Implemented protocols in UNIGATE CL with Universal Script
Deutschmann Automation GmbH & Co. KG
22
UNIGATE fieldbus gateway UNIGATE CL - ProfibusDP V. 2.3
17.6.10
10 Implemented protocols in UNIGATE CL with Universal
Script
UNIGATE CL is supplied with the Script “Universal Script Deutschmann“. The configuration of
the protocols is carried out by means of the software WINGATE.
Attention:
The "Universal Script" will get lost and has to be input again if a Reset
Device is carried out.
The Script can be found on the Deutschmann Support-CD in the folder
\Software\ProtocolDeveloper\Example\Universal\
10.1 Protokoll: Transparent
The data is transferred bidirectional from the UNIGATE.
10.1.1 Data structure
On the RS-entry side the timeout time of 2 ms is firmly set. If no more data is received within the
timeout period, then the data that has been received so far is transferred to the bus.
If less data is received through Rx then configured by the GSD-file (I/O-length), then the rest is
complemented with ZERO.
Too much data received will be cut off.
10.2 Protocol: Universal 232
The protocol designation "Universal 232" and the relation to the
"RS232-interface" in the description have eveloped over the years. The
protocol also works with RS422 and RS485 though!
10.2.1 Data structure
10.2.2 Fieldbus parameters
Trigger byte: See "The trigger byte", Chapter 10.5‚ on page 27
Length byte: See "The length byte", Chapter 10.6‚ on page 27