Devair DRD 200 Instruction Manual Download Page 4

4

1.6 Electronic Demand Drain

Installation

1.

Remove Service Panel by removing two shipping
screws and turning (2) Quick Release Locks.

2.

Reach inside and remove screws on Separator/filter
shipping support bracket and remove bracket.

3.

Reach behind filter and cut plastic shipping strap
holding Energy Saving Demand Drain.

4.

Insert Demand Drain into brass quick disconnect on
bottom of Separator/filter.

5.

Remove manual petcock from drain hose and mount
into manual outlet drain connection on outside of side
panel.

Operation

A.  Verify that isolation valves are open. If the drain fails to

discharge after the valve is energized, the electronic
control circuit will repeatedly energize the valve in an
attempt to clear the discharge port.  If, after 60 sec-
onds, the drain still fails to discharge, the control circuit
then switches to the alarm mode.  In this mode the
valve is de-energized and the red alarm light is activated
on the drain and the dryer controller. The valve is then
automatically energized every 4 minutes for 5 seconds.
Check the drain operation. Push drain (push-to-test)
button on the emm Energy Management Monitor
control board to energize drain. A flow of condensate
and/or air should be present at the drain outlet. The
alarm mode automatically clears after the drain returns
to normal operation.

B.  Condensate enters the reservoir 

(1)

 through the inlet

port. When the condensate level in the reservoir covers
the capacitance sensor, an electronic signal is sent to
the solid state countdown processor.  The processor
delays the opening of the solenoid valve for a given
period of time.  Once the time has elapsed, the solid
state processor transmits information to energize the
coil in the solenoid valve 

(2)

.The magnetic force of the

coil causes the solenoid core

(3)

 to move, closing the

pilot air supply line and opening the pilot air exhaust
line. After the pilot air above the diaphragm 

(4)

 is

vented, pressure in the reservoir opens the discharge
port and forces the condensate through the discharge
port and outlet piping.

1.2 Mounting

Mount on floor or shelf free from vibration.

1.3 Piping connections

A.

Air Inlet—Connect compressed air line from air
source to air inlet.

          Refer to Serial Number Tag for maximum

working pressure. Do not exceed dryer’s Maximum
Working Pressure.

NOTE: Install dryer in air system at highest pressure
possible (e.g. before pressure reducing valves).

NOTE: Install dryer at coolest compressed air temperature
possible. Maximum inlet compressed air temperature:
120

°

F (49

°

C). If inlet air exceeds this temperature, precool

the air with an aftercooler.

B.

Air Outlet—Connect air outlet to downstream air lines.

C.

By-pass piping—If servicing the dryer without
interrupting the air supply is desired, piping should
include inlet and outlet valves and an air by-pass valve.

D.

Water cooled models—cooling water inlet and outlet
1.

Connect cooling water supply to cooling
water inlet.

2.

Connect cooling water return line to cooling
water outlet connection.

NOTE: Strainer and water regulating valve are supplied on
water cooled models.

1.4 Electrical connections

IMPORTANT: Use copper supply wires only.

A.

Dryer is designed to operate on the voltage, phase,
and frequency listed on the serial number tag.

B.

Connect power source to terminal strip in electrical
enclosure.

NOTE: Refrigeration condensing unit is de-
signed to run continuously and should NOT be
wired to cycle on/off with the air compressor.

1.5 Moisture separator

A.

An automatic electric demand drain (EDD)
discharges condensate removed by the
separator. It may be desirable to pipe the
condensate from the EDD outlet to a
suitable drain.

B.

For manual draining, convenient dryer depressuriza-
tion, and EDD service, a three-way valve at the bottom
of the moisture separator and before the EDD is
installed. For manual draining, turn the valve handle
so it is in a horizontal position. Open the petcock on
the side of the dryer base pan to discharge the
condensate or to depressurize the dryer if it has been
by-passed. The petcock can be left in a throttled
(partially opened) position should there be a problem
with EDD.

NOTE: Discharge is at system pressure. Drain line should
be anchored.
NOTE: Condensate may contain oil. Comply with applicable
laws concerning proper disposal.

2.0  OPERATION

2.1 Minimum/Maximum operating conditions

A.

Maximum inlet air pressure: refer to dryer serial
number tag

B.

Minimum inlet air pressure: 30 psig (2.1 kgf/cm

2

)

C.

Maximum inlet air temperature: 120

°

F (49

°

C)

D.

Maximum ambient temperature:

Air-cooled models: 110

°

F (43

°

C)

Water-cooled models: 130

°

F (54

°

C)

E.

