Hardware ports, switches and LEDs
For the operation at a 485-interface the two pins labeled "485-" have to
be connected together.
Also the two pins "485+".
11.2.2 Connector supply voltage and DEBUG-interface
Pin assignment X2 (4-pole screw-plug connector, on the bottom side, at the back)
Attention:
At isolated devices (option GT) Ground for the DEBUG-Interface must be
connected with pin 3 (AP-GND) of the RS-interface!
At devices that are not isolated also the 0V (Pwr)-signal can be used as
reference.
11.2.3 MPI-bus-connector
The plug (labeled: MPI) for the connection to the MPI-bus is available on the front side of the
device.
Pin assignment (9-pole D-SUB, socket)
11.2.4 Power supply
The device must be powered with 10-33 VDC, The voltage supply is made through the 4-pole
screw-plug connector at the device’s bottom side.
Please note that the devices of the series UNIGATE should not be operated with AC voltage.
11.3 LEDs
The Gateway UNIGATE
®
CL - MPI features 9 LEDs with the following significance:
Pin No.
Name
Function
1
UB (Pwr)
10..33 V supply voltage / DC
2
0 V (Pwr)
0 V supply voltage / DC
3
Rx-Debug
Receive signal Debug
4
Tx-Debug
Transmit signal Debug
Pin No.
Name
Function
1
Shield
2
3
B
Not inverting input-/output-signal from the MPI-bus
4
CNTR-P
Control signal / repeater
5
M5
DGND-data reference potential
6
P5
5 V supply voltage
7
8
A
Inverting input-/output-signal from MPI-bus
9
LED (Bus) Power
green
Supply voltage MPI-bus
LED Bus
green
MPI-bus-error
LED (Bus) State
red/green
Interface state Mpi-bus
LED Power
green
Supply voltage serial interface
LED State
red/green
User-defined / general Gateway error
LEDs 1 / 2 / 4 / 8 (Error No. / Select ID) green
User-defined / general Gateway error