38
ElectroVap RTH-LC
Valves maintenance
Maintenance
Drain valve maintenance
To be made at each tank maintenance
x
Press the manual drain button, then switch the
humider off.
x
Lift the boiler a little from its base.
x
Unscrew screw 1, remove coil 2 and unscrew
moving part 4.
x
Flush clear water inside valve body 6.
x
Clean up valve 5 and rinse actuator 3.
x
Reassemble. Take care to place back spring. Wa-
tertightness is made by O ring.
1
2
3
4
5
6
Inlet valve maintenance
Turn the water supply off and switch the hu-
midifier off.
x
Remove water inlet hose 1, then screw 2.
x
Take out filter 3 with a pair of pliers and
flush it with clear water.
x
Pull coil 4 out with the help of a small
screwdriver.
x
Flush the internal part of valve body 5
with clear water.
x
Change parts if needed.
x
Reassemble. Do not forget to insert 0
ring 6.
1
2
3
4
5
6
During maintenance of your humidifier,
all clamps should be checked and re-
tightened if needed.
During maintenance of your
humidifier, all clamps should
be checked and retightened
if needed.