![Devatec ElectroVap Technical Manual Download Page 56](http://html.mh-extra.com/html/devatec/electrovap/electrovap_technical-manual_2488611056.webp)
ElectroVap RTH-V2
56
Pictures and values are not contractual - The devices may be subject to changes without notice
6 - Maintenance
RTH 5 TO 50
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
1.
Drain the tank out by pressing the manual drain button (s.a.
picture n°1). Wait for complete draining and allow the tank to cool
down (if this feature has been enabled).
2.
Cut off the power supply in the power switch-board and switch off
the RTH humidifier with the rock button (Fig. 1).
3.
Remove the door and unscrew the clamps. Completely remove
the steam hose (Fig. 2) and remove it from the device.
4.
Unscrew the black knob located in the lower part of the tank.
Uncouple the drain hose by loosening the union (Fig. 3-a) and the
water supply hose on the tank (Fig. 3-b).
5.
Now you can tilt the tank to its intermediate position (Fig. 4).
6.
Detach the 4 closing clips of the tank - 2 on the front and 2 on the
back (Fig. 5).
7.
Disconnect the cables from the water level sensor, unscrew the
retaining collar of the pressure equalizing tube and disconnect it
from the tank cover (Fig. 6).
a
b
6.1 STAINLESS STEEL TANK