21.4.15
Instruction manual UNIGATE
®
IC - RS V. 2.8
12
Deutschmann Automation GmbH & Co. KG
Hardware design
3.2
Pinout
Pin
Technical
specifications
Name
Description
Remark
1
5V ± 5% < 200mA
Vcc
+ 5 V voltage supply
optionally also 3,3V
available
2
IN
Logic
-BE
boot enable
3
OUT
Driver
Load out
(SS0-)
strobe signal for synchronous, serial interface
4
OUT
Driver
Data out
(SS1-)
output data for synchronous, serial interface
5
IN
Logic
Data in
(MISO)
input data of the synchronous, serial interface
internally pulled up with
10 k
6
OUT
Logic
Load in
(MOSI)
input data of the synchronous, serial interface;
alternatively strobe signal of the output data
7
OUT
Driver
Clock
(SCK)
clock pulse signal for synchronous, serial interface
8
IN
Reset
-Reset in
reset-input of the IC
internally pulled up with
100 k
9
connected to pin 1
Vcc
+ 5 V voltage supply
10-12 nc
nc
no pin
13
IN
Rx 422 -
input A of 422 (-)
14
IN
Rx 422 +
input B of 422 (+)
galvanically isolated
insulation voltage 1000
Vrms
15
OUT
Tx 422 -
output A of 422 (-)
galvanically isolated
insulation voltage 1000
Vrms
16
OUT
Tx 422 +
output B of 422 (+)
galvanically isolated
insulation voltage 1000
Vrms
17
IN
Rx 232
serial fieldbus data Rx
galvanically isolated
insulation voltage 1000
Vrms
18
OUT
Tx 232
serial fieldbus data Tx
galvanically isolated
insulation voltage 1000
Vrms
19
FB Vcc (5V)
FB Vcc
FB Vcc (optionally CTS 232)
galvanically isolated
insulation voltage 1000
Vrms
20
FB GND
RSGND
ground reference FB RS
(optionally RTS 232)
galvanically isolated
insulation voltage 1000
Vrms
21-23 nc
nc
no pin
24
connected to pin 32 GND
ground supply voltage of the IC
25
OUT
Logic
LED-PB
bus error LED of the PROFIBUS
26
IN
Logic
-Config Mode signal to start the configuration mode
internally pulled up with
10 k
27
OUT
Logic
DbgTX
serial Debug TX
28
IN
Logic
DbgRX
serial Debug RX
internally pulled up with
10 k
29
IN
Logic
RX
serial data RX
internally pulled up with
10 k
30
OUT
Logic
TX
serial data TX
31
OUT
Logic
TE
transmit enable
32
GND
GND
ground supply voltage of the IC
The bus signals are galvanically isolated. The insulation voltage is 1000 Vrms.
Summary of Contents for UNIGATE IC-RS
Page 5: ...Deutschmann Automation GmbH Co KG 5 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Page 7: ...Deutschmann Automation GmbH Co KG 7 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Page 51: ...Appendix Deutschmann Automation GmbH Co KG 51 Instruction manual UNIGATE IC RS V 2 8 21 4 15...
Page 52: ...21 4 15 Instruction manual UNIGATE IC RS V 2 8 52 Deutschmann Automation GmbH Co KG Appendix...
Page 57: ......
Page 58: ......