS 485 Female connector 1 2 3 4 1 2 3 4 5 6 7 8 9 1 0 11 1 2 1 3...

Page 24: ...Phase Smart Meter SET ESC 1 7 4 10 25 24 3 9 6 10 RS 485 CHNT DTSU666 3 6 9 10 1 4 7 10 Pic 7 6 Connec on diagram of CHNT meter Solar Panel array Inverter meter AC Breaker Grid RS485 Communication Family load 1 7 4 10 25 24 3 9 6 10 Three Phase Smart Meter SET ESC L1 L2 L3 N L1 L2 L3 N N L3 L2 L1 VCC_5V 485_B 485_B 485_A 485_A GND RS 485 Male connector RS 485 Female connector 1 2 3 4 ...

Page 25: ...eter by choosing up down bu on please press enter bu on to confirm when se ng done 3 Move the cursor to OK press enter to save the se ngs and exit the running parameters page otherwise the se ngs are invalid 4 If set up successfully you can return to the menu interface and display the LCD to home page by press the up down bu on If it displays meter power XXW the zero export func on se ng is complet...

Page 26: ... as slaves And all of them need to connect to the meter via RS485 Below is the system diagram and configura on of the system This applica on is that when the string inverters work in parallel there is only one power grid and one load and only one meter can be connected to prevent reverse current so only this many to one an reverse current connec on can be connected MENU Setting Back Exp_Mode AVG CT...

Page 27: ... it should be set as 01 Parallel mode Set one inverter as Master others are Slave ONLY need to set the master Slave will follow the se ngs in the master Number of inverters in parallel DG side meter func on Enable Disable CT ra o of power DG side meter when extern CT is applied Manufacturer of the DG side meter Modbus Address of it should be set as 02 Output power percentage of the DG Capacity of ...

Page 28: ...y Solar Panel array L1 L2 L3 N load Grid meter 5 6 7 8 N L3 L2 L1 Master Mst Slave1 Slv1 Slave2 Slv2 Grid L1 L2 L3 N 1 2 3 4 Master Mst RS485 1 2 3 4 Slave1 Slv1 RS485 1 2 3 4 Slave2 Slv2 RS485 485_B 485_A AC Breaker AC Breaker AC Breaker GND 485_B as short as possible 485_A as short as possible GND as short as possible 485_B as short as possible 485_A as short as possible GND as short as possible...

Page 29: ... Breaker AC Breaker N L3 L2 L1 LA NA S2 S1 S2 S1 S2 S1 GND B A 1 2 3 4 5 6 7 8 9 1 0 11 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 P M E U I ESC Eastron CT1 Note the arrow direction towards the inverter CT2 CT3 Grid meter White line black line White line black line White line black line 1 2 3 4 Master Mst RS485 1 2 3 4 Slave1 Slv1 RS485 1 2 3 4 Slave2 Slv2 RS485 485_B 485_A GND 485_B as short as possible...

Page 30: ...array Solar Panel array L1 L2 L3 N load Master Mst Slave1 Slv1 Slave2 Slv2 AC Breaker AC Breaker AC Breaker Grid L1 L2 L3 N 1 7 4 10 25 24 3 9 6 10 Three Phase Smart Meter SET ESC 1 2 3 4 Master Mst RS485 1 2 3 4 Slave1 Slv1 RS485 1 2 3 4 Slave2 Slv2 RS485 485_B 485_A GND 485_B as short as possible 485_A as short as possible 485_B as short as possible 485_A as short as possible AC Breaker VCC_5V 4...

Page 31: ...rding to above diagram A er the connec on completed successfully the inverter will show the load power on the LCD But please don t setup Meter ON Also you will be able to browse the load power on the monitoring pla orm The plant se ng method as below descrip on Firstly go to the solarman pla orm h ps pro solarmanpv com this link is for solarman distributor account or h ps home solarmanpv com this ...

Page 32: ... 30 Secondly go to plant page if it shows the PV power load power and grid power which means the configura on is correct ...