Minimum ambient temperature: 45

°

F (7

°

C)

1

2

3

4

For Sales & Service Call:  705-722-5747  Ext.1

Summary of Contents for DRD 200

Page 1: ...NTENANCE 6 SIZING 6 ENGINEERING DATA 7 ELECTRICAL SCHEMATICS 8 DIMENSIONS WEIGHTS 9 TROUBLESHOOTING 10 PARTS LIST 11 WARRANTY 12 SERVICE DEPARTMENT 724 746 1100 7610 530 11A 9 01 Refrigerated Compressed Air Dryers Models DRD 200 250 300 400 500 750 Instruction Manual c For Sales Service Call 705 722 5747 Ext 1 ...

Page 2: ...carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found upon unpacking ...

Page 3: ...r cooled 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this and has not been preset at the factory for this altitude contact manufacturer s Service Department NOTE Outdoor installation Standard units are designed for indoor installation Contact manufactu...

Page 4: ...imum working pressure Do not exceed dryer s Maximum Working Pressure NOTE Install dryer in air system at highest pressure possible e g before pressure reducing valves NOTE Install dryer at coolest compressed air temperature possible Maximum inlet compressed air temperature 120 F 49 C If inlet air exceeds this temperature precool the air with an aftercooler B Air Outlet Connect air outlet to downst...

Page 5: ...cy of service Typically element changeout is recommended at least annually e Push Set Run button again to exit Set Mode NOTE If dryer is left in the Set Mode for longer than 30 seconds Alarm light will illuminate and TIME OUT will appear on the Interface panel Dryer will resume previous operating mode C Starting dryer IMPORTANT Dryer must be energized 24 hours before starting refrigeration compres...

Page 6: ...rm that activates if drain fails to discharge f Check drain operation push Drain push to test button to energize electric drain A flow of condensate and or air should be present at the drain outlet E Using the RS 232 port The RS 232 port is used to monitor dryer operation from a host computer A 1 to 1 DB 9 cable is required to connect dryer and computer For PC connections data is transmitted on pi...

Page 7: ...pliers MODEL 200 250 300 400 500 750 Rated capacity of 60 Hz 200 250 300 400 500 750 air cooled models scfm 50 Hz 170 210 250 340 420 630 TABLE 1 Rated capacity scfm and pressure drop 100 psig inlet pressure 100 F inlet temperature and 100 F ambient temperature Air cooled models water cooled models use 1 15 multiplier if cooling water is below 35 C 95 F Element o ring Separator Element Bowl o ring...

Page 8: ... Max Min voltage 253 187 253 187 253 187 253 187 Rated Load Amps 8 4 11 5 13 6 22 9 Locked Rotor Amps 51 65 5 75 90 Minimum Circuit Ampacity 10 5 16 9 17 1 31 7 Branch Circuit Fuse Size amps 15 20 25 45 Watts 35 F Evaporator 100 F Ambient 1335 1940 2620 3600 Resistance Ohms Three phase Total 1 77 1 256 1 058 0 853 Nominal Voltage 460 3 60 460 3 60 460 3 60 460 3 60 Max Min Voltage 506 414 506 414 ...

Page 9: ...eight lb 405 415 416 457 498 625 LEGEND CON CONTACTOR HTR CRANKCASE HEATER MTR COMPRESSOR 1FU FUSE SECONDARY 2FU FUSE PRIMARY 3FU FUSE PRIMARY 1FM FAN MOTOR 1 2FM FAN MOTOR 2 1FPS FAN PRES SWITCH 1 2FPS FAN PRES SWITCH 2 TC1 DEWPOINT TEMPERATURE T1 TRANSFORMER CONTROL T2 TRANSFORMER HDD BOARD SSMP SOLID STATE MOTOR PROTECTION SOL1 DEMAND DRAIN ELECTRICAL SCHEMATIC NOTE Dimensions and Weights are f...

Page 10: ...ol switch Water cooled Cooling temperature too high flow too low clogged strainer faulty water regulating valve a Hot gas by pass valve requires adjustment a Dryer overloaded b Refrigeration system off or not cooling sufficiently a Drain line restricted or frozen b Drain mechanism faulty Dryer left in the Set Mode for longer than 30 seconds Blow out system with dry air Check valve positions Check ...

Page 11: ...0 111 25 4130 111 28 Low refrigerant pressure switch 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 High refrigerant pressure switch 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 Fan cutout switch 1 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 Fan cu...

Page 12: ...uct based on the original date of purchase and or date of manufacture as outlined above There is no other expressed warranty Implied warranties including those of merchantability and fitness for a particular purpose are limited to one 1 year from date of purchase to the extent permitted by law and any and all implied warranties are excluded This is the exclusive remedy Liability for consequential ...

Reviews: