INSTALLATION INSTRUCTIONS
AIR HANDLER : AHF
8
Specifications subject to change without notice.
X40159 Rev. E
6. Refer to the Air Flow Data,
Table 4
, to find the speed setting that
will most closely provide the required air flow for the system.
7. Refer to Motor Speeds and Airflow in these instructions if the
speed is to be changed.
8. Recheck the external static pressure with the new setting, and
confirm speed switch selection.
TEMPERATURE RISE CHECK
Temperature rise is the difference between the supply and return air
temperatures.
NOTE:
The temperature rise can be adjusted by changing the
heating speed tap at the unit’s blower terminal block. Refer to the
unit’s
Installation Instructions
for airflow information.
A temperature rise greater than 60
°
F (33.3
°
C) is not
recommended.
1. To check the temperature rise through the unit, place
thermometers in the supply and return air ducts as close to the
unit as possible,avoiding direct radiant heat from the heater
elements.
2. Open
ALL
registers and duct dampers.
3. Set thermostat Heat-Cool selector to
HEAT
.
4. Set the thermostat temperature setting as high as it will go.
5. Turn electric power
ON
.
6. Operate unit
AT LEAST
5 minutes, then check temperature rise.
NOTE:
The maximum outlet air temperature for all models is 200°F
(93.3°C).
7. Set thermostat to normal temperature setting.
8. Be sure to seal all holes in ducts if any were created during this
process.
Airflow Based on no coil, no filter, no electric heat. Deduct heater static shown in heater static table.
Deduct coil static, See Coil Specification Sheet.
Deduct .20 in wc (50 Pa) for Downflow Subbase Kit.
Table 4
Airflow is blower only, no coil attached
AHF08
In wc
SPEED
VOLTS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
Low
230v
1029
1020
1007
985
960
915
862
208v
872
860
845
825
797
765
721
Med
230v
1286
1270
1254
1220
1180
1125
1058
208v
1113
1105
1091
1070
1042
1000
947
High
230v
1500
1470
1432
1380
1315
1250
1168
208v
1317
1305
1286
1255
1220
1170
1008
AHF12
In wc
SPEED
VOLTS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
Low
230v
973
975
979
979
973
955
931
208v
811
815
816
810
797
780
749
Med
230v
1284
1295
1301
1305
1302
1280
1246
208v
1084
1084
1084
1090
1089
1065
1030
High
230v
1663
1670
1671
1655
1631
1585
1519
208v
1383
1385
1390
1390
1383
1365
1328
AHF16
In wc
SPEED
VOLTS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
Low
230v
1020
1015
1009
1002
991
975
950
208v
858
845
830
815
801
780
749
Med
230v
1379
1385
1386
1379
1364
1343
1309
208v
1156
1154
1149
1144
1134
1120
1098
High
230v
1776
1782
1783
1765
1736
1698
1643
208v
1496
1496
1496
1495
1495
1470
1433
AHF20
In wc
SPEED
VOLTS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
Low
230v
1492
1495
1492
1475
1451
1395
1308
208v
1246
1245
1238
1225
1203
1175
1125
Med
230v
1969
1955
1935
1890
1818
1700
1570
208v
1641
1640
1633
1615
1584
1510
1406
High
230v
2696
2600
2492
2350
2192
2020
1844
208v
2417
2355
2287
2200
2092
1940
1774
* THE MAXIMUM EXTERNAL STATIC PRESSURE I
S 0.8’’ W.C., WITHOUT COOLING COIL. DEDUCT STATIC PRESSURE OF COIL
FOR MAXIMUM STATIC PRESSURE.
Figure
13
Static Pressure Check
Supply
Indoor
Section
Incline
Manometer
Return