Page 33: ...ator temperature so ware version number and Wifi connec on state of the inverter 8 General Opera on Protect param Comm param System param Run param ON OFF Setup Sta s cs Fault record AC output data Interface LCD main menu DC input data E Day E Month E Year E History E History Turn ON Turn OFF Time Set Language Set Display Set Factory data reset English polski 简体中文 Confirm to reset Cancel Se ng Resto...

Page 34: ... UF Uprate WGRa WGraStr Sunspec OK Cancel AUTO CHNT EASTRON ACREL AVG MIN OFF SLV MST CT_Ra o 0 MFR Exp_Mode ShuntQTY Generator G CT G MFR G FeedIn G Cap FeedIn Shunt QP OFF PFP QU PF PER P1 P6 Q1 Q6 Back start stop PmpTime PtUsed Curve Cut In Cut Out P1 P6 PF1 PF6 Time PowerLim LVRT Vstart Vstop HVRT HardLim P_H So Lim P_S AUTO CHNT EASTRON ACREL Setup Running param ...

Page 35: ...04 MEA PEA 240 0V 1000ms 235 0V 1000ms 52 00HZ 1000ms 48 00HZ 1000ms OV_3 OV_1 Tov_3 Tov_1 Tuv_1 Tuv_3 UV_1 UV_3 OF_3 OF_1 Tof_3 Tof_1 UF_1 UF_3 Tuf_1 Tuf_3 Vrc_H Vrc_L OV10Min Frc_H Frc_L VGrid 127 220V Uov Address 08 Meter Unkonw BaudRate 9600 GridStanderd Advanced Back Setup Protect Param Comm param ...

Page 36: ... Down you can check inverter DC voltage DC current AC voltage AC current inverter temperature so ware version informa on You can check the PV informa on the number of strings input MPPT voltage and MPPT current Power Day Total State Standby 0 29 86Kw P 45 Kw 295kWh 25 MWh 6 12 18 24 ID 2110214096 PF 0 000 Flash 0 0Kw SN 01 2022 01 18 08 00 00 PV1 V 349 9V I 10 3A P 3 6KW PV2 V 313 0V I 8 3A P 2 6K...

Page 37: ...n the bo om right corner The first flash means inverter is communica ng with LCD The second flash means LCD is communica ng with wifi plug Ua 234 5V Ia 0 0A Grid Freq 50 00Hz RUN Grid Pic 8 4 Inverter firmware version Pic 8 5 Meter power and load power Meter Power 0W Load Power 0W Day Total ImpEp 0 00kWh 0 00kWh ExpEp 0 00kWh 0 00kWh LoadEp 0 00kWh 0 00kWh PARAMETR Meter SN 0 Total DC Power 3 602W Lcd0...

Page 38: ... 8 1 1 Main Menu 8 2 Sta s cs informa on Pic 8 6 Main Menu Pic 8 7 Sta s cs There are five submenu in the sta s cs Into each submenu through cursor E Day E History E Month E Year Test Data MENU Statistics Statistics Fault Record ON OFF Setup MENU ...

Page 39: ... E Month Pic 8 10 E Year 2022 01 1 10 20 31 MENU Statistics E Month 01 10MWh 02 03 04 05 06 07 08 09 10 2022 MENU Statistics E Year 01 200KWh 02 03 04 05 06 07 08 09 10 11 12 2022 01 18 MENU Statistics E Day 0 10MWh 6 12 18 24 ...

Page 40: ...ep four fault record in the menu include me customer can deal with it depends on the error code Pic 8 11 E History Pic 8 12 Test Data PV1 PV2 HV GFD DiL AVL 126 1k2 146 147 19186 19198 24362 9119 36 2 287 6 0 148 0 149 0 0 1k3 1k4 1k5 1k6 vHV BSn ofA ofB 11126 11140 16666 2927 ofC 138 139 140 2057 2248 137 2145 1497 0 141 0 142 0 143 0 144 0 24362 12218 2065 2653 145 0 2015 2024 MENU Statistics E ...

Page 41: ... ON OFF se ng Pic 8 14 ON OFF se ng MENU ON OFF Turn ON Turn OFF Into each submenu through cursor Pic 8 15 ON set MENU ON OFF Turn ON Turn ON OK Cancel Pic 8 16 OFF set MENU ON OFF Turn OFF Turn OFF OK Cancel ...

Page 42: ...mm Pic 8 17 1 System Param Se ng MENU Setup Time Set Language Set Display Set Factory data reset Setting Restore System Param 8 5 Parameter se ng 8 5 1 System Param Se ng includes system param run param protect param comm param All of these informa on for maintenance reference ...

Page 43: ... Set 2022 01 18 09 36 30 OK Cancel Pic 8 18 System Param 8 5 1 2 Language Set Pic 8 19 Lauguage set 8 5 1 3 Display Set Pic 8 20 Display set Display Set Brightness Keep Delay time 05S OK Cancel Lauguage Set 简体中文 English Polski ...

Page 44: ...actory data reset Confirm to reset Cancel 8 5 1 5 Se ng Restor Pic 8 22 Factory data reset set Setting Restor Confirm to restore Cancel Note Password required only for access authorized engineer Un authorized access may avoid the warranty The ini al password is 1234 ...

Page 45: ... 23 Password PassWord MENU Setup Run Param OK Cancel ActiveP 31 ReactP 0 0 QMode OFF PF 1 000 Fun_ISO OFF Fun_RCD OFF Island OFF Meter ON Limiter OFF Feed_In 0 MPPT Num 6 SelfCheck 20S 43 8 5 2 Running Param ...

Page 46: ...ec on Energy meter If inverter will connect meter then set here to ON It is used to deploy how much power can be feed in to grid when the inverter works under zero export mode For example Feed_in 50 of the 110KW modeland loadpower is 54KW which means Max 55KW power can befeed into grid a er inverter providing 54Kw to the load firstly RANGE 100 100 ReactP Adjust reac ve power output in Note Engineer...

Page 47: ...WGraStr OFDerate UFUprate PU Ac ve power response to over frequency Ac ve power response to under frequency power response to grid voltage devia on Ac ve power ramp rate Pnom Sec Ac ve power ramp rate at first start Pnom Sec 80 260V Vref Grid reference voltage for func ons including Q U PF P P U etc ON OFF PowerLimit Hard so export limit control ON OFF DRM Demand Response Modes ON OFF Sunspec Sunsp...

Page 48: ...eaches StopPoint 51 5Hz Frq Watt Mode for Over frequency Conditions 50 0 50 1 50 2 50 3 50 4 50 5 50 6 50 7 50 8 50 9 51 0 51 1 51 2 51 3 51 4 51 5 51 6 51 7 51 8 51 9 52 0 RecoverPoint StartPoint StopPoint Rated Output Power kW Grid Frequency Hz Hysteresis mode 8 5 2 1 Over frequency Response DRM OFF PowerLimit VoltageRT Sunspec OFF Definition of Over frequency Response Parameters StartPoint Stop...

Page 49: ...the corresponding parameters The reac ve power regula on func on is disabled The PF is fixed at 1 000 OFF Mode Adjust reac ve power output in ReactiveP The power factor PF is fixed and the reac ve power is regulated by the parameter PF The PF ranges from 0 8 leading to 0 8 lagging Leading the inverter is sourcing reac ve power to the grid Lagging the inverter is injec ng reac ve power into the grid ...

Page 50: ...4 Curve QU Setting Back V1 80 0 V2 90 0 V3 110 0 V4 120 0 V5 120 0 V6 120 0 Q1 25 0 Q2 0 0 Q3 0 0 Q4 25 0 Q5 25 0 Q6 25 0 Pic 8 25 Reac ve Power Regula on Curve in Q U Curve Upper Q Pn lnd Lower Q Pn Cap Grid Voltage U1 Q1 U2 Q2 U3 Q3 U4 Q4 U5 Q5 U6 Q6 Q U Mode ...

Page 51: ...de curve Value of Q Pn at point U1 Q1 on the Q U mode curve Value of Q Pn at point U2 Q2 on the Q U mode curve Value of Q Pn at point U3 Q3 on the Q U mode curve Value of Q Pn at point U4 Q4 on the Q U mode curve Value of Q Pn at point U5 Q5 on the Q U mode curve Value of Q Pn at point U6 Q6 on the Q U mode curve 0 130 Rate out power 0 110 VRated 60 60 Q Pn 0 110 VRated 60 60 Q Pn 0 110 VRated 60 ...

Page 52: ... 120 0 P6 120 0 Q1 25 0 Q2 0 0 Q3 0 0 Q4 25 0 Q5 25 0 Q6 25 0 MENU Setup Run Param OK Cancel ActiveP 31 ReactP 0 0 QMode QP PF 1 000 Fun_ISO ON Fun_RCD ON Island OFF Meter ON Limiter OFF Feed_In 0 MPPT Num 6 SelfCheck 20S Pic 8 26 Reac ve Power Regula on Curve in Q P Mode P1 Q1 P4 P4 Q4 P5 P5 Q5 P6 P6 Q6 P Pn P2 P2 Q2 P3 P3 Q3 Upper Q Pn lnd Lower Q Pn Cap ...

Page 53: ...P mode curve Value of Q Pn at point P2 Q2 on the Q P mode curve Value of Q Pn at point P3 Q3 on the Q P mode curve Value of Q Pn at point P4 Q4 on the Q P mode curve Value of Q Pn at point P5 Q5 on the Q P mode curve Value of Q Pn at point P6 Q6 on the Q P mode curve 0 100 Pn 0 100 Pn 0 100 Pn 0 100 Pn 0 100 Pn 0 100 Pn P1 P2 P3 Q1 Q2 Q3 P4 Q4 P5 Q5 P6 Q6 parameter Range descrption 60 60 Q Pn 60 6...

Page 54: ...t at point P4 U4 on the PU mode curve Value of P Pn at point P1 U1 on the PU mode curve Value of P Pn at point P2 U2 on the PU mode curve Value of P Pn at point P3 U3 on the PU mode curve Value of P Pn at point P4 U4 on the PU mode curve 0 110 Pn P1 P2 P3 U1 U2 U3 P4 U4 parameter Range Description 0 150 Vref 0 110 Pn 0 150 Vref 0 110 Pn 0 150 Vref 0 110 Pn 0 150 Vref PU Setting Back U1 0 0 U2 0 0 ...

Page 55: ...5 0 0 Vstop 0 0 PF1 1 000 PF2 1 000 PF3 1 000 PF4 1 000 PF5 1 000 PFP Setting Back P6 0 0 Time 0s PF6 1 000 Pic 8 28 Power factor Regula on Curve in PF P Mode PF lagging PF leading P Pn P1 P1 PF1 P2 P2 PF2 P3 P3 PF3 P4 P4 PF4 P5 P5 PF5 P6 P6 PF6 PF P Mode 53 ...

Page 56: ...n Power value at point P3 PF3 on the PF P Curve 0 8 leading 0 8 lagging PF value at point P3 PF3 on the PF P Curve 0 110 Pn Power value at point P4 PF4 on the PF P Curve 0 8 leading 0 8 lagging PF value at point P4 PF4 on the PF P Curve 0 110 Pn Power value at point P5 PF5 on the PF P Curve 0 8 leading 0 8 lagging PF value at point P5 PF5 on the PF P Curve 0 110 Pn Power value at point P6 PF6 on t...

Page 57: ...4105 UTE_C15 RD_1699 CEI_0_21 G98_G99 AS4777 NBT32004 CUSTOM AC OverVoltage 1 270 0V Tripping Time 1 100ms AC OverVoltage 2 300 0V Tripping Time 2 100ms AC OverVoltage 3 300 0V Tripping Time 3 100ms CUSTOM AC LowVoltage 1 176 0V Tripping Time 1 100ms AC LowVoltage 2 176 0V Tripping Time 2 100ms AC LowVoltage 3 176 0V Tripping Time 3 100ms 55 ...

Page 58: ...verFreq 1 52 00Hz Tripping Time 1 2000ms AC OverFreq 2 53 00Hz Tripping Time 2 500ms AC OverFreq 3 54 00Hz Tripping Time 3 200ms CUSTOM AC LowFreq 1 48 00Hz Tripping Time 1 2000ms AC LowFreq 2 47 00Hz Tripping Time 2 500ms AC LowFreq 3 46 00Hz Tripping Time 3 200ms 56 ...

Page 59: ...r Unkonw BaudRate 9600 MENU Setup Protect Param OK Cancel INMETRO EN50549 EN50438 IEC61727 CUSTOM VED_4105 UTE_C15 RD_1699 CEI_0_21 G98_G99 AS4777 NBT32004 Pic 8 30 AS4777 MENU Setup Protect Param AS4777 2 Australia A AS4777 2 Australia B AS4777 2 Australia C AS4777 2 New Zealand 57 ...

Page 60: ...ing energy into the grid The alarm descrip on and their corresponding alarm messages are listed Table 10 1 Warning When the device is running the local temperature is too high and the touch can cause burns Turn off the inverter and wait for it cooling then you can clean and maintain Warning No solvent abrasive materials or corrosive materials can be used for cleaning any parts of the inverter Inver...

Page 61: ...king mode changed Grid mode changed 1 Lost of one phase or AC voltage detec on circuit or relays not closed old inverter not have relays detec on func on 2 Restart the inverter if the error s ll exists please contact your installer or Deye service F20 DC over current fault of the hardware 1 Check whether solar panel output current is within the allowed range 2 Check DC current sensor and its detec...

Page 62: ...0 AC main contactor failure 1 Check relays and AC voltage of relays 2 Check relays driver circuit Check if the so ware is not suitable for this inverter Old inverter not have relays detec on func on 3 Restart the inverter if the fault s ll exists contact your installer or Deye service F23 AC leakage current is transient over current 1 This fault means the leakage current is above 30mA suddenly Che...

Page 63: ...tage protec on se ng And Check if the AC cable is too thin Check the voltage difference between LCD and meter F42 AC Line W U low voltage Check the AC voltage protec on se ng Check the voltage difference between LCD and meter Also need to check whether AC cables are all firmly and correctly connected F44 AC Line V W low voltage Check the AC voltage protec on se ng Check the voltage difference between ...

Page 64: ...appened so far F60 AC grid W over current Hardly appear the code Never ever happened so far F61 Reactor A phase over current Hardly appear the code Never ever happened so far F62 Reactor B phase over current Hardly appear the code Never ever happened so far Error code Description Ongrid Three Phase Table10 1 Error codes and their solu ons F64 IGBT heat sink high temperature 1 Check temperature sen...

Page 65: ... 3 175 4A 193 8 215 3 207 5 230 6 221 2 245 8 248 9 276 6 276 6 307 3 304 3 338 1 DC Injec on Current mA Grid Frequency Range Max Efficiency Euro Efficiency 99 MPPT Efficiency Efficiency General Data Output Power Factor 0 5 47 52 or 57 62 op onal 98 8 98 7 98 3 0 8 leading to 0 8 lagging 3 Grid Current THD 838 568 324 838 568 346 Transformerless Size mm W H D 81 Weight kg Topology 1W Night Internal consum...

Page 66: ...MC 4 mateable DC Connec on IP65 rated plug AC Connec on LCD1602 Display RS485 RS232 Wifi LAN Interface General Data 64 2022 07 01 Ver 2 3 ...

Page 67: ...Add No 26 30 South Yongjiang Road Beilun 315806 Ningbo China Fax 86 0 574 8622 8852 Tel 86 0 574 8622 8957 E mail service deye com cn Web www deyeinverter com ...

Reviews